ML20195J480

From kanterella
Jump to navigation Jump to search
Requests Addl Info Re Acceptance Criteria for Eddy Current Measurement Scheduled to Be Performed After 12 Wks of Operation & Action Plan If Measurement Shows Excessive Wear, Per
ML20195J480
Person / Time
Site: South Texas STP Nuclear Operating Company icon.png
Issue date: 01/05/1988
From:
NRC
To:
HOUSTON LIGHTING & POWER CO.
References
NUDOCS 8801280278
Download: ML20195J480 (1)


Text

p >, '*

' ~

k.

i DOCKET N0. 50-498 REQUEST FOR ADDITIONAL INFORMATION BASED ON LETTER OF JANUARY 5, 1988 (1) Please specify the following:

(a) Acceptance criteria for the eddy current measurement scheduled to be performed after 12 weeks of operation.

(b) Action plan if the measurement shows excessive wear.

(2) Submit calculations on rate of leakage flow if one thimble tube is completely severed.

What is the capacity of each of the two centrifugal charging pumps?

(3) Please provide:

(a) Drawing and brief description of the crimping tool.

(b) Copy of procedures for isolating a leaking thimble.

(4) The staff requests a commitment to provide the results of the Tihange-3 inspection of BMI thimbles during their next refueling outage.

l 8801280278 880105 PDR ADOCK 05000498 g

PDR