Myw.... g g 1988
In Reply Refer To:
Docket: 50-298.
Nebraska Public Power District
ATTN:
George A. Trevors
Division Manager - Nuclear Support
P.O. Box 499
Columbus, NE 68601
Gentlemen:-
This refers to the telephone conference call conducted on May 24, 1988, with
you and other members of your staff, and Region IV personnel. This conference
call regarded certain findings documented in our NRC Inspection Report 50-298/
86-28, dated April 1,1987, and your June 17, 1987 response to those findings.
The subjects discussed during the conference call are described in the enclosed
Meeting Sumary.
In accordance with Section 2.790 of the NRC's "Rules of Practice," Part 2,
Title 10, Code of Federal Regulations, a copy of this letter will be placed in
the NRC's Public Document Room.
Should you have any questions concerning this matter, we will be pleased to
discuss them with you.
Sincerely,
k
k
L. J. Callan, Director
Division of Reactor Projects
Enclosure:
Meeting Sumary
cc w/ encl:
(seenextpage)
RIV:DRP/C *
TS/DRS *
D/DRS *
D D
D/DRP b
EJHoller:gb
REIreland
JMilhoan
AB' ach
,LJCallan
<
'
/ /88
/ /88
/ /88
/88
5 /26/88
t
- Previously concurred
jll
8806090064 880526
h
,
ADOCK 05000298
Q
.-
.
. . .
-
_ - . -
.
.
_
L
1
, . U.
Nebrasks Public Power District
2
Cooper Nuclear Station
ATTN: Guy Horn, Division Manager.
of. Nuclear Operations-
P.O. Box 98
JBrownv111e, Nebraska 68321-
'
Kansas Radiation Control Program Director
Nebraska Radiation Control Program Director
bec to DMB (IE-01) - DRS & DRP
bec distrib. by RIV:
4
- RRI
R. D. Martin, RA
-
- SectionChief(DRP/C)
Lisa Shea, RM/ALF
- RPSB-DRSS
- RIV File
- Project Engineer, DRP/C
RSTS Operator
- W. Long, NRR Project Manager
- DRS
- DRP
i
u
!
.
1
- .
1
}
- -
-
.
>
.
s
s .
.
ENCLOSURE
NEBRASKA PUBLIC POWER DISTRICT
JANUARY 28 -1988
MEETING SUMMARY
Licensee:
Nebraska Public Power District (NPPD)
Facility:
CooperNuclearStation(CNS)
License:
DRP-46
Docket:
50-237
SUBJECT:
COMPLIANCE WITH 10 CFR 50.49 AT COOPER NUCLEAR STATION
On May 24, 1988, representatives of Nebraska Pbblic Power District (NPPD)
participated in a telephone conference cell with NRC Region IV personnel to
discuss the findings documented id NRC Inspection Report 50-298/86-28 dated
April 1, 1987, and NPPD's re 90nse to that report dated June 17, 1987. The
participant list for the .. . phone conference is attached. The
conference call was held at the request of Region IV.
'
The NRC discussed its concern with the operability of certain items addressed
in NRC Inspection Report 50-298/86-28 and requested an update from NPPD
regarding the corrective steps noted in NPPD's June 17, 1987 response to the
report. The particular items discussed were:
1.
Boston Insulated Wire (BIW) Bostrad 7E Cable (Item 50-298/8628-01).
f
'
advised that BIW Bostrad 7E cable installations had been modified to
provide for conduit shielding of the cable.
2.
Kerite 600 Volt Cable (Item 50-298/8628-03). NPPD advised that an
operability analysis had been performed regarding this cable.
NPPD also
indicated that modifications at CNS may have replaced Kerite 600 volt
cable applications inside containment. NPPD offered to make further
comments regarding Kerite 600 volt cable in a subsequent telephone
conference call scheduled for Friday, May 27, 1988.
,
3.
Raychem Coaxial Cable (Item 50-298/8628-04). NPPD indicated that
cable inspections to date had not identified use of this cable in EQ
applications but that inspection results were still being evaluated.
agreed to inform the NRC if Raychem cable installations of interest were
'
identified and to address this item in the Friday, May 27, 1988 telephone
conference call.
4.
General Electric Electrical Penetrations (Item 50-298/8628-5). NPPD
advised that the EQ file nad been revised to clearly show the link
between tested and installed items at CNS.
- _ _____ _ ____________
- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ - _ _ _ _ _ _ _ _ - _ _
_ _ _ _ _ _ _ _ _ _ _
<t.
r
,
.
2
5.
Model OP-N Microswitches (Item'50-298/8628-11).
NPPD advised that
similarity comparisons have been completed.
6.
ASCO. Solenoid Valves (Item 50-298/8628-14).
NPPD advised that plant air
system pressure is limited to 110 psig and that EQ data packages have
,
been revised.-
7.
Okonite Splices in Limitorque Motor Operators (Item 50-298/8620-09).
NPPD advised that it would address this item in the Friday, May 27, 1988
telephone conference call.
8.
Scotch Taped Splices and Blind Barrel Splices (Item 50-298/8628-08).
advised that the taped splices had been replaced and that these items
were addressed in a NPPD letter to the NRC dated August 24, 1987.
Region IV and NPPD agreed to further discuss items 2. , 3. , and 7. above in a
subsequent telephone conference cal'i at 1:00 p.m. (CDT) on Friday, May 27,
1988.
Attachment:
Participation List.
l
.
.
.
._
-
.g :
_$
.-
, . . .
,
Attachment
_ Telephone Conference Call May 24, 2988
4
With Nebraska Public Power District
NRC Participants:
J. Milhoan, Director, Division of Reactor Safety _
B. Beach, Deputy Director, Division of Reactor Projects
R. Ireland, Chief, Plant Safety Section
A. Johnson, Reactor Inspector
E. Holler, Chief, Projects Section C
W. Bennett, Senior Re;ident Inspector
,.
Licensee Participants:
G. H.-Trevors, Nuclear Support Division Manager
R. E. Wilbur, Nuclear Engineering and Construction
Division Manager
W. C. Fisher, Electrical Engineering Supervisor
E. M. Hace, Engineering Manager
J. R. Flaherty, Plant Engineering Supervisor
_S. J. Jobe, Simulator Supervisor
J. R. Hackney, Senior Staff Engineer
D. E. Buman, Electrical Engineer
G. R. Smith, Licensing and Safety Supervisor
,