Rev 23 to AR-402, PSA G Annunciator Response
ML20197H137
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 12/20/1997
From:
FLORIDA POWER CORP.
To:
References
AR-402, NUDOCS 9712310199
Download: ML20197H137 (91)


Text

__--

Document Transmittal #: 80384 Date: 12/20/97 To:

NRC (DC DESK)

MAC: N/A Destination:

==

Description:==

Copy Copy Totals Document:

Revision:

Comment:

INFO CNTL MSTR AR0402 23 24 1

0 0

instmctions to the Addressee:

Please verify the document (s) received agrees with the above information.

Operations department must attach old document (s) or portions of document (s) superseded by the above to this transmittal.

[f The signature Indicates acknowledgment of receipt of the above document (s) and that documents have j

been updated, Retum signed and dated transmittal to Document Control within 15 working days of transmittal date to mail code:

NA1C

/'

  • Florda Power Corporatgm

'l t

t

!j ' h - }

s -

-\\

Document controf, NA1C Crystal River Energy Complex i e a 15760 W. Power Lme St.

crystal River, FL 34426-6708

'y, V.L U 4 t '

y Signature of Addrest,00:

Date:

9712310199 971220 PDR ADDCK 05000302 F

PDR

4 Rev. 23 Effective Date /2-00-97 IN ORMATION ONLY ANNUNCIATOR RESPONSE AR-402 FLORIDA POWER CORPORAT7 N CRYSTAL RIVER UNIT 3 PSA G ANNUNCIATOR RESPONSE l

l l

r l

l-APPRGWD BY: Interpretation Contact

.YliA Ekn b f4 f (SIGNATURE ON FILE) / 12!d0/9 7 DATE: I I INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support . ~. - O

r i I i TABLE OF CONTENTS \\ t 1 SECTION PAC 4 i i l 1.0 PURP05E................................................................. 1 1 I 2.0 REFERENCE 5.............................................................. 1 2.1 IN1DENH!ni_!tEFERENCES............................................. 1 2.2 DEVELOPENTAL. REFERENCES............................................ 1 r 3. 0 PERSONNEL. INDOCTRINATION................................................ 2 4.0. INSTRUCTIONS............................................................ 2 5. 0 F01 i nW. UP ACT10NS....................................................... 2 ENCLOSURE 1 Annunciator 4.sponse............................................... 3 P 4 d + O u AR-402-Rev. 23 Page i w.,


et aw-e W

b y a ai, ew 4 w Q- ,+-m- 'egr wP']- 9 de-+" --=wa -ge--P+v--

J.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the I PSA-Y Lampbox. 1.2 Establish operato. actions for valid Annunciator alarms on the PSA-Y Lampbox. 1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the PSA-Y Lampbox. 2.0 REFERrNCES 2.1 IMPLEMEM Sjd REFERENCES 2.1.1 AI-$04, Guidelines for Reduced RCS Inventory 2.1.2 OP-301, Reactor Coolant System 2.1.3 OP-402, Makeup and Purification System 2.1.4 OP-404, Decay Heat System /~') (f 2.1.5 OP-406, Spent Fuel System 2.1.6 OP-418 Demineralized Water System 2.1.7 OP-407J. Operation of Reactor Coolant Drain Tank 2.1.8 E0P, Emergency Operating Procedure 4 2.1.9 AP-470, Loss of Instrument Air 2.1.10 AP-1080, Refueling Canal Level Decrease 2.1.11 Technical Specifications 2.1.12 MAR 92-01-01-02, Demin Upgrade 2.1.13 MAR 92-02-02-OlA, RC Orain Tank Level Setpoint Change 2.2 DEVELOPMENTAL _ REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 ys U AR-402 Rev. 23 Page 1

4 s i 3.0 PERMEL IN 3.1 The An'anciator System is powered from VBDP-5 Breaker 28. 4.O INSTRUCTIONS 4.1 Respond to alarms on the PSA-Y Lampbox as indicated on Enclosure 1 Annunciator Response. 5.0 - FOLLOW-UP ACIIONS None t O O AR-402 Rev. 23 Page 2

i 9 l ENCLOSURE,_1 l',,'; (Page 1 of 87) L_) PSA-G ANNUNCIATOR RESPONSE PSA-Y 01-01 G-01-01 I I STATION l AIR PRESS g LOW I I, I EVENT POINT 0894 INDICATED CONDITION: o STATION AIR PRESSURE IS <90 PSIG AS SENSED BY SA-13-PS / ( REDUNDANT INDICATION WHICH-WILL VERIFY ALARM: o STATION AIR PRESSURE INDICATOR SA-4-PI OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS o ENSURE SAV-647 BACKUP AIR SUPPLY PRESSURE REDUCING VALVE OPEN DISCUSS'ON: STATION AND INSTRUMENT AIR ARE CROSS TIED THROUGH IAV-30. CHECK INSTRUMENT AIR PRESSURE.

REFERENCES:

DRAWING 208-051 SHEET SA-01 SENSING ELEMENT: SA-13-PS AR-402 Rev. 23 Page 3

l ENCLOSURE 1 -w ) (Page 2 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y 01-01 G-O'.-01 I I STATION ~ AIR PRESS LOW l l g I I I I EVENT POINT 0918 INDICATED CONDITION: o IAV-30 CLOSED ,Cl REDUNDAN' 1NDICATION WHICH WILL VERIFY ALARM: o INSTRUMENT AIR PRESSURE <80 PSIG OPERATOR ACTIONS FOR A VALID ALARM: o <. FER TO AP-470 LOSS OF INSTRUMENT AIR o u.SURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS o ENSURE SAV-647 BACKUP AIR SUPPLY PRESSURE REDUCING VALVE OPEN DISCUSSION: IAV-30 WILL AUTOMATICALLY CLOSE WHEN INSTRUMENT AIR PRESSURE IS <80 PSIC AS SENSED BY IA-3-PS. THIS WILL ISOLATE INSTRUMENT AIR FROM STATION AIR. WITH IAV-30 CLOSED INSTRUMENT AIR WILL NOT FEED STATION AIR, BUT STATION AIR WILL FEED INSTRUMENT AIR THROUGH A CHECK VALVE AROUND IAV-30. TO REOPEN IAV-30 ONCE INSTRUMENT AIR PRESSURE HAS BEEN RECOVERED THE IAV-30 CONTROL SWITCH MUST BE TAKEN TO THE CLOSED POSITION AND THEN BACK TO AUTO. ()

REFERENCES:

DRAWING 208-037 SHEET IA-04 L.) SENSING ELEMENT: IA-3-PS, 33-C VALVE POSITION LIMIT AR-402 Rev. 23 Page 4

j t ENCLOSURE 1 -( )_ (Page 3 of 87) %./ - PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 G-01-02 lA/SA COMP TRIP EVENT POINT 0896 INDICATED CONDITION: o SAP-1A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:- o GREEN INDICATING LIGHT ON WITH A RED FLAG ON SAP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: c VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE SAP-1B RUNNING DISCUSSION:- i A HIGH AIR DISCHARGE TEMPERATURE WILL TRIP.THE AIR COMPRESSOR. TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM. 4

REFERENCES:

DRAWING 208-051 SHEET SA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS AR-402 Rev. 23 Page 5 l

ENCLOSURE 1 ,m (a) (Page 4 of 87) PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 G-01-02 IA/SA COMP TRIP 4 EVENT POINT 0902 INDICATED CONDITION: o SAP-1B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o CREEN INDICATING LIGHT ON WITH A RED FLAG ON SAP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE SAP-1A RUNNING DISCUSSION: A HIGH DISCHARGE AIR TEMPERATURE WILL TRIP THE AIR COMPRESSOR. TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-051 SHEET SA-02 ) a (_/ SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS I AR-402 Rev. 23 Page 6 l

8 ENCLOSURE 1 d.

f (Page 5 of 87)

. Q, PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 - G-01-02 IA/SA COMP TRIP EVENT POINT 0908 INDICATED CONDITION: o IAP-1A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICAYION WHICH WILL VERIFY ALARM: o GREEN INDICATING LIGHT ON WITH /s RED FLAG ON IAP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE IAP-1B RUNNING DISCUSSION: A HIGH DISCHARGE AIR TEMPERATURE WILL TRIP THE AIR COMPRESSOR. TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-037 SHEET IA-01 i'v SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS AR-402 Rev. 23 Page 7

ENCLOSURE 1 (Page 6 of 87) PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 G-01-02 I IA/SA COMP TRIP EVENT POINT 0914 INDICATED CONDITION: o IAP-1B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION /~ ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o GREEN INDICATING LIGHT ON WITH A RED FLAG ON IAP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE IAP-1A RUNNING DISCUSSION: A HIGH DISCHARGE AIR TEMPERATURE WILL TRIP THE AIR COMPRESSOR. TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-037 SHEET IA-02 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS AR-402 Rev. 23 Page 8

ENCLOSURE 1 _m (Page 7 of 87) PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-03 G-01-03 lA/SA COMP AUTO START EVENT POINT 0895 INDICATED CONDITION: o SAP-1A BREAKER CLOSED WITH CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION ,, ~ y REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ~ o RED INDICATING LIGHT ON WITH A GREEN FLAG ON SAP-IA CONTROL STATION o STATION AIR PRESSURE <95 PSIG OPERATOR ACTIONS FOR A VALID ALARM: -o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION: INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30, ALL IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE. STARTING THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRtWING 208-051 SHEET SA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS, SA-8-PS 'AR-402 Rev. 23 Page 9

