W3P88-0963, Application for Amend to License NPF-38,consisting of Tech Spec License Amend NPF-38-88,deleting Ammonia Detection Sys from Chemical Detection Sys & Tech Spec for Ammonia Detection Sys.Fee Paid

From kanterella
(Redirected from ML20154N178)
Jump to navigation Jump to search
Application for Amend to License NPF-38,consisting of Tech Spec License Amend NPF-38-88,deleting Ