Forwards Safety Evaluation Supporting Interim Degraded Grid Voltage Procedures Until Final Protection Mods Completed During 1987 Refueling Outage
ML20195B491
Person / Time
Site: Millstone 
Issue date: 05/20/1986
From: Charemagne Grimes
Office of Nuclear Reactor Regulation
To: Opeka J
NORTHEAST NUCLEAR ENERGY CO.
Shared Package
ML20195B494 List:
References
NUDOCS 8605290368
Download: ML20195B491 (3)


Text

_

May 20,1986 Docket No.:

50-245 Mr. John F. Opeka, Senior Vice President Nuclear Engineering and Operations Northeast Nuclear Energy Company Post Office Box 270 Hartford, Connecticut 06141-0270

Dear Mr. Opeka:

SUBJECT:

DEGRADED GRID VOLTAGE PROCEDURES Re:

Millstone Nuclear Power Station, Unit No. 1 f

By letter dated October 9, 1985, you submitted Degraded Grid Voltage Procedures to be used under non-accident conditions at the Millstone, Unit 1, facility.

The submittal fulfilled commitments made in your letters dated January 17, and June 11, 1984. Our review considered the most recent revision, Revision 23, to the operating procedure (OP 340), in place of Revision 21. We have concluded that the interim degraded grid voltage procedures (until the final degraded grid protection modifications are completed during the 1987 refueling outage) are acceptable.

A copy of our safety evaluation is enclosed.

Sincerely, Original signed by: C. I. Grimes Christopher I. Grimes, Director Integrated Safety Assessment Project Directorate Division of PWR Licensing - B

Enclosure:

As Stated cc: See Next Page DISTRIBUTION 564

'ISAP Reading JPartlow

~"

NRC PDR Local PDR JShea NSIC MBoyle PAnderson FMiraglia OELD CGrimes EJordan BGrimes PAnderson ISAP P B 4

B ISAP:DPL-JShea:lt pan on CGrimes 05/Q/86 05//q/86 05g)/86 8605290368 860520 PDR ADOCK 05000245 P

PDR

  1. ja# 58%g%

UNITED STATES

[

Ih NUCLEAR REGULATORY COMMISSION p

WASWNG TON, D. C. 20555 o

e

%...../

May 20,1986 Docket No.: 50-245 Mr. John F. Opeka, Senior Vice President Nuclear Engineering and Operations Northeast Nuclear Energy Company Post Office Box 270 Hartford, Connecticut 06141-0270

Dear Mr. Opeka:

SUBJECT:

DEGRADED GRID VOLTAGE PROCEDURES Re:

Millstone Nuclear Power Station, Unit No. 1 By letter dated October 9,1985, you submitted Degraded Grid Voltage Procedures to be used under non-accident conditions at the Millstone, Unit 1, facility.

The submittal fulfilled commitments made in your letters dated January 17, and June 11, 1984. Our review considered the most recent revision, Revision 23.,

to the operating procedure (OP 340), in place of Revision 21. We have concluded that the interim degraded grid voltage procedures (until the final degraded grid protection modifications are completed during the 1987 refueling outage) are acceptable.

A copy of our safety evaluation is enclosed.

Sincerely, CMyb1-UA Christopher I. Grimes, Director Integrated Safety Assessment Project Directorate Division of PWR Licensing - B

Enclosure:

As Stated cc: See Next Page l

Mr. John F. Opeka Millstone Nuclear Power Station Northeast Nuclear Energy Company Unit No. 1 CC' Gerald Garfield, Esquire Kevin McCarthy, Director Day, Berry & Howard Radiation Control Unit Counselors at Law Department of Environmental City Place Protection Hartford, Connecticut 06103-3499 State Office Building Hartford, Connecticut 06106 Edward J. Mroczka Vice President, Nuclear Operations Richard M. Kacich, Supervisor Northeast Utilities Service Company Operating Nuclear Plant Licensing Post Office Box 270 Northeast Utilities Service Company Hartford, Connecticut 06141-0270 Post Office Box 270 Hartford, Connecticut 06141-0270

' State of Connecticut Office'of Policy and Management ATTN: Under Secretary Energy Division 80 Washington Street Hartford, Connecticut 06106 Regional Administrator, Region I

.U.S. Nuclear Regulatory Commission e

631 Park Avenue King of Prussia, Pennsylvania 19406 Northeast Nuclear Energy Company ATTN: Superintendent i

Millstone Nuclear Pcwer Station P. O. Box 128 Waterford, Connecticut 06385 Resident Inspector-c/o U.S. NRC Millstone Nucitar Power Station P. O. Box 811 Niantic, Connecticut 06357 First Selectman of the Town of Waterford Hall of Records 200 Boston Post Road Waterford, Connecticut 06385 i

L

-w

,+&

e-e+

--