ENCLOSURE 1 w-)- (Page 8 of 87) l PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-03 'G-01-03 lA/SA COMP AUTO START EVENT POINT 0901 INDICATED CONDITION: o SAP-1B BREAKER CLOSED WITH CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION i REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RED INDICATING LIGHT ON WITH A GREEN FLAG ON SAP-1B CONTROL STATION o STATION AIR PRESSURE <95 PSIG OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION: INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30, ALL IN-HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE. STARTING THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-051 SHEET SA-02 SENSING ELEMENT CONTROL SWITCH AND BREAKER CONTACTS, SA-8-PS AR-402 Rev. 23 Page 10 /

~, -, ~ DCLOSURE 1 _,)-

(Page 9 of 87)-

L(:V -PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01 G-01-03 lA/SA COMP AUTO START EVENT POINT 0907. INDICATED CONDITION:- 4 o-IAP-1A BREAKER CLOSED WITH CONTROL HANDLE.IN THE NORMAL AFTER STOP POSITION-REDUNDANT INDICATION WHICH WILT. VERIFY ALARM: o RED INDICATING LIGHT ON WITH A GREEN FLAG IAP-1A CONTROL STATION

o. INSTRUMENT AIR PRESSURE <95 PSIG OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT.-AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION: . INSTRUMENT.AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30, ALL -IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE. STARTING THE COMPRESSOR LOCALLY WILL.ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-037 SHEET IA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAVER CONTACTS, IA-13-PS AR-402 Rev. 23 Page.11

m. ENCLOSURE 1 '{ (Page 10 of 87) PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-03 G-01-03 lA/SA COMP AUTO START EVENT POINT 0913 INDICATED CONDITION: o IAP-1B BREAKER CLOSED WITH CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION r(\\) REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RED INDICATING LIGHT ON WITH A CREbN FLAG ON IAP-1B CONTROL STATION o INSTRUMENT AIR PRESSURS <95 PSIG OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION: INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30, ALL IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE. STARTING THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-037 SHEET IA-02 p._ (, SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS, IA-13-PS AR-402 Rev. 23 Page 12

L ENCLOSURE 1 -(g (Page 11 of 87) v). PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-06 G-01-06 RC DRAIN TANK LEVEL HIGH/ LOW EVENT POINT 1592 INDICATED CONDITION: o RC DRAIN TANK LEVEL IS >114.48" A.S SENSED BY WD-23-LS1 ) REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RC DRAIN TANK INDICATION, WD-23-LI-1 OPERATOR ACTIONS,'OR A VA'_ID ALARM: o PUMP RC DRAIN TANK PER OP-407] m DISCUSSION: RC PUMP SEAL LEAK 0FF, PORV, RC SAFETY VALVES ARE ALL INPUTS TO THE RC DRAIN TANK. INCREASING RCDT LEVELS MAY INDICATE LEAKING PRIMARY RELIEF VALVES OR DEGRADING RC PUMP SEALS / \\

REFERENCES:

DRAWING 208-060 SHEET WD-19 'd SENSING ELEMENT: WD-23-LS1 AR-402 Rev. 23 Page 13

EHCLOSURE 1 / (Page 12 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-06 G-01-06 RC DRAIN TANK LEVEL HIGH/ LOW EVENT POINT 1593 INDICATED CONDITION: o RC DRAIN TANK LEVEL IS <90.16" AS SENSED BY WD-23-LS1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RC DRAIN TANK INDICATION, WD-23-LI-3 OPERATOR ACTIONS FOR A VALID ALARM: o RESTORE RC DRAIN TANK LEVEL PER OP-407] DISCUSSION: RC DRAIN TANK PUMP WILL TRIP IF RC DRAIN TANK IS <91.20" as sensed by WD-23-LS2

REFERENCES:

DRAWING 208-060 SHEET WD-19 SENSING ILEMENT: WD-23-LS1 AR-402 Rev. 23 Page 14

ENCL 0iEE_1 ,m ( ) (Page 13 of 87) \\_/ PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 I I I RC INVENTORY g LOW EVENT POINT 0081 INDICATED CONDITION: o RCS LEVEL IS <129' AS SENSED BY RC-201-LS REDUNDANT INDICATION WHICh WILL VERIFY ALARM: oRCSLEVELINDICATION,RC-201-LI1,Rk-201-LI2,RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM: o RESTORE RCS LEVEL PER OP-301, OP-402, AND/OR OP-404 j o REFER TO AI-504 DISCUSSION: l DURING PERIODS OF LOW RCS LE\\'EL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION t

REFERENCES:

DRAWING 208-047 SHEET RC-27 ,s ~, SENSING ELEMENT: RC-201-LS AR-402 Rev. 23 Page 15

ENCLOSURE 1 (Page 14 of 87) V PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 RC INVENTORY LOW EVENT POINT 0794 INDICATED CONDITION: o RCS LEVEL IS <146'-5.8" AS SENSED BY RC-1638-LS1A REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RCS LEVEL INDICATION, RC-201-LI1, RC-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM: o RESTORE RCS LEVEL PER OP-301, OP-402, AND/OR OP-404 o REFER TO AI-504 DISCUSSION: DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION

REFERENCES:

~ DRAWING 208-047 SHEET RC-27 ,s V SENSING ELEMENT: RC-1638-LS1A AR-402-Rev. 23 Page 16

4 ENCLOSURE 1 _ (%{ (Page 15 of 87) y/ PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 RC INVENTORY LOW 88_ _-- EVENT POINT 0795 INDICATED CONDITION: f o RCS LEVEL IS <I46'-5.8" AS SENSED BY RC-1648-LSIA f% i j REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ~ o RCS LEVEL INDICATION, RC-201-LII, RC-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM: o RESTORE RCS LEVEL PER OP-301, OP-402, AND/OR OP-404 o REFER TO AI-504 DISCUSSION: DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION

REFERENCES:

DRAWING 208-047 SHEET RC-27 () SENSING ELEMENT: RC-164B-LS1A AR-402 Rev. 23 Page 17

-8 ENCLOSURE 1 (Page 16 of 87) PSA-G ANNUNCIATOR RESPONSE lPSA-Y-01-08 G-01-08 RC INVENTORY - LOW EVENT POINT 1684 INDICATED CONDITION: o RCS LEVEL IS <129' AS SENSED BY RC-202-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RCS LEVEL INDICATION, RC-201-LII, RC-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM: o RESTORE RCS LEVEL PER OP-301, OP-402 AND/0R OP-404 o REFER TO AI-504 DISCUSSION: DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION.

REFERENCES:

DRAWING 208-047 SHEET RC-27 SENSING ELEMENT: RC-202-LS AR-402 Rev. 23 Page 18

EHCLOSURE-1 (Page 17 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 RC INVENTORY LOW EVENT POINT 2046 INDICATED CONDITION: o RCS LEVEL IS <146'-5.8" AS SENSED BY RC-163A-LS1A REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RCS LEVEL INDICATION, RC-201-LI1, C-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM: o RESTORE RCS LEVEL PER OP-301, OP-402 AND/0R OP-404 o REFER TO AI-504 DISCUSSION: DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION l

REFERENCES:

DRAWING 208-047 SHEET RC-27 ( SENSING ELEMENT: RC-163A-LSIA l AR-402 Rev. 23 Page 19 I

ENCLOSURE 1 T)N-( (Page 18 of 87) PSA-C ANNUNCIATOR RESPONSE PSA-Y 02-01 G-02-01 I I INSTRUMENT l l AIR PRESS l l LOW l l I I EVENT POINT 0906 INDICATED CONDITION: o INSTRUMENT AIR PRESSURE IS <90 PSIG AS SENSED BY IA-18-PS 3 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l-oINSTRUMENTAIRFRESSUREINDICATORkA-4-PI OPERATOR ACTIONS FOR A VALID ALARM: ~ o REFER TO AP-470 o ENSURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS o ENSURE SAV-647 BACKUP AIR SUPPLY PRESSURE REDUCING VALVE OPEN DISCUSSION: .NSTRUMENT AIR PRESSURE <90 PSIG WILL ALSO DE-ENERGIZE IADR-2. THE DRIER MUST BE RESET LOCALLY WHEN INSTRUMENT AIR PRESSURE IS RESTORED.

