E.. ),.
r Duke Energy Corporation b--
Catawba Nuclear Station
=
4800 Concord Road l
York, SC 29745 Gary R. Peterson (803) 831-4251 OFFICE Vice Pinident (803)8313425ux June 18, 1999 U.
S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Catawba Nuclear Stations, Units 2 Docket Nos. 50-414 Steam Generator Tube Inspection Report Pursuant to Technical Specifications 5.6.8a. and 5.6.8b., please find attached the steam generator tube inspection conducted during the Unit 1 End of Cycle 11 refueling outage.
'The following quantity of tubes were inspected:
Tubes Inspected Tubes Inspected Steam Generator Full Length Partial Length A
1455 487 B
1382 0
C 1365 109 D
1381 480 Attachments 1, 2,
3, and 4 identify tubes with imperfections in
((/
steam generators A, B,
C, and D, respectively.
The location and size of the imperfections are also provided.
There were no
/
tubes removed from service by plugging.
Any questions concerning this report may be directed to Kay
/f7)()/
Nicholson at 803-831-3237.
Sincerely,
- 7 Gary R.
Peterson fg Attachments e:J ~
xc:
L. A. Reyes, Regional Administrator P.
S. Tam, ONRR D. J.-Roberts, SRI f
l 9906290060 990618 PDR ADOCK 05000414-P PDR m
.s-
- *
- c e * *
- 9p e *
- FTI TUIAN II (Vartien 2.3) 05/12/1999 08:27:31
- 0**12%***,
C:tcwb2 N.S.
- Unit On3 R piccoment
- ocee***o*
S/G A
- e e*ce*********
05/99 RFO l
oce**********
BOBBIN,MRPC C/L SI,MRPC H/L SI,MRPC UBEND SI l
j j
ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 4 35 05/99 BOBBIN ADI O.96 08H
+27.29 05/99 BOBBIN ADI 1.02 09H
-14.95 4 59 05 99 BOBBIN ODI 3
0.27 02C
+15.79 05 99 MRPC C/L SI VOL 0.22 02C
+15.81 8 123 05 99 BOBBIN OXP 80.25 TEC
+0.00 to
+3.16 l
14 5 05 99 BOBBIN NEX 7.97 TSH
-0.26 l
14 81 05 99 BOBBIN ADI 0.22 03C
+25.56 17 32 05 99 BOBBIN ODI 11 0.18 04H
+21.61 05 99 BOBBIN ODI 11 0.20 Olc
+19.41 05 99 MRPC C/L SI VOL 0.15 Olc
+19.01 05 99 MRPC H/L SI VOL 0.23 04H
+19.42 05 99 MRPC H/L SI VOL 0.33 04H
+19.14 l
05 99 MRPC H/L SI VOL 0.47 04H
+21.61 20 91 05 99 BOBBIN ODI 7
0.20 02H
+7.16 05 99 MRPC H/L SI VOL 0.30 02H
+7.16 I
20 115 05 99 BOBBIN ADI 0.19 03H
+13.47 21 104 05 99 BOBBIN ADI 0.31 02H
+16.87 21 130 05 99 BOBBIN OXP 76.02 TEC
+16.87 to
+17.92 21 138 05/99 BOBBIN OXP 72.26 TEC
+16.83 to
+17.78 22 53 05/99 BOBBIN ADI 0.53 02C
+4.63 05 99 MRPC C/L SI VOL 0.21 02C
+4.52 22 103 05 99 BOBBIN ADI 0.21 02H
+9.22 05 99 BOBBIN ODI 4
0.26 02H
+11.22 05 99 MRPC H/L SI VOL 0.18 02H
+9.44 05 99 MRPC H/L SI VOL 0.29 02H
+12.60 05 99 MRPC H/L SI VOL 0.49 02H
+11.22 27 10 05 99 BOBBIN ODI 2
0.59 03H
+3.39 05 99 BOBBIN ODI 7
0.11 07C
+9.97 28 11 05 99 BOBBIN ODI 12 0.16 O1H
+26.51 l
28 13 05 99 BOBBIN ADI O.17 04H
+23.18 1
32 49 05 99 BOBBIN ADI 0.15 02H
