Notice of Violation from Insp on 880325-0429.Violation Noted:Failure to Establish Procedure Adequate for Covering Control Room Annunciator Inverter Alignment & Operation, Resulting in Loss of All Annunciators for 12 Min
ML20154P915
Person / Time
Site: Vogtle 
Issue date: 05/13/1988
From: Brownlee V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20154P914 List:
References
50-424-88-17, NUDOCS 8806060121
Download: ML20154P915 (1)


Text

f O

l ENCLOSURF 1 NOTICE OF VIOLATION Georgia Power Company Docket No. 50-424 Vogtle 1 License No. NPF-68 During the Nuclear Regulatory Comission (NRC) inspection conducted on March 25

- April 29, 1988, a violation of NRC requirements was identified.

In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1987), the violation is listed below:

Technical Specification 6.7.1.a requires that written procedures be established, implemented and maintained covering activities delineated in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978.

Contrary to the above, on April 26, 1988, an adequate procedure had not been established to cover the control room annunciator inverter alignment and operation.

Failure to provide an adequate procedure to prescribe the alignment and operation for the backup power source resulted in a loss of all control room annunciators for a period of 12 minutes following the loss of the normal power supply.

This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, Georgia Power Company is hereby required to submit a written statement or explanation to the Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, Region II, and a copy to the NRC Resident Inspector, Vogtle, within 30 days of the date of the letter transmitting this Notice.

This reply should be clearly marked as a "Reply to a Notice of Violation" and should include for each violation:

(1) admission or denial of the violation, (2) the reason for the violation if admitted, (3) the corrective steps which have been taken and the results achieved, (4) the corrective steps which will be taken to avoid further violations, and (5) the date when full compliance will be achieved.

Where good cause is shown, consideration will be given to extending the response time.

If an adequate reply is not received within the time specified in this Notice, an order may be issued to show cause why the license should not be modified, suspended, or revoked or why such other action as may be proper should not be taken.

FOR THE NUCLEAR REGULATORY COMMISSION

.w,w L/(M Virgil (L.Brownlee, Chief 8806060121 880 Reactor Projects Branch 3 DRADOCK.0000g13 4 Division of Reactor Projects Dated at Atlanta, Georgia this g day of May 1988

-