REFERENCES:

DRAWING 208-037 SHEET IA-01 (f SENSING ELEMENT: IA-18-PS AR-402 Rev. 23 Page 20

ENCLOSUAE_1 c ( (Page 19 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 IA/SA COMP DISCH TEMP HIGH EVENT POINT 0898 INDICATED CONDITION: o SAP-1A DISCHARGE TEMPERATURE IS >375' F AS SENSED BY SA-11-TS t REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o LOCAL DISCHARGE TEMPERATURES ARE II GH o SAP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. DISCUSSION: IF DISCHARGE t.IR TEMPERATURE REACHES 400* THE COMPRESSOR WILL TRIP HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-051 SHEET SA-01 SENSING ELEMENT: SA-11-TS AR-402 Rev. 23 Page 21

ENCLOSURE 1 (Page 20 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 lA/SA COMP DISCH TEMP HIGH EVENT POINT 0899 INDICATED CONDITION: o SAP-1A AFTER COOLER DISCHARGE TEMPERATURE IS >120' F AS SENSED BY SA-5-TS ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oLOCALDISCHARGETEMPERATURESAREHkCH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DCNN THE COMPRESSOR. o VERIFY PROPER SC FLOW TO.AFTERC00LER 1 DISCUSSION: HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-051 SHEET SA-01 (v SENSING ELEMENT: SA-5-TS AR-402 Rev. 23 Page 22

ENCLOSURE 1 (Page 21 of 87) -PSA-G ANNUNCIATOR RESPONSE PSA-Y-02 G-02-02 lA/SA COMP DISCH TEMP HIGH EVENT POINT 0904 INDICATED CONDITION: o SAP-1B DISCHARGE TEMPERATURE IS >375' F AS SENSED BY SA-12-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o LOCAL DISCHARGE TEMPERATURES ARE HIGH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. DISCUSSION: IF DISCHARGE AIR. TEMPERATURE REACHES 400* THE COMPRESSOR WILL TRIP HIGH DISCHARGE TEMPERATURES INDICATE AN AIR-COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-051 SHEET SA-02 SENSING ELEMENT: SA-12-TS M-402 Rev. 23 Page 23

ENCLOSURE 1 A {) (Page 22 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 lA/SA COMP DISCH TEMP HIGH EVENT POINT 0905 INDICATED CONDITION: o SAP-1B AFTER COOLER DISCHARGE TEMPERATURE IS >120' F AS SENSED BY SA-6-TS ( REDUNDANT INDICATION WHICH WILL VERIFY ALAkM: oLOCALDISCHARGETEMPERATURESAREd5GH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. e VERIFY PROPER SC FLOW TO AFTERC00LER DISCUSSION: HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-051 SHEET SA-02 .,d SENSING ELEMENT: SA-6-TS l AR-402 Rev. 23 Page 24

ENCLOSURE 1 (Page 23 of 87) h PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 lA/SA COMP DISCH TEMP HIGH EVENT POINT 0910 INDICATED CONDITION: o IAP-1A DISCHARGE TEMPERATURE IS >350' F AS SENSED BY IA-16-TS Oh REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oLOCALDISCHARGETEMPERATURESAREHIGH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. DISCUSSION: IF DISCHARGE AIR TEMPERATURE REACHES 375', AS SENSED BY IA-14-TS THE COMPRESSOR WILL TRIP HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-01 (v/ SENSING ELEMENT: IA-16-TS -AR-402 Rev. 23 Page 25

ENCLOSURE 1 (] (Page 24 of 87) f.g PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 IA/SA COMP DISCH TEMP HIGH EVENT POINT 0911 INDICATED C0l'DITION: o IAP-1A AFTER COOLER DISCHARGE TEMPERATURE IS >120' F AS SENSED BY IA-6-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ~ o LOCAL DISCHARGE TEMPERATURES ARE HIGH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. o VERIFY PROPER SC FLOW TO AFTERC00LER DISCUSSION: HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-01 (- 'y SENSING ELEMENT: IA-6-TS .AR-402 Rev. 23 Page 26

ENCLOSURE 1 (Page 25 of 87) _ 'y,. PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 IA/SA COMP DISCH TEMP HIGH n EVENT POINT 0916 INDICATED CONDITION: o IAP-18 DISCHARGE TEMPERATURE IS >350' F AS SENSED BY IA-17-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oLOCALDISCHARGETEMPERATURESAREHkCH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. DISCUSSION: IF DISCHARGE AIR TEMPERATURE REACHES 375', AS SENSED BY IA-15-TS THE COMPRESSOR WILL TRIP HICH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR' COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-02 SENSING ELEMENT: IA-17-TS AR-402 Rev. 23 Page 27

ENCLOSURE 1 l (Page 26 of 87) PSA-C ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 L IA/SA COMP DISCH TEMP HIGH EVENT POINT 0917 INDICATED CONDITION: o IAP-1B AFTER COOLER DISCHARGE TEMPERATURE IS >120' F AS SENSED BY IA-7-TS ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oLOCALDISCHARGETEMPERATURESAREHiGH OPERATOR ACTIONS FOR A VALID ALARM: o START STANDBY COMPRESSORS. o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR. o VERIFY PROPER SC FLOW TO AFTERC00LER DISCUSSION: HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-02 D. (,/ SENSING ELEMENT: IA-17-TS AR-402 Rev. 23 Page 28

ENCLOSURE 1 { (Page 27 of 87) q PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-03 G-02-03 lA/SA COMP MOTOR OVERLOAD EVENT POINT 0897 INDICATED CONDITION: o SAP-1A MOTOR AMPS >115% RATED LOAD REQUNDANT INDICATION WHICH WILL VERIFY ALARM: o SAP-1A HIGH MOTOR AMPS o SAP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE PROPER INSTRUMENT AND STATION AIR PRESSURE o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION: ELECTRICIANS SHOUI.D BE INSTRUCTED TO INVESTIGATE MOTOR AND BREAKER OPERATION IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-051 SHEET SA-01 () - SENSING ELEMENT: 49 OVERLOAD RELAY AR-402-Rev. 23 Page 29

ENCLOSURE 1 (~g i ) (Page 28 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-03 G-02-03 lA/SA COMP MOTOR OVERLOAD EVENT POINT 0903 INDICATED CONDITION: o SAP-IB MOTOR AMPS >115% RATED LOAD ,OQ REDUNDANT INDICATIbH WHICH WILL VERIFY ALARM: o SAP-1B HIGH MOTOR AMPS o SAP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE PROPER INSTRUMENT AND STATION AIR PRESSURE o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION: ELECTRICIANS SHOULD BE INSTRUCTED TO INVESTICATE MOTOR AND BREAKER OPERATION. IT IS POSSIBLE TO HAVE THIS A GM PRIOR TO THE PREAKER TRIP.

REFERENCES:

DRAWINC 208-051 SHEET SA-02 (D V SENSING ELEMENT: 49 OVERLOAD RELAY AR-402 Rev. 23 Page 30

l l l LNCLOSURE 1 b) (Page 29 of 87) G PSA-G ANNUNCIATOR RESPONSE P5A-Y-02-03 G-02-03 IAISA COMP MOTOR OVERLOAD EVENT POINT 0909 INDICATED CONDITION: o IAP-1A MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o IAF-IA HICH MOTOR AMPS o IAP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE PROPER INSTRUMENT AND STATION AIR PRESSURL o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION: ELECTRICIANS SHOULD BE INSTRUCTED TO INVESTICATE MOTOR AND BREAKER OPERATION. IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-037 SHEET IA-01 A() SENSING ELEMENT: 49 OVERLOAD RELAY AR-402 Rev. 23 Page 31

l fm BCLOSURE 1 ( ) (Page 30 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-03 G-02-03 lAISA COMP MOTOR OVERLOAD EVENT POINT 0915 l INDICATED CONDITION: o IAP-1B MOTOR AMPS >115% RATED LOAD (O) REDUNDANT INDICATION WHICH W* '. VERIFY ALARM: o IAP-18 HIGH M010R AMPS o IAP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o ENSURf PROPER INSTRUMENT AND STATIC't AIR PRESSURE o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION: ELECTRICIANS SHOULD BE INSTI K TED TO INVESTIGATE MOTOR AND BREAKER OPERATION. IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-037 SHEET IA-02 7, SENSING ELEMENT: 49 OVERL0AD RELAY l AR-402 Rev. 23 Page 32

ENCLOSURE 1 73 ( (Page 31 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-08 G-02-08 ANNUNCIATOR OROUND EVENT POINT 0196 INDICATED CONDITION: o POSITIVE OR NEGATIVE GROUND INDICATION IN ANNUNCIATOR GROUND CABINET (Oj REDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTIONS FOR A VALID ALARM: o CONTACT ELECTRICIANS FOR GROUND TROUBLESHOOTING DISCUSSION: THIS ALARM INDICATES THERE IS " ~ .) IN SOME DC ALARM CIRCUIT. NOTES SHOULD BE MADE OF ALARMS OR CPD JiONS THAT OCCURRED THE SAME TIME THE CROUND CAME IN TO ASSIST T:iE ELECTRICIANS IN FINDING THE CROUND.

REFERENCES:

DWG D1011-121 1 Q SENSING ELEMENT: ANNUNCIATOR PROCESSOR AR-402 Rev. 23 Page 33

f3 CLOSURE 1 (Page 32 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-03-01 G-03-01 I I SUBCOOLING l l MARGIN l l LOW I I I I EVENT POINT 1954 INDICATED CONDITION: o SUBCOOLING MARCIN 15 <30' F AND THE REACTOR IS TRIPPED ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SATURATION MONITOR METERS RC4-TI4[RC4-TIS ~ o RCS - HIGH TEMPERATl'RE AND/OR LOW PRESSURE o SPDS MONITORS OPERATOR ACTIONS FOR A VALID ALARM: o TAKE PROMPT AND APPROPRIATE ACTIONS IN ACCORDANCE WITH REQUIREMENTS OF THE E0P DISCUSSION: THIS ALARM INDICATES A POSSIBLE SATURATED CONDITION IN THE RC5.