+26.82 05 99 BOBBIN ODI 5
0.56 02H
+18.70 05 99 MRPC H/L SI VOL 0.28 02H
+18.70 33 10 05 99 BOBBIN ODI 10 0.20 04C
+25.05 05/99 MRPC C/L SI VOL 0.22 04C 425.35 36 7 05/99 BOBBIN NEX 10.11 TSC
-0.27 i
1 37 50 05 99 BOBBIN ODI 7 0.44 TSH
+11.52 l
38 39 05 99 BOBBIN ODI 21 0.33 05H
+16.81 l
40 83 05 99 BOBBIN ODI 8 0.81 04C
+29.65 l
05 99 KRPC C/L SI VOL 0.43 04C
+29.E5 43 30 05 99 BOBBIN NEX 8.05 TSH
-0.25 44 65 05 99 BOBBIN ADI 0.27 04C
+15.80 l
05 99 MRPC C/L SI VOL 0.22 04C
+15.80 45 50 05 99 BOBBIN ODI 7
0.24 03H
+25.80 47 8 05 99 BOBBIN NEX 6.05 TSH
-0.28 48 33 05 99 BOBBIN ODI 5 0.21 07C
+35.35 i
05 99 MRPC C/L SI VOL 0.51 07C
+35.35 1
52 55 05 99 BOBBIN ODI 9
0.40 02H
+8.26 l
05 99 MRPC H L SI VOL 0.44 02H
+6.51 l
05 99 MRPC H L SI VOL O.48 02H
+8.59 I
52 61 05 99 BOBBIN ADI 0.17 02H
+13.15 05 99 MRPC H/L SI VOL 0.41 02H
+12.51 05 99 MRPC H/L SI VOL 0.48 02H
+13.50 54 37 05 99 BOBBIN ADI 0.26 02H
+23.71 55 38 05 99 BOBBIN ODI 8 0.32 04H
+29.20 05 99 MRPC H/L SI VOL 0.29 04H
+29.20 61 22 05 99 BOBBIN ODI 13 0.42 02C
+28.20 05 99 MRPC C/L SI VOL 0.81 02C
+28.10 62 13 05 99 BOBBIN NEX 8.49 TSC
-0.26 71 30 05 99 BOBBIN OXP 41.53 TEC
+20.87 to
+22.06 74 33 05 99 BOBBIN ADI 0.23 02H
+10.67 05 99 BOBBIN ODI 3
0.10 02H
+7.90 05 99 MRPC H/L SI VOL 0.28 02H
+7.61 05/99 MRPC H/L SI VOL 0.28 02H
+11.50 05/99 MRPC H/L SI VOL 0.39 02H
+12.65 a
i l
l t
s l
FTI TUBAN II (Version 2.3) 05/12/1999 08:27:31 1
Catawba N.S. - Unit One Replacement l
l S/G A 05/99 RFO BOBBIN,MRPC C/L SI,MRPC H/L SI,MRPC UBEND SI ATTACHMENT #1 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGA ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION I
l 75 22 05/99 BOBBIN ODI 25 0.24 05C
+29.48 75 50 05/99 BOBBIN ODI 10 0.32 05H
+9.86 05 99 MRPC H/L SI VOL 0.31 05H
+9.86 76 115 05 99 BOBBIN NEX 8.75 TSC
-0.25 76 123 05 99 BOBBIN NEX 11.82 TSC
-0.27 77 20 05 99 BOBBIN NEX 8.49 TSH
-0.25 80 35 05/99 BOBBIN NEX 8.86 TSH
-0.25 to
+0.00 83 122 05/99 BOBBIN NEX 10.06 TSC
-0.27 84 27 05 99 BOBBIN ADI 0.38 FB4
+7.31 05 99 BOBBIN ADI 0.70 FB4
+5.01 05 99 MRPC UBEND SI VOL 0.60 FB4
+7.31 05 99 MRPC UBEND SI VOL O.73 FB4
+5.01 87 26 05 99 BOBBIN NEX 9.33 TSC
-0.26 88 35 05 99 BOBBIN NEX 6.10 TSH
-0.25 90 35 05 99 BOBBIN NEX 8.00 TSH
-0.32 93 98 05 99 BOBBIN ODI 2
0.45 02H
+2.93 05 99 MRPC H/L SI VOL 0.26 02H
+4.64 05 99 MRPC H/L SI VOL 0.45 02H
+2.93 05 99 MRPC H L SI VOL O.51 02H
+5.92 05 99 MRPC H L SI VOL 0.53 02H
+6.48 96 47 05 99 BOBBIN ODI 6
0.51 02H
+16.01 05 99 MRPC H/L SI VOL 0.27 02H
+16.01 97 34 05 99 BOBBIN ODI 18 0.30 OSC
+12.19 99 46 05 99 BOBBIN ADI 0.16 08C
+21.38 114 75 05/99 BOBBIN ADI 0.30 OSH
+34.93 l
Total Indications Found = 90 Total Tubes Found = 51 1
I l
E...
