SUPPLEMENTAL REPORT REANALYSIS OF 1984 EDDY CURRENT DATA FOR STEAM GENERATORS NO. 3 AND NO.
4 9
Prepared by:____
l 1
_ /_9_[_[_
D.
F.
May Date Nuclear Engineer l
Reviewed ane Approved by [___
/______
_h,d_kh____
u_
R.
A.
Mello Date Technical Director 8806200047 880607 PDR ADOCK 05000029 l
Q DCD t
4 Introduction This Special Report is a result of the review: of previous inservice inspection data for steam generators (S/G) No. 3 and No. 4 performed in May and June of 1987 and is intended to supplement the 1984 report, "Steam Generator Inservice Inspection Results" (Reference 1).
During the 1987 inspection, results of previous inspections done in 1985 for S/G No. 1 and in 1984 for S/G's No. 3 and No.
4 were re-l evaluated due to discrepancies found during a review of the 1984 eddy current data for S/G No.
2.
References 1.
Steam Generator Inservice Inspection Results, May 1984, FYR 85-61 2.
Steam Generator No. 2 Inservice Inspection Results, June 1988, FYR 88-79 3.
Zetec report. "Assessment of Data Interpretation Techniques", dated July 16, 1987.
4.
LER 87-006, "Defective Tubes Missed During 1984 Steam Generator Eddy Current Examination". FYR 87-69 dated July 2, 1987 S.
Memorandum from C.G.Garrow to D.A.Maidrand, "Evaluation of the Potential 10 CFR Part 21 - Zetec Steam Generator Evaluation", dated September 29, 1987 Results Discussion As a result of this re-evaluation 18 tubes were plugged in S/G No. 3 and 16 tubes in S/G No. 4 in May and June of 1987.
No additional tubes were plugged in S/G No.
1.
Tables I and II list the location and percent of wall thickness penetration for each imperfection found in the re-evaluation.
Imperfections listed in these tables include those that l
either differed significantly from, or were not included in, the 1984 report results.
The failure to detect defective tubes during the 1984 inspection has been attributed to the improvements in eddy current inspection and evaluation techniques and also to the lack of a secondary review of the eddy current data (Reference 4).
An evaluation (Reference 5) conducted after the E/C testing concluded the deviations experienced during the 1984 inspection were not reportable under 10 CFR Part 21.
Corrective actions were provided in Reference 4.
i
6.w.
TABLE I - STEAM GENERATOR NO. 3 INSPECTION RESULTS (based on review of old data)
Row Column
% Degradation Location of Degradation Plugged D
019 38 TTS-CL+0000.3 YES D
042 38 TTS-CL+0002.3 YES 47 TTS-CL+0001.4 D
041 24 TTS-CL+0001.0 NO C
022 67 TTS-CL+0000.6 YES E
O25 42 TTS-CL+0000.5 YES I
O20 59 TTS-CL+0000.2 YES I
O21 33 TTS-CL+0000.9 NO G
O22 25 TTS-HL+0000.9 NO F
O22
<20 TTS-CL+0002.8 NO K
O26 31 TTS-CL+0000.8 NO G
O26 36 TTS-CL+0001.9 YES F
O26 24 TTS-CL+0001.3 NO H
O24
<20 TTS-HL+0003.3 NO 21 TTS-HL+0000.6 J
O24 35 TTS-CL+0001.2 YES K
O25 81 TTS-CL+0000.6 YES I
O25 69 TTS-CL+0000.4 YES N
028 46 TTS-CL+0001.6 YES J
O28
<20 TTS-CL+0001.3 NO K
030 56 TTS-CL+0000.8 YES F
036
<20 TTS-CL+0000.9 NO E
037
<20 TTS-CL+0001.2 NO G
037 26 TTS-HL+0000.7 NO H
037
<20 TTS-CL+0001.1 NO I
038 33 TTS-HL+0001.4 YES l
46 TTS-HL+0001.7 l
48 TTS-CL+0000.8 G
039 24 TTS-CL+0000.4 NO H
039
<20 TTS-CL+0000.8 NO G
041 33 TTS-CL+0001.1 NO H
041 29 TTS-CL+0000.7 NO F
043 25 TTS-CL+0000.8 NO H
043 36 TTS-HL+0002.0 YES I
043
<20 TTS-HL+0001.0 NO DD 035 35 4-AVB+ 0000.0 YES R
047 23 TTS-HL+0000.4 NO BB 047 49 TTS-HL+0000.5 YES H
049 62 TTS-HL+0000.3 YES K
049 (20 TTS-HL+0000.5 NO L
049 23 TTS-HL+0001.2 NO O
049 33 TTS-HL+0000.5 NO AA 050
<20 TTS-HL+0000.5 NO l
H 053
<20 TTS-HL+0000.5 NO V
055
<20 TTS-HL+0000.5 NO W
055 27 TTS-HL+0001.7 NO P
056
<20 TTS-HL+0000.6 NO
<20 TTS-HL+0000.8
~~-
4
~
s TABLE I CONTINUED Row Column
% Degradation Location of Degradation Plugged R
057
<20 TTS-HL+0000.4 NO S
057
<20 TTS-HL+0000.4 NO O
058
<20 TTS-HL+0001.3 NO I
060
<20 TTS-HL+0000.6 NO E
039 036 TTS-CL+0001.3 YES D
039 036 TTS-CL+0000.8 YES H
035 023 TTS-CL+0001.3 NO F
O28 029 TTS-CL+0000.4 NO l
l l
l l
l l
l l
l l
l
)
AVB - Antivibration Bar 1
CL
- Cold Leg j
HL
- Hot Leg TE
- Tube End TTS - Top of Tube Sheet 1
I I
TABLE II - STEAM GENERATOR NO. 4 INSPECTION RESilLTS (Based on review of old data) f Row Column X Degradation Location of Degradation Plugged l
G 048 078 TTS-HL+0001.5 YES P
044 076 TTS-HL+0000.9 YES P
043 054 TTS-HL+0000.9 YES O
043 059 TTS-HL+0001.5 YES D
039 031 TTS-CL+0001.0 NO R
041
<20 TTS-HL+0002.6 NO K
037 077 TTS-HL+0005.6 YES J
035 039 TTS-CL+0001.5 YES O
034 079 TTS-HL+0000.8 YES K
033
<20 TTS-HL+0002.6 NO O
032 081 TTS-HL+0003.0 YES N
031 071 TTS-HL+0003.1 YES P
O29 038 TTS-HL+0001.0 YES J
O29 027 TTS-HL+0004.2 YES 046 TTS-CL+0001.7 G
O29 034 TTS-ru+0001.2 NO H
O28 038 TTS CL+0000.3 YES L
028 022 TTd-HL+0002.4 NO P
O28 031 TTS-HL+0001.2 NO M
O27 031 TTS-CL+0000.6 NO H
018 039 TTS-CL+0000.8 YES H
O20 061 TTS-HL+0001.8 YES F
O21 026 TTS-CL+0001.6 NO L
022 056 TTS-CL+0000.5 YES J
O25
<20
'TS-CL+0000.4 NO H
O23
<20 TTS-CL+0002.9 NO L
023 045 TTS-HL+0002.1 YES 050 TTS-CL+0000.6 l
l l
9 AVB - Antivibration Bar l
CL
- Cold Leg l
HL
- Hot Leg TE
- Tube End TTS - Top of Tube Sheet
)