REFERENCES:

EC-209-047 RC-12, 205-047 SH. RC 11 (yD x SENSING ELEMENT: RC3A-PT-3 AR-402 Rev. 23 Page 34

MCLOSURE 1 ( (Page 33 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-03-01 G-03-01 I I SUBCOOLING I I MARGIN l LOW l l I I EVENT POINT 1955 INDICATED CONDITION: o SUBC00 LING MARGIN IS <30' F AND THE REACTOR IS TRIPPED REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ~ o SATURATION MONITOR METERS, RC4-TI4, RC4-TIS o RCS - HICH TEMPERATURE AND/OR LOW PRES 5URE o SPDS MONITORS OPERATOR ACTIONS FOR A VALID ALARM: o TAKE PROMPT AND APPROPRIATE ACTIONS IN ACCORDANCE WITH REQUIREMENTS OF THE E0P DISCUSSION: THIS ALARM INDICATES A POSSIBLE SATURATED CONDITION IN THE RCS,

REFERENCES:

SENSING ELEMENT: AR-402 Rev. 23 Page 35

l ENCLOSURE 1 -() (Page 34 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-03-03 G-03-03 BACK UP AIR BOTTLES ON LINE EVENT POINT 0878 INDICATED CONDITION: o BACK UP AIR SUPPLY ON LINE AND SUPPLYING AIR TO IA/SA AS SENSED BY SA-127-PS () REDUNDANT INDICATION WHICH WILL VERIFY ALARM: u STATION AIR PRESSURE < 90 PSIG AS INDICATED BY SA-4-PI OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS o REFER TO AP-470, LOSS OF INSTRUMENT AIR DISCUSSIONS: o CONTACT MAINTENANCE TO RECHARGE BACK UP AIR CYLINDERS OR ORDER NEW CYLINDERS TO REPLACE USED ONES

REFERENCES:

209-051, SA-02 (x j SENSING ELEMENT: SA-127-PS AR-402 Rev. 23 Page 36

e rs ENCLOSURE 1 ( (Page 35 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-01 G-04-01 I I SC PUMP l l TRIP I l l l I l EVENT POINT 0329 INDICATED CONDITION: o SCP-1A BREAKER IS OPEN WITH THE CONTROL HANDLE IN THE NORMAL AFTER START FOSITION. Ci V REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o GREEN LIGHT WITH A RED FLAG ON SCP-1A CONTROL STATION. OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE SCP-1B OPERATING o IF NO SC PUMPS ARE OPERATING CONSIDERATION SHOULD BE CIVEN TO TRIPPING THE MAIN TURBINE. DISCUSSION: THE PUMP WILL TRIP IF EITHER: SCV-1. SCP-1A SUCTION VALVE CLOSES QB SCV-3, SCP-1A DISCHARGE VALVE CLOSES A LOSS OF DC PO*'ER TO SCV-3 WILL CAUSE SCV-3 TO CLOSE.

REFERENCES:

DRAWING 208-052 SHEET SC-01 rs ( SENSING ELEMENT: CONTROL STATION CONTACTS I AR-402 Rev. 23 Page 37

s ENCLOSURE _1 [- (Page 36 of 87) v PSA G ANNUNCIATOR RESPONSE PSA-Y-04-01 0-04-01 I I SC PUMP l l TRIP I I I I I I EVENT POINT 0332 INDICATED CONDITION: o SCP-1B BREAKER IS OPEN WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION. ( REDUNDANT INDICATION WHICH WILL VEdIFY ALARM: o CREEN LIGHT ON WITH A RED FLAG ON SCP-1B CONTROL STATION. OPERATOR ACTIONS FOR A VALID ALARM: o LNSURE SCP-1A OPERATING o IF NO SC PUMPS ARE OPERATING CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE. DISCUSSION: THE PUMP WILL TRIP IF EITHER: SCV-2, SCP-1B SUCTION VALVE CLOSES QB SCV-4, SCP-1B DISCHARGE VALVE CLOSES A LOSS OF DC P(VER TO SCV-4 WILL CAUSE SCV-4 TO CLOSE.

REFERENCES:

DRAWING 208-052 SHEET SC-02 () SENSING ELEMENT: CONTROL STATION CONTACTS 1 AR-402 Rev. 23 Page 38

1 f Et(CLOSURE 1 (Page 37 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-02 G-04-02 SC PUMP MOTOR OVEALOAD EVENT POINT 0327 INDICATED CONDITION: o SCP-1A MOTOR AMP 5 >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SCP-1A HIGH MOTOR AMPS o SCP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o CONSIDERATION SHOULD BE CIVEN TO STARTING SCP-1B AND SECURING SCP-3A o HAVE BREAKER CUBICLE C;;ECKED FOR DROPPED TARCETS DISCUSSION: THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANECUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0t'5 OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER. IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-052 SHEET SC-01 SENSING ELEMENT:74 SCP A OVERLOAD RELAY AR-402 Rev. 23 Page 39

4 4 e EliCLQ5URE 1 3 (Page 38 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-02 G-04-02 SC PUMP MOTOR OVERLOAD EVENT POINT 0330 INDICATED CONDITION: o SCP-IB MOTOR AMPS >I15% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SCP-1B HIGH MOTOR AMPS o SCP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM: o CONSIDERATION SHOULD BE GIVEN TO STARTING SCP-IA AND SECURING SCP-1B o HAVE BREAKEtt CUBICLE CHECKLD FOR DROPPED TARGETS DISCUSSION: THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER. IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-052 SHEET SC-02 SENSING ELEMENT:74 SCP-B OVERLOAD RELAY AR-402 Rev. 23 Page 40

ENCLOSURE 1 (Page 39 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-03 G-04-03 SC SYSTEM TROUBLE EVENT POINT 0333 INDICATED CONDITION: o SC SURCE TANK LEVEL IS >11'6" AS SENSED BY SC-68-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oSCSURGETANKLEVELINDICATOR,SCdO-LI o LOCAL SC SURGE TANK SIGHT CLASS OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE SC SURCE TANK AUTO FILL VALVE, SCV-146 CLOSED, IF NOT, CLOSE MANUAL ISOLATION VALVE, SCV-108 DISCUSSION: SC SURCE TANK AUTO FILL VALVE, 50'-146 OPENS AT 7.5' AND CLOSES AT 10'

REFERENCES:

DRAWING 208-052 SHEET SC-05 m SENSING ELEMENT: SC-68-LS AR-402 Rev. 23 Page 41

GCLOSME_1 (Pa;;e 40 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-03 G-04-03 SC SYSTEM TROUBLE EVENT POINT 0334 INDICATED CONDITION: o SC SURGE TANK LEVEL IS <6' AS SENSED BY SC-68-LS ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oSCSURGETANKLEVELINDICATOR,SC-5-LI o LOCAL SC SURGE TANK SIGHT CLASS OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE SC SURGE TANK AUTO FILL VALVE, SCV-146 OPEN, IF NOT, MANUALLY OPEN SCV-146. o INSPECT SC SYSTEM FOR LEAKAGE INCLUDING THE TEMPORARY SAMPLE MANIFOLD BEHIND THE NA0 0FFICE. DISCUSSION: IF SC SURGE TANK LEVEL CANNOT BE RESTORED CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE TURBINE. SC SURGE TANK AUTO FILL VALVr, SCV-146 OPENS AT 7.5' AND CLOSES AT 10'

REFERENCES:

DRAWING 208-052 SHEET SC-05 (h / / SENSING ELEMENT: SC-68-LS AR-402 Rev. 23 Page 42

EffCLOSURE 1 (Page 41 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-03 G-04-03 SC SYSTEM TROUBLE EVENT POINT 0335 INDICATED CONDITION: o SC SYSTEM PRESSURE IS <50 PSIG AS SENSED BY SC-89-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o LOCAL SC SYSTEM PRESSURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE BACKUP SC PUMP AUTO STARTS o IF SC SYSTEM PRESSURE CANNOT BE RECOVERED THEN CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE. DISCUSSION: STANDBY SC PUMP SHOULD AUTO START WHEN SC SYSTEM PRESSURE IS <55 PSIG FOR >10 SECONDS.

REFERENCES:

DRAWING 208-052 SHEET SC-03 SENSING ELEMD4T: SC-89-PS AR-402 Rev. 23 Page 43

l GCLOSURE 1 (Page 42 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-04 G-04-04 SC PUMP AUTO START EVENT POINT 0328 INDICATED CONDITION: o SCP-1A BREAKER CLOSED AND CONTROL STATION IS IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oREDLIGHTONWITHAGREENFLAGON}CP-1ACONTROLSTATION OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE PUMP DISCHARGE VALVE OPENS, SCV-3 o VERIFY SC SYSTEM PRESSURE NORMAL o IF NORMAL SC SYSTEM OPERATION IS NOT POSSIBLE THEN CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE. DISCUSSION: STANDBY SC PUMP SHOULD AUTO START WHEN SC SYSTEM PRESSURE IS <55 PSIG FOR >10 SECONDS.

REFERENCES:

DRAWING 208-052 SHEET SC-01 i) SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 23 Page 44

i GCLOSURE 1 s (Page 43 of 87) PSA-C ANNUNCIATOR RESPONSE PSA-Y-04-04 G-04-04 I SC Pt'MP AUTO START EVENT POINT 0331 INDICATED CONDITION: o SCP-1B BREAKER CLOSED AND CONTROL STATION IS IN NORMAL AFTER STOP I REDUNDANT INDICATION WHiCH WP.L VERIFY ALARM: oREDLIGHTONWITHAGREENFLAGONhCP-1BCONTROLSTATION OPERATOR ACTIGNS FOR A VALID ALARM: o ENSURE PUMP DISCHARCE VALVE OPENS, SCV-4 o VERIFY SC SYSTEM PRESSURE NORMAL o IF NORMAL SC SYSTEM OPERATION 15 NOT POSSIBLE THEN CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE. DISCUSSION: STANDBY SC PUMP SHOULD AUTO START WHEN SC SYSTEM PRESSURE 15 <55 PSIG FOR >10 SECONDS. =

REFERENCES:

DRAWING 208-052 SHEET SC-02 7 SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 23 Page 45

t h ENCE05URE 1 ( (Page 44 of 87) v PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-08 G-04-08 EVACUATION TONE GENERATOR FAILURE EVENT POINT 1907 INDICATED CONDITION: o EVACUATION TONE GENERATOR 1 HAS FAILED s l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o EMERGENCY EVACUATION ALARMS WILL NOT OPERATE OPERATOR ACTIONS FOR A VALID ALARM: o NOTIFY ELECTRICIANS DISCUSSION: THIS ALARM INDICATES NO EMERGENCY EVACUATION ALARMS ARE AVAILABLE