FTI TUBAN II (V:rcion 2.3) 05/12/1999 12:54:59
- 9*****.-
Cat wbn N.S. - Unit Cn3 Repiccoment l_
S/3 B l
05/99 RFO l
-BOBBIN,MRPC C/L SI,MRPC H/L SI,MRPC USEND SI l
I l
ATTACHMENT #2 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGB ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 25 ;24 05 99 BOBBIN ADI 0.13 07H
+23.62 i
33:- 54 05 99 BOBBIN ODI 3
0.25 03H
+25.68 05 99 MRPC N/L SI
.VOL 0.24 03H
+26.15 37 24 05 99 BOBBIN ODI 2
0.24 03C
+23.55 05 99 MRPC C/L SI VOL 0.58 03C
+23.49 41 64 05 99 BOBBIN ODI 9 0.91 O1H
+21.59 l
05 99 MRPC H/L SI VOL 0.14 O1H
+21.72 48 105 05 99 - BOBBIN OXP 34.09 TEH
+3.02 l
59 20 05 99 BOBBIN ADI 0.29 TSC
+10.88 i
61 96 05 99 BOBBIN ADI 0.23 02H
+24.89 64 '55 05 99 -BOBBIN NEX 11.02 TSC
-0.30 65 62 05 99 BOBBIN ODI 5
0.64 06H
+4.47 05 99 BOBBIN ODI 6 1.12 06H
+6.04 05 99 MRPC H L SI VOL 0.55 06H
+4.41 l-05 99 MRPC H L SI VOL 0.78 06H
+6.35 l
65 72 05 99 BOBBIN ODI 25 0.48 05H
+32.63 1
05 99 BOBBIN ODI 27 0.31 05H
+8.45 i
05 99 MRPC H/L SI VOL 0.36 05H
+32.06 l
G9 70 05 99 BOBBIN ADI 0.25 07H
+26.33 1
05 99 BOBBIN ADI 0.26 04H
+12.63 05 99 BOBBIN
'ADI 0.33 04H
+16.41 05 99 BOBBIN ADI 0.36 04H
+14.42 05 99 MRPC H L SI VOL 0.22 04H
+16.77 05 99 MRPC H L SI VOL 0.25 04H
+12.93 05 99 MRPC H L SI VOL 0.37 04H
+14.90
- 05 99 MRPC H L SI VOL 0.45 07H
+27.19 76 105 05 99 BOBBIN ADI 0.19 FB8
+6.77 76 121-05 99 BOBBIN ODI 10 0.22 03H
+7.28 79 24 05 99 BOBBIN ODI 7
0.16 FBI
+11.02 i
'79 76 05 99 BOBBIN ODI 19 0.46 04H
+21.61 I
05 99 MRPC H/L SI VOL 0.38 04H
+22.12 80 105 05 99-BOBBIN ODI' 6 0.18 08H-
+3.83 i
05 99 BOBBIN ODI 12 0.39 07H
+35.18
~
05 99 MRPC H/L SI VOL 0.24 07H
+35.22 94 85 05 99 DOBBIN ADI-0.17 02H
+23.86 95 64 05 99-BOBBIN ADI 0.28 02H
+18.95 j
107 88 05 99 BOBBIN ADI 0.28 03H
+8.42 l
110 45 05 99 BOBBIN OXP 34.19 TEC
+14.97 l-Total Indications Found = 38 Total Tubes Found = 20 l
I
I FTI TUBAN II (V rcien 2.3) 05 12/1999 12:55:49
- ege*o**
Cattwb2 N.S. - Unit On3 Rrp ccoment
- * *e *e* * * ** e d S/G C 05/99 RFO j
BOBBIN,MRPC C/L SI,MRPC H/L SI,MRPC UBEND SI l
l ATTACHMENT #3 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGC ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION 4
5 54 05 99 BOBBIN NQI 3.64 TSH
+0.89 5 132 05 99 BOBBIN ODI 6 0.75 05C
+27.11 05 99 MRPC C/L SI VOL 0.15 OSC
+27.11 1
6 35 05 99 BOBBIN OXP 36.71 TEH
+0.02 to
+19.43 l
12 115 05 99 BOBBIN OXP 29.96 TEH
+0.00 to
+3.75 19 40 05 99 BOBBIN ADI 0.80 07H
