Correction to Amend 75 to License NPF-12
ML20195D139
Person / Time
Site: Summer 
(NPF-12-A-075, NPF-12-A-75)
Issue date: 10/31/1988
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20195D143 List:
References
NUDOCS 8811040212
Download: ML20195D139 (3)


Text

.

ATTACHMENT T0 t,1CEN5i AMEN 0 MENT NO. 75 TO FActt. TTY OPER4TtNG 1.tCENSE NO. NPF-12 00CKET NO. 50-395 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pa vs. The revised pages are identified by amendment nunter and contain vertica lines indicating the areas of change. Corresponeing overleaf pages are also provided to maintain docurent completeness.

Remove Pages insert Pages 21 2-1 22 2-2 2-5 2-5 2-8 28 2-9 29 2-10 2 10 B 2-1 8 2-1 8 2-2 5 2-2 B 2-4 8 2-4 3/4 1-3a 3/4 1-34 3/4 1 4 3/4 1-4 3/4 1 5 3/4 1-5 3/4 1-Sa 3/4 1-6 3/4 1-6 (overleaf) 3/4 1-11 3/4 1-11 3/4 1-12 3/4 1-12 (r r'=')

l 3/4 1-19 3/4 1-19 3/4 1-20 3/4120(overleaf) 3/4 b'1 3/4 2 1 3/4 2d 3/4 2-2 3/4 2-3 3/4 2-3 3/4 2 4 3/4 2-4 3/4 2 5 3/4 2 5 3/4 2-6 3/4 2-6 3/4 2 6a 3/4 2 6b 3/4 2-6c 6811040212 881031 PDR ADOCK 0500039:3 P

ppc

REACTIVITY CONTR0!,,j,$.:[

80 RATED WATER SroW On tt. TING LIMITING CONDITI0ii r0R OPERATION 3.1.2.6 As a minimum, the following borated water source (s) shall be OPERABLE as required by Specification 3.1.2.2:

a.

A boric acid storage system with:

1.

A minimum contained borated water volume of 14,000 gallons, 2.

Between 7000 and 7700 ppm of boron, and 3.

A minimum solutien temperature of 65'F.

b.

The refueling water storage tu.K with:

1.

A minimum containea corated water volume of 453,800 gallons, l

2.

A minimum boron concentration of 2300 ppm, and 3.

A minimum solution temperature of 40'F.

APPLICABILITY:

MODES 1, 2, 3 and 4.

ACTION:

a.

With the boric acid storage system inoperable and being used as one of the above required borated water sources, restore the storage system to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT i

STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and borated to a SHUTDOWN MARGIN equivalent to at least 2 percent delta k/k at 200*F; restore the boric acid storage system to OPERABLE status within the next 7 days or be in COLD SHUTDOWN within the next 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.

With the refueling water storage tank inoperable, restore the tank to OPERABLE status within one hour or be in at least HOT STANDBY within the next S hours and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i SUteER - UNIT 1 3/4 1-12 Amendment No fl, 75

POWER DISTRIBUTION LINITS I

SURVEILLANCE REQUIREMENTS (Continued) t e.

With the maximum value of F((z)

K(z) over the core height (z) increasing since the previous determination of F (z) either of the following actions shall be taken:

t (1) F (z) shall be increased by 2% over that specified in Specificat!on 4.2.2.2c or (2) F (z) shall be measured at least once per 7 Etfective Full Power Days until two successive maps indicate that the maximum value of t

F (z)

K(z) i i

l over the core height (z) is not increasing.

[

)

f.

With the relationships specified in Specification 4.2.2.2c. above not i

being satisfied, t

(1) Calculate the maximum percent over the core height (z) tilat F (z) exceeds its limit by the following expression:

9 e

  • Fhz)xW(z)1-1),x100forP>0.:,

)

1 2.45 x K(z),

(*T

{

",. F (2) x W(zh-1 x 100 for P < 0.5 h

2.45 x K(z) i i

f i

f 1

l l

I SutWER - UNIT 1 3/4 2-6 Amendment No.

75 l

L

-