REFERENCES:

DRAWING 208-064 SHr.f ME-04 ( SENSING ELEMENT: TONE GEN I. AN0X AR-402 Rev. 23 Page 46

fliCLOSUAL_1 (Page 45 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-08 G-04-08 EVACUATION TONE GENERATOR FAILURE MMNM MMMM EVENT POINT 1918 INDICATED CONDITION: o EVACUATION TONE GENERATOR 2 HAS FAILED REDUNDANT INDICATICi /HICH WILL VERIFY ALARM: o EMERGENCY EVACUATION ALARMS WILL NOT OPERATE OPERATOR ACTIONS FOR A VALID ALARM: o NOTIFY ELECTRICIANS DISCUSSION: THIS ALARM INDICATES NO EMERGENCY EVACUATION ALARMS ARE AVAILABLE

REFERENCES:

DRAWING 208 064 SHEET ME-04 SENSING ELEMENT: TONE GEN #2 AN0X AR-402 Rev. 23 Page 47

ENCloSVRE_1 (Page 46 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-01 C-05-01 V l l DW FROM CR 1 l l WTR QUALITY l l lMPURE I I I I I I EVENT POINT 0809 INDICATED CONDITION: o DFMIN WATER FROM CR-1 HAS ISOLATED REDUNCANT INDICATION WHICH VILL VERIFY ALARM: o DW-346 IS CLOSED o DEMIN WATER SAMPLE PANEL INDICATES HIGH READINGS ON ONE OR MORE OF THE n FOLLOWING: SODIUM SILICA DISSOLVED OXYGEN ORGANIC CARBON CATION CONDUCTIVITY OPERATOR ACTIONS FOR A VALID ALARM: o NOTIFY SECONDARY CHEMISTRY o SUSPEND ALL UNNECESSARY DEMIN WATER USE ) DISCUSSION: DEMIN WATER MAKEUP TO SW AND DC SURGE TANKS IS NOT ISOLATED BY DWV-3(S. MAKEUP SUPPLY TO THE AUX BLDG DEMIN WATER TANK IS UNAVAILABLE AS LONG AS DWV-346 IS CLOSED. UNDEA NORMAL USAGE THIS TANK VOLUME (AT NWL) WILL LAST MORE THAN AN HOUR, THEREFORE IF THERE IS A SIGNIFICANT PROBLEM WITH CR-1/2 DEMIN WATER CHEMISTRY CONSIDERATION SHOULD BE GIVEN TO LINING UP CR-4/5 DEMIN WATER TO THE CR-1/2 SYSTEM. THIS ALTERNATIVE MAY REQUIRE SEVERAL HOURS TO FLUSH THE CROSS TIE LINE FROM CR-4/5. DWV-346 CAN BE MANUALLY OVERRIDDEN TO 1HE OPEN POSITION BY CHEMISTRY (-k

REFERENCES:

DRAWING 208-025 SHEET DW-07 SENSING ELEMENT: 2X DW-32-CR AR-402 Rev. 23 Page 48

ENCLOSURE 1 7-( (Page 47 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-02 G-05-02 DW 5 #ANSFER PP TROUBLE EVENT POINT 1566 INDICATED CONDITION: o WTP-6A OR WP-6B BREAVER CLOSED WITH THEIR CONTROL STATIONS IN NORMAL AFTER STOP. r} RED *JNDANT INDICATION WHICH WILL VERIFY ALARM: o RED LIGHT ON WITH A GREEN FLAG ON THE WTP-6A OR WTP-6B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o CONTACT CR-1 & 2 TO ENSURE PROPER OPERATION OF WTP-6A OR WTP-6B DISCUSSION: THE DEMIN WATER TRANSFER PUMPS WILL AUTO START IF THE RUNNING PUMP TRIPS AND THE STANDBY PUMP IS IN NORf%L AFTER STOP. THE STANDBY PUMP WILL ALSO AUTO START IF A LOW LEVEL IN WTT-1 CLEARS.

REFERENCES:

DRAWING 203-063 SHEET WT-08 ) SENSING ELEMENT: CONTACTS IN THE CONTROL STATION AR-402 Rev. 23 Page 49

[MCLOSURE 1 4 (Page 48 of 87) s PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-02 G-05-02 DW TRANSFER PP TROUBLE i EVENT POINT 1569 INDICATED CONDITION: o WTP-6A OR WTP-6B BREAKER OPEN WITH THEIR CONTROL STATIONS IN NORMAL AFTER START. m REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oCREENLIGHTONWITHAREDFLACONkilEWTP-6AORWTP-6BCONTROLSTATION o LOW LEVEL IN WTT-1, WT-32-LI2 OPERATOR ACTIONS FOR A VALID ALARM: o CONTACT CR-1 & 2 TO ENSURE PROPER OPERATION OF WTP-6A OR WTP-6B o NOTIFY CR-1/2 IF PROBLEM IS WITH LOW TANK LEVEL DISCUSSION: A LOW LEVEL IN CR-1/2 DEMIN WATER 510 RACE TANK WILL TRIP THE DEMIN WATER TRANSTER PUMP. l l f

REFERENCES:

JRAWING 208-063 SHEET WT-08 k SENSING ELEMENT: CONTACTS IN THE CONTROL STATION s AR-402' Rev. 23 Page 50

. __=_ - - r l ENCLOSURE 1 O (Page 49 of 37) l l PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 1 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0244 INDICATED CONDITION: o DWT-1 LEVEL IS <3 FT AS SENSED BY DW-15-LS. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o DVT-1 LOCAL LEVEL SIGHT CLASS \\ OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE AUTOMATIC LEVEL CONTROL VALVE DWV-325 IS OPEN IF NOT, OPEN CONTROL VALVE BYPASS, DWV-329 o MINIMIZE DEMIN WATER USACE IN PLANT DISCUSSION: FILL WATER FOR THE DEMIN WATER STORACE TANK IS SUPPLIED FROM UNITS 1 AND 2 DEMIN WATER TRANSFER PUMP.

REFERENCES:

DRAWING 208-025 SHEET DW-06 f SENSING ELEMENT: DW-15-LS AR-402 Rev. 23 Page 51

c ENCLOSEE._1 ( (Page 50 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0245 INDICATED CONDITION: o DWP-1A/1B DISCHARGE PRESSURE IS <80 PSIG AS SENSED BY DW-6-PS2. O\\Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o DWP-1A/1B LOCAL DISCHARGE PRESSURE INDICATION o STANDBY PUMP AUTO STARTS OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY DWT-1 LEVEL NORMAL. o CHECK AUX BUILDING FOR DW LEAKS o ENSURE PROPER OPERATION OF DW PUMPS RECIRC VALVE, Dav-320 DISCUSSION: IF DW PUMP RECTRC VALVE, DWV-320 IS OPEN CONSIDERATION SHOULD BE GIVEN TO I ISOLATING THE VALVE BY CLOSING DWV-134

REFERENCES:

DRAWING 208-025 SHEET DW-06 (3 U/ SENSING ELEMENT: DW-6-PS2 AR-402 Rev. 23 Page 52

FNCLOSURE 1 [ (Page 51 of 87) \\J PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TT5UBLE EVENT POINT 0246 INDICATED CONDITION: o DWT-1 LEVEL IS >7.5 FT AS SENSED BY DW-17-LS. ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o D*T-1 LOCAL SIGHT CLASS OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY AUTO CONTROL VALVE, DW-325 IS CLOSED IF NOT ISOLATE THE AUTO CONTROL VALVE AND IT'S BYPASS DISCUSSION: DnT-1 MAY BE DRAINED TO THE AUX BUILDING SUMP VIA DW-142 LOCATED ON 143' ELEVATION AUX BUILDING.

REFERENCES:

DRAWING 208-025 SHEET DW-06 C SENSING ELEMENT: DW-17-LS AR-402 Rev. 23 Page 53

ENCLOSURE.1 (Page 52 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0247 INDICATED CONDITION: o DVFL-1 DIFFERENTIAL PRESSURE IS >25 PSID AS SENSED BY DW-9-DPS. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o DWFL-1 LOCAL PRESSURE INDICATION OPERATOR AGIONS FOR A VALID ALARM: o BYPASS AND CHANGE DWFl -1 PER OP-418. DISCUSSION:

REFERENCES:

DRAWING 208-025 SHEET DW-06 l'h () SENSING ELEMENT: DW 9-DPS AR-402 Rw. 23 Page 54

ENCLOSURE 1 p t (Page 53 of 87) P5A-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0248 INDICATED CONDITION: I o DWP-1A BREAKER CLOSED WITH THE CONTROL STATION IN NORMAL AFTER STOP. Aij REDUNDANT INDICATION WHICH WILL VERIFY A8. ARM: oREDLIGHTONWITHAGREENFLAGONhWP-1ACONTROLSTATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER DW SYSTEM OPERATION. o INVESTICATE CAUSE OF AUTO START DISCUSSION: DWP-1A WILL AUTO START WHEN DW PRESSURE IS <100 P3IG AS SENSED BY DW-6-PS1

REFERENCES:

DRAWING 208-025 SHEET DW-01 ,r N !.] SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 23 Page 55