+22.77 29 10 05 99 BOBBIN NQI 4.27 TSC
+0.84 47 20 05 99 BOBBIN NEX 8.65 TSC
-0.37 63 120 05 99 BOBBIN ODI 1
0.04 FB4
+1.03 67 88 05 99 BOBBIN ODI 7
0.94 07C
+24.84 05 99 BO9 BIN ODI 9
1.05 07C
+29.62 05 99 MRPC C/L SI VOL 0.77 07C
+24.84 05 99 MRPC C/L SI VOL 1.00 07C
+29.62 76 73 05 99 BOBBIN ODI 6
0.10 FB6
+7.96 90 115 05 99 BOBBIN ADI O.20 02H
+13.13 05 99 MRPC H/L SI VOL 0.18 02H
+13.13 91 40 05 99 BOBBIN NQI 1.23 02C
+4.45 05 99 MRPC C/L SI VOL 0.33 02C
+4.45 96 55 05 99 BOBBIN NQI O.87 09H
+13.46 100 49 05 99 BOBBIN NQI 0.84 TSH
+0.98 I
05 99 BOBBIN ODI 11 0.18 04H
+7.91 1
05 99 MRPC H/L SI VOL 0.37 04H
+7.86 q
113 70 05/99 BOBBIN ADI 0.17 O1H
+30.98 Total Indications Found = 23 Total Tubes Found = 15 l
FTI TUBAN'II (Varcian 2.3) 05/12/1999 12:56 50
- ese****eees Cittwbs N.S. - Unit On3 Repiccoment esseeeebeesed S/G D
- eet L*************
05/99 RFO
- ee*e*******
BOBBIN,MRPC C/L SI, m c H/L SI,MRPC UBEND SI 1
Page 1
? ATTACHMENT #4 - INDICATIONS OF IMPERFECTIONS INDS OF IMPERFECTIONS - SGD I
ROW COL OUTAGE TEST TYPE IND %TW VOLTS LOCATION i
1 138 05 99 BOBBIN NEX 12.35 TSC
-0.32 7 112 05 99' BOBBIN ODI 17 0.55 08C
+3.18 05 99 MRPC C/L SI VOL
'O.21 08C.
+3.18 16 141 05 99 - BOBBIN NEX 6.83 TSC'
-0.29 28 9 05 99 BOBBIN ODI 2
0.52 09C
+4.25 05 99 MRPC UBEND SI VOL 0.60 09C
+4.15 33 90 05 99 BOBBIN OXP 28.38 TEC
, +17.05 to
+18.77 33 110 05 99 BOBBIN
.37 42 05/99 BOBBIN-OXP 29.48 TEC
+9.82 to
+13.24 ODI 3 0.24 04H
+27.50 05/99 'MRPC H/L SI VOL 0.32 04H
+27.50
. 37 136 05 99 BOBBIN NEX 8.87 TSH
-0.26 38 125 05 99 BOBBIN ODI 3 0.26 07C
+23.24 39 10 05 99. BOBBIN ODI 6 0.42 05C
+3.59 05 99' MRPC C/L SI.
VOL 0.70 OSC
+3.59 49 20 05 99 BOBBIN ADI 0.21 06C
+21.03 56.83 05 99 BOBBIN DNT 20.27 09C
+1.69 05 99 MRPC C/L SI DNT 4.30 09C
+1.78 05 99 MRPC USEND SI DNT 4.31 09C
+1.64 65 72 05 99 BOBBIN-ADI 1.84 08C
+3.38 05 99 MRPC C/L SI VOL 0.59 08C
+3.38 4
67 14 05 99 BOBBIN NEX 10.12 TSC
-0.28 73 20 05 99 BOBBIN NEX 9.37 TSC
-0.27 73 126 05 99 BOBBIN OXP 33.03 TSC
-0.01 80 45 05 99 BOBBIN ADI 0.12 05H
+34.21 05/99 BOBBIN ADI 0.16 05H
+32.74 05/99 MRPC H/L SI VOL 0.21 05H
+32.74 80 95 05 99 B03 BIN ADI 0.21 05H
+34.39 1
05 99 MRPC H/L SI VOL 0.24 05H
+34.39 l
89 112 05 99 BOBBIN ODI 18 0.32 06C
+14.71 l
05 99 MRPC C/L SI VOL 0.22 06C
+14.71 93 50 05 99 BOBBIN ADI 0.13 08H
+22.14 05 99-MRPC H/L SI VOL 0.10 08H
+22.14 105 40 05 99 BOBBIN NEX 10.01 TSC
-0.25 1
Total Indications Found = 33 Total Tubes Found = 21 l
l 1
L..