ENCLOSURE 1 l (Page 54 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TRL 'BLE EVENT POINT 0249 INDICATED CONDITION: o DWP-1A BREAKER OPEN WITH THE CONTROL STATION IN NORMAL AFTET START. REDUNDANT INDICATION WHICH WT,LL VERIFY ALARM: oCREENLIGHTONWITHAREDFLAGONhWP-1ACONTROLSTATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY DWP-IB STARTS. o INVESTICATE CAUSE OF TRIP. DISCUSSION: DWP-1A WILL TRIP IF LEVEL IN DWT-1 IS <2 FEET AS SENSED BY DW-14-LS

REFERENCES:

DRAWING 208-025 SHEET DW-01 7( SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 rev. 23 Page 56

e ENCLOSURE 1 (Page 55 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 C-05-03 t AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0250 INDICATED CONDITION: f o DWP-IB BREAKER CLOSED WITH THE CONTROL STATION IN NORMAL AFTER STOP. REDUNDANT INDICATION WHICH WI:1. VERIFY ALARM: o RED LIGHT ON WITH A GREEN FLAG ON DWP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY PROPER DW SYSTEM OPERATION. o INVESTICATE CAUSE OF AUTO START DISCUSSION: DWP-1B WILL AUTO START WHEN DW PRESSURE IS <100 PSIG AS SENSED BY DW-6-PS1

REFERENCES:

DRAWING 208-025 SHEET DW-02 O gh SENSING ELEMENT: CONTROL STATION CONTACTS l l l AR-402 Rev. 23 Page 57 l I:

4 4 ENCLOSURE 1 g (Page 56 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0251 INDICATED CONDITION: o D4P-1B BREAKER OPEN WITH THE CONTROL STATION IN NORMAL AFTER START. t REDUNDANT INDICATION WHICH WILL VERIFV ALARM: o GREEN LIGHT ON WITH A RED FLAG ON DWP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY DWP-1A STARTS. o INVESTIGATE CAUSE OF TRIP. DISCUSSION: DWP-1B WILL TRIP'IF LEVEL IN DWT-1 IS <2 FEET AS SENSED BY DW-14-LS

REFERENCES:

CVWING 208-025 SHEET DW-02 C i, i SENSING ELEMENT: CONTROL STATION CONTACTS I AR-402 Rev. 23 Page 58

l e ENCLOSURE 1 p), (Page 57 of 87) i PSA-C ANNUNCIATOR RESPONSE PSA-Y-06-01 G-06-01 BORIC ACID PP TRIP EVENT POINT 0068 INDICATED CONDITION: o CAP-1A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o CREEN LIGHT ON WITH A RED FLAG ON bP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF PUMP TRIP o IF BORIC ACID PUMP OPERATION IS REQUIRED START CAP-1B DISCUSSION: SHUTTING DOWN CAP-1A LOCALLY WILL CAUSE THIS ALARM TO AGUATE

REFERENCES:

DRAWING 208-010 SHEET CA-01 f SENSING ELEMENT: CONTAGS IN CONTROL STATION AR-402 Rev. 23 Page 59

A ENCLOSURE 1-g t (Page 58 of 87) v PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-01 G-06-01 EORIC ACID PP TRIP 1 EVENT POINT 0069 INDICATED CONDITION: o CAP-1B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION i REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oGREENLIGHTONWITHAREDFLAGONbAP-1BCONTROLSTATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF PUMP TRIP o IF BORIC ACIO PUMP OPERATION IS REQUIRED START CAP-1A DISCUSSION: SHUTTING DOWN CAP-1B LOCALLY WILL CAUSE THIS ALARM.TO ACTUATE

REFERENCES:

DRAWISG 208-010 SHEET CA-02 1 / SENSING ELEMENT: CONTACTS IN CONTROL STATION AR-402 Rev. 23 Page 60

ENCLOSURE 1 ( (Page 59 of 87) L/ PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-02 0-06-02 i* BORIC ACID STOR TNK LEVEL HIGH/ LOW EVENT POINT 0072 INDICATED CONDITION: o CAT-5A LEVEL IS >95" WATER AS SENSED BY CA-11-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-201 o LOCAL TANK LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF HICH LEVEL. o IF BAST FILL IS IN PROGRESS, STOP THE FILL. DISCUSSION: BORIC ACID STORACE TANKS OVERFLOW TO THE 119' FLOOk. IF A SPILL OCCURS NOTIFY HEALTH PHYSICS.

REFERENCES:

DRAWING 208-010 SHEET CA-24 ~ () SENSING ELEMENT: CA-11-LS AR-402 Rev. 23 Page 61

ENCLOSURE 1 (Page 60 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-02 G-06-02 BORIC ACID STOR TNK LEVEL HIGH/ LOW EVENT POINT 0073 INDICATED CONDITION: o CAT-SA LEVEL IS <30" WATER AS SENSED BY CA-11-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-201 o LOCAL TANK LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF LOW LEVEL. o FILL BAST AS REQUIRED. DISCUSSION: THIS CONDITION SHLULD ALSO DE-ENERCIZE THE BAST HEATERS.

REFERENCES:

DRAWING 208-010 SHEET CA-24 SENSING ELEMENT: CA-11-LS AR-402 Rev. 23 Page 62

~ ENCLOSURE 1 (Page 61 of 87) PSA-G ANNbNCIATOR RESPONSE PSA-Y-06-02 G-06-02 BORIC ACID STOR TNK LEVEL HIGH/ LOW EVENT PolNT 0076 INDICATED CONDITION: o CAT-5B LEVEL IS >95" WATER AS SENSED BY CA-13-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-204 o LOCAL TANK LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF HIGH LEVEL. o IF BAST FILL IS IN PROGRESS STOP THE FILL. 4 DISCUSSION: BORIC ACID STORACE TANKS OVERFLOW TO THE 119' FLOOR. IF A SPILL OCCURS NOTIFY HEALTH PHYSICS.

REFERENCES:

DRAWING 208-010 SHEET CA-24 rN kjy SENP NG ELEMENT: CA-13-LS AR-402 Rev. 23 Page 63

l. ENCLOSUP&_1 p) ( (Page 62 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-02 G-06-02 BORIC ACID STOR TNK LEVEL HIGH/ LOW EVENT POINT 0077 INDICATED CONDITION: o CAT-5B LEVEL IS <30" WATER AS SENSED BY CA-13-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-204 o LOCAL TANK LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF LOW LEVEL. o FILL BAST AS REQUIRED. DISCUSSION: THIS CONDITION SHOULD ALSO DE-ENERCIZE THd BAST HEATERS.

REFERENCES:

DRAWING 208-010 SHEET CA-24 b SENSING ELEMENT: CA-13-LS -AR-dO2 Rev. 23 Page 64

ENCLOSURE 1 (Page 63 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 G-06-03 BORIC ACID STOR TNK TEMP HIGH/ LOW EVENT POINT 0070 INDICATED CONDITION: o CAT-5A TEMPERATURE IS >164* F AS SENSED BY CA-10-TSI. REDUNDANT INDICATION WHICH WILL VERIFY ALARMt o COMPUTER POINT X-200 c LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE BAST HEATER, CAHE-3A IN AUTO. o INVESTICATE CAUSE OF HIGH TEMPERATURE. o SECURE BAST HEATERS IF ON. DISCUSSION: THE BAST HEATERS CYCLE ON AT 156' F AND CYCLE OFF AT 162* F.

  • EFERENCES:

DRAWING 208-010 SHEET CA-24 .' :0 \\_/ SENSING ELEMENT: CA-10-TS1 AR-402 Rev. 23 Page 65

ENCLOSURE 1 {')T (Page 64 of 87) y PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 }G-06-03 BORIC ACID STOR TNK TEMP HIGH/ LOW EVENT POINT 0071 INDICATED CONDITION: o CAT-5A TEMPERATURE IS <152' F AS SENSED BY CA-10-TSI. I REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-200 o LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY BAST LEVEL IS >30" WATER. o ENSURE BAST HEATER, CAHE-3A IN AUTO. o INVESTIGATE CAUSE OF LOW TEMPERATURE. o PLACE BAST HEATERS IN ON. DISCUSSION: THE BAST HEATERS CYCLE ON AT 156' F AND CYCLE OFF AT 162' F.

REFERENCES:

DRAWING 208-010 SHEET CA-24 , ) SENSING ELEMENT: CA-10-TS1 l\\ AR-402 Rev. 23 Page 66

4 i ENCLOSURE 1 (Page 65 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 G-06-03 BORIC ACID STOR TNK TEMP HIGH/ LOW EVENT POINT 0074 INDICATED CONDITION: o CAT-5B TEMPERATURE IS >164* F AS SENSED BY CA-12-TSI. ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-203 o LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE BAST HEATER, CAHE-3B IN AUTO. o INVESTIGATE CAUSE OF HIGH TEMPERATURE. o SECURE BAST HEATERS IF ON. DISCUSSION: THE BAST HEATERS CYCLE ON AT 156* F AND CYCLE OFF AT 162* F.

REFERENCES:

DRAWING 208-010 SHEET CA-24 SENSING ELEMEKT: CA-12-TS1 AR-402 Rev. 23 Page 67

ENCLOSURE 1 ( (Page 66 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 G-06-03 BORIC ACID STOR TNK TEMP HIGHILOW I EVENT POINT 0075 INDICATED CONDITION: l o CAT-5B TEMPERATURE IS <152*F AS SENSED BY CA-12-TSI. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o COMPUTER POINT X-203 o LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY BAST LEVEL IS >30" WATER. o ENSURE BAST HEATER, CAHE-3B IN AUTO. o INVESTIGATE CAUSE OF LOW TEMPERATURE. o PLACE BAST HEATERS IN ON. DISCUSSION: THE BAST HEATERS CYCLE ON AT 156* F AND CYCLE OFF AT 162* F. i

REFERENCES:

DRAWING 208-010 SHEET CA-24 SENSING ELEMENT: CA-12-TS1 AR-402 Rev. 23 Page 68

~ e -ENCLOSURE 1 -[ (Page 67 of 87) PSA-C ANNUNCIATOR RESPONSE .PSA-Y-06-04 G-06-04 HEAT TRACING DE-ENERGlZED EVENT POINT 1994 INDICATED CONDITION: o HEAT TRACING FROM ES BUS "A" IS DE-ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oGREENLIGHTONHEATTRACEPANELLkATEDBYESMCC-3A2 OPERATOR ACTIONS FOR A VALID ALARM: o RESET HEAT TRACE CIRCUITS BY DEPRESSING RESET PUSH-BUTTON LOCATED ON HEAT TRACE PANEL NEAR ESMCC-3A2 DISCUSSION: -480V ESA LOCKOUT WILL DE-ENERGIZE HEAT TRACE AND HEAT TRACE WILL NOT BE ABLE TO BE RESET UNTIL THIS LOCK 0UT IS RESET. DEPRESSING THE TEST PUSH-BUTTON ON THE HE.;T TRACE PANEL WILL DE-ENERGIZE HEAT TRACE. THE RESET PUSH-BUTTON WILL HAVE TO BE DEPRESSED TO RE-ENERGIZE THE HEAT TRACE CIRCUITS.

REFERENCES:

DRAWING 208-035 SHEET HT-03 SENSING ELEMENT: 42-1A,2A,3A,4A,5A HEAT TRACE CONTAOS AR-402 Rev. 23 Page 69

t ENCLOSURE 1 ( (Page 68 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-04 G-06-04 HEAT TRACING DE ENEROlZED EVENT POINT 1995 INDICATED CONDITION: o HEAT TRACING FROM ES BUS "B" 15 DE-ENERGIZED ( REDvNDANT INDICATION WHICH WILL VERIFY ALARM: oGREENLIGHTONHEATTRACEPANELLdCATEDON95'BYAUXBLDGELEVATOR OPERATOR ACTIONS FOR A VALID ALARM: o RESET HEAT TRACE CIRCUITS BY DEPRESSING RESET PUSH-BUTTON LOCATED ON HEAT TRACE PANEL NEAR AUX BLDG ELEVATOR ON 95' ELEVATION. DISCUSSION: 480V ESB LOCK 0UT WILL DE-ENERGIZE HEAT TRACE AND HEAT TRACE WILL NOT BE ABLE TO BE RESET UNTIL THIS LOCK 0UT 15 RESET. DEPRESSING THE TEST PUSH-BUTTON ON THE HEAT TRACE PANEL WILL DE-ENERGIZE HEAT TRACE. THE RESET PUSH-BUTTON WILL HAVE TO BE DEPRESSED TO RE-ENERGIZE THE HEAT TRACE CIRCUITS.

REFERENCES:

DRAWING 208-035 SHEET HT-01 SENSING ELEMENT: 42-1B,2B,38,4B HEAT TRACE CONTACTS l AR-402 Rev. 23 Page 70

4 a ENCLOSURE 1 (Page 69 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-05 G-06-05 i GW PUMP TRIP EVENT POINT 1247 INDICATED CONDITION: o GWP-1A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o GREEN LIGHT ON WITH A RED FLAG ON GWP-1A CONTROL STATION. OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE CWP-1B IS OPERATING. o INVESTIGATE CAUSE OF PUMP TRIP. DISCUSSION: STOPPING CWP-1A LOCALLY WILL ACTUATE THIS ALARM A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER BOOSTER PUMPS.

REFERENCES:

DRAWING 208-034 SHEET CW-01 SENSING ELEMENT: CONTACTS IN THE CONTROL STATION AR-402 Rev. 23 Page 71

\\ l ENCLOSURE 1 ( (Page 70 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-05 G-06-05 GW PUMP TRIP EVENT POINT 1249 INDICATED CONDITION: o CWP-18 BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o CREEN LIGHT ON WITH A RED FLAG ON GWP-1B CONTROL STATION. OPERATOR ACTIONS FOR A VALID ALARM: o ENSURE CWP-1A IS OPERATING. o INVESTICATE CAUSE OF PUMP TRIP. DISCUSSION: STOPPING GWP-1B LOCALLY WILL ACTUATE THIS ALARM A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER B0OSTER PUMPS.

REFERENCES:

DRAWING 208-034 SHEET GW-02 n .N SENSING ELEMENT: CONTACTS IN THE CONTROL STATION AR-402 Rev. 23 Page 72

ENCLOSURE 1 n) (Page 71 of 87) _i PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-06 G-06-06 GW PRESS LOW EVENT. POINT 1245 INDICATED CONDITION: f o GLAND WATER PRESSURE IS <190 PSIG AS SENSED BY GW-39-PS l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: j oSTANDBYGLANDWATERPUMPAUTOSTARfS. o LOCAL GLAND WATER PRESSURE LOW. l l OPERATOR ACTIONS FO' A VALID ALARM: 1 i o ENSURE STANDBY GLAND WATER PUMP IS RUNNING. o INVESTIGATE CAUSE OF LOW PRESSURE CONDITION. l l ' DISCUSSION: A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER B0OSTER PUMPS. l

REFERENCES:

DRAWING 208-034 SHEET GW-01 ,() SENSING ELEMENT:.GW-39-PS AR-402 Rev. 23 Page'73 i

ENCLOSURE 1 j (Page 72 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-07 G-06-07 GW PUMP MOTOR OVERLOAD EVENT POINT 1253 INDICATED CONDITION: o GWP-1A MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o GWP-1A TRIPS o HIGH AMPS READ LOCALLY ON THE 480V BUS OPERATOR ACTIONS FOR A VALID ALARM: o CONSIDERATION SHOULD BE GIVEN TO STARTING GWP-1B AND STOPPING GWP-1A o IF GWP-1A HAS TRIPPED THEN ENSURE GWP-1B IS OPERATING. o INSPECT GWP-1A FOR ABNORMAL OPERATION DISCUSSION: A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER BOOSTER PUMPS. IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-034 SHEET GW-01 k SENSING ELEMENT: 49X OVERLOAD RELAY AR-402 Rev. 23 Page 74

ENCLOSURE 1 (] (Page 73 of 87) V PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-07 G-06-07 I GW PUMP MOTOR OVERLOAD 1 EVENT POINT 1254 INDICATED CONDITION: o GWP-1B MOTOR AMPS >115% RATED LOAD ( REDUNDANT INDICATION WHICH WILL VERIFY ALARM: L o GWP-1B TRIPS o HIGH AMPS READ LOCALLY ON THE 480V BUS OPERATOR ACTIONS FOR A VALID ALARM: o CONSIDERATION SHOULD BE GIVEN TO STARTING GWP-1A AND STOPPING GWP-1B o IF GWP-1B HAS TRIPPED THEN ENSURE GWP-1A IS OPERATING. o INSPECT GWP-1B FOR ABNORMAL OPERATION DISCUSSION: A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER B0OSTER PUMPS. IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

ORAWING 208-034 SHEET GW-02 ( SENSING ELEMENT: 49X OVERLOAD RELAY AR-402 Rev. 23 Page 75

1 ) ENCLOSURE 1 O'w/ (Page 74 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-08 G-06-08 GW PUMP AUTO START ' ~ EVENT POINT 1246 INDICATED CONDITION: 1 o GWP-1A BREAKER CLOSED WITH CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RED LIGHT ON WITH A GREEN FLaC ONh'P-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF LOW GLAND WATER PRESSURE DISCUSSION: THE GLAND WATER PUMP THAT IS SELEC1ED ON THE LOCAL CONTROL STATION WILL AUTO START AT <I95 PSIG. THE NON SEL.ECTED GLAND WATER PUMP WILL START AT <I85 PSIG GLAND WATER PRESSURE.

REFERENCES:

DRAWING 208-034 SHEET GW-01 SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 23 Page 76

ENCLOSURE 1 O) (Page 75 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-08 G-06-08 GW PUMP AUTO START EVENT POINT 1248 INDICATED CONDITION: o GWP-1B BREAKER CLOSED WITH CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o RED LIGHT ON WITH A GREEN FLAG ON GWP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTIGATE CAUSE OF LOW GLAND WATER PRESSURE DISCUSSION: THE GLAND WATER PUMP THAT IS SELECTED ON THE LOCAL CONTROL STATION WILL AUTO START AT <195 PSIG. THE NON SELECTED GLAND WATER PUMP WILL START AT <185 PSIG GLAND WATER PRESSURE.

REFERENCES:

DRAWING 208-034 SHEET GW-02 Ah SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 23 Page 77

ENCLOSURE 1 ^) (Page 76 of 87) /\\J PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 l l SPENT FUEL POOL LEVEL l g l l HIGH/ LOW l l I I EVENT POINT 0340 INDICATED CONDITION: o SPENT FUEL POOL "A" LEVEL > +.5 FT AS SENSED BY SF-1-LS1 USING 159'6" AS A REFERENCE. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SPENT FUEL POOL LEVEL INDICATION, SF-1-LIl OPERATOR ACTIONS FOR A VALID ALARM: o IF FILLING SPENT FUEL POOLS, SECURE FILLING. o VERIFY SPENT FUEL COOLING VALVE LINEUP. o REDUCE SPENT FUEL POOL LEVEL BELOW ALARM SETPOINT DISCUSSION: "0" INDICATION ON SPENT FUEL LEVEL INDICAiL 1UATES TO 158'6" IF BWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT DECREASING. IF BWST LEVEL IS DROPPING CONSIDERATION SHOU' D BE GIVEN TO SECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BE VERIFIED. IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 (-(j SENSING ELEMENT: SF-1-LS1 AR-402-Rev. 23 Page 78

ENCLOSURE 1 ,s (Page 77 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 l l l l SPENT FUEL POOL LEVEL l g l l HIGH/ LOW I I I I EVENT POINT 0341 INDICATED CONDITION: o SPEKT FUEL POOL "A" LEVEL < -2 FT AS SENSED BY SF-1-LS1 USING 158'6" AS A REFERENCE. 1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SPENT FUEL POOL LEVEL INDICATION, SF-1-LIl OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY SPENT FUEL COOLING VALVE LINEUP. o FILL SPENT FUEL POOL PER OP-406 DISCUSSION: "0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF BWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT INCREASING. IF BWST LEVEL IS INCREASING CONSIDERATION SHOULD BE GIVEN TO SECURING BOTH SPENT FUEL PbMPS UNTIL LINEUPS CAN BE VERIFIED. IF SF TRANSFER TUBES ARE OPEN CHANCES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 SENSING ELEMENT: SF-1-LS1 AR-402 Rev. 23 Page 79 m a~ m -u +

ENCLOSURE 1 ) (Page 78 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 l l SPENT FUEL l l POOL LEVEL l HIGH/ LOW l l I I EVENT POINT 0342 INDICATED CONDITION: o SPENT FUEL POOL "B" LEVEL > +.5 FT AS SENSED BY SF-1-LS2 USING 158'6" AS A REFERENCE. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SPENT-FUEL POOL LEVEL INDICATION, SF-1-LI2 OPERATOR ACTIONS FOR A VALID ALARM: o IF FILLING SPENT FUEL POOLS, SECURE FILLING. o VERIFY SPENT FUEL COOLING VALVE LINEUP. o REDUCE SPENT FUEL POOL LEVEL BELOW ALARM SETPOINT DISCUSSION: "0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF BWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT DECREASING. IF BWST LEVEL IS DROPPING CONSIDERATION SHOULD BE GIVEN TO 5,ECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BE VERIFIED. IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 SENSING ELEMENT: S F-1-LS 2 AR-402-Re". 23 Page 80

ENCLOSURE 1 ( (Page 79 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 I I l l SPENT FUEL l l POOL LEVEL l l HIGH/ LOW I I I I EVENT POINT 0343 INDICATED CONDITION: o SPENT FUEL POOL "B" LEVEL < -2 FT /.S SENSED BY SF-1-LS2 USING 158'6" AS A REFERENCE. A REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2 OPERATOR ACTIONS FOR A VALID ALARM: o VERIFY SPENT FUEL COOLING VALVE LINEUP. o FILL SPENT FUEL POOL PER OP-406 DISCUSSION: "0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF BWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT INCREASING. IF BWST LEVEL IS INCREASING CONSIDERATION SHOULD BE GIVEN TO SECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BE VERIFIED. IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL 'EVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 ()N, ( SENSING ELEMENT: SF-1-LS2 AR-402 Rev. 23 Page 81

ENCLOSURE 1 (Page 80 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-02 G-08-02 FUEL TRAJWSFER CAJWAL LEVEL HIGH/LO)N EVENT POINT 0346 INDICATED CONDITION: o FUEL TRANSFER CANAL LEVEL > +.5 FT AS SENSED BY SF-10-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2, WHEN TRANSFER TUBES ARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o SECURE TRANSFER CANAL FILL OPERATIONS o VERIFY SPENT FUEL / DECAY VALVE LINEUPS DISCUSSION: "0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6' IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE ~*TLL EFFECT FUEL -TRANSFER CANAL LEVEL. 4 ~

REFERENCES:

DRAWING 208-053 SHEET SF-04 ,~) ( SENSING ELEMEKT: SF-10-LS AR-402 Rev. 23 Page 82

i ~ ENCLOSURE 1 (Page 81 of 87) v PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-02 G-08-02 FUEL TRANSFER CANAL LEVEL HIGH/ LOW i EVENT POINT 0347 1 INDICATED CONDITION: I o FUEL TRANSFER CANAL LEVEL < -1 FT AS SENSED BY SF-10-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON. cb REDUNDANT INDICATION WHICH WILL VERIFY ALARM: %J ~ o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2, WHEN TRANSFER TUBES ARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o REFER TO AP-1080 o FILL FUEL TRANSFER CANAL DISCUSSION: "0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT FUEL TRANSFER CANAL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 SENSING ELEMENT: SF-10-LC v AR-402 Rev. 23 Page 83

ENCLOSURE 1 ,O -(Page 82 of 87) () PSA-G ANNUNCIATOR RESPONSE-PSA-Y-08-03 G-08-03 CASK AREA LEVEL HIGH/ LOW EVENT POINT 0344 INDICATED CONDITION: o CASK AREA LEVEL > +.5 FT AS SENSED BY SF-11-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: oSPENTFUELPOOLLEVELINDICATION,5)-1-LI2,WHENCASKAREAGATESARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A' VALID ALARM: o SECURE SPENT FUEL POOL FILL OPERATIONS o VERIFY SPENT FUEL VALVE LINEUPS DISCUSSION: "O" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT CASK AREA LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 q. (/ SENSING ELEMENT: SF-11-LS AR-402 Rev. 23. Page 84

g ENCLOSQRE_1 (Page 83 of 87) 4 'V PSA-G ANP"NCIATOR RESPONSE PSA-Y-08-03 G-03-03 CASK AREA LEVEL HIGHILOW EVENT POINT 0345 INDICATED CONDITION: o CASK AREA LEVEL < -1 FT AS SENSED BY.SF-11-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON. REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2, WHEN CASK AREA CATES ARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM: o FILL THE CASK AREA o VERIFY SPENT FUEL VALVE LINEUPS DISCUSSION: "0" INDICATION ON SPEN 1 FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT CASK -AREA LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 -(j ISENSING ELEMENT: SF-11-LS AR-402 Ruv. 73 Page 85

ENCLOSURE 1 (Page 84 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-04 G-0P-04 SPENT FUEL PUMPS TRIP EVENT POINT 0337 L INDICATED CONDITION: 1 o 5FP-1A BREAKEn IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION. L ltEDUNDANT INDICATION WHICH WILL VERIFY ALARM: o GREEN LIGHT ON WITH A RED FLAG ON FP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o IWESTICATE SFP-1A FOR MALFUNCTIONS DISCUS! ION: SECURING SFP-IA LOCALLY WILL CAUSE THIS ALARM TO ACTUATE ESA 480V UNDERVOLTAGE LOCKOUT WILL TRIP THE SFENT FUEL PUMPS, 7 TART OF THESE PUMPS WILL BE BLOCKED UNTIL THIS LOCKOUT IS RESET.

REFERENCES:

DRAWING 208-053 SHEET SF-01 SENSING ELEMENT: 42 RELAY AND CONTACTS IN THE CONTROL STATION z AK 402 Rev. 23 Page 86

ENCLOSURE 1 f'J} (Page 85 of 87) 'w PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-04 G-08-04 SPENT FUEL PUMPS TRIP EVENT POINT 0338 INDICATED CONDITION: o SFP-1B BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION. O REDUNDANT INDICATION WHICH WILL VERIFY ALARM: o CREEN LIGHT ON WITH A RED FLAG ON SFP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTICATE 5FP-1B FOR MALFUNCTIONS DISCUSSION: SLCURING SFP-1B LOCALLY WILL CAUSE THIS ALARM TO ACTUATE ESA 480V UNDERVOLTAGE LOCKOUT WILL TRIP THE SPENT FUEL PUMPS, START OF THESE PUMPS WILL BE BLOCKED UNTIL THIS LOCKOUT IS RESET.

REFERENCES:

DRAWING 208-053 SHELT SF-02 ,,~ ( SENSING ELEMENT: 42 RELAY AND CONTACTS IN THE CONTROL STATION AR-402 Rev. 23 Page 87

. -. = - ENCLOSURE 1 (Page 86 of 87) PSA-C ANNUNCIATOR RESPONSE l PSA-Y-08-04 G-08-04 i SPENT FUEL PUMPS TRIP EVENT POINT 0339 INDICATED CONDITION: o SFP-2 BREAKER IS OPEN WITH CONTr.01. HANDLE IN THE NORMAL AFTER START POSITION. R2DUNDANT INDICATION WHICH WILL VERIFY ALARM: o CREEN LIGHT.ON WITH A RED FLAG ON SFP-2 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM: o INVESTICATE SFP-2 FOR MALFUNCTIONS DISCUSSION: SECURING SFP-2 LOCALLY WILL CAUSE THI; ALARM TO ACTUATE

REFERENCES:

DRAWING 208-053 SHEET SF-03 SENSING ELEMENT: 42 RELAY AND CONTACTS IN THE CONTROL STATION AR-402 Rev. 23 Page 88

e ENCLOSURE 1 (Page 87 of 87) PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-08 G-08-08 I I I I l l WASTE l 3 DISPOSAL PANEL j. l TROUBLE EVENT POINT 1588 INDICATE CONDITION: o A. UNACKNOWLEDGED ALARM HAS EXISTED ON THE AUX BUILDING WASTE DISPOSAL MNEL FOR 30 MINUTES RfDUNDANT INDICATION WHICH WILL VERIFY ALARM: OPERATOR ACTIONS FOR A VALID ALARM: o NOTIFY AUXILIARY BUILDING OPERATOR DISCUSSION: REFERENCES? SENSING ELEMENT: 'AR-402 Rev. 23 Page 89 (LAST PAGE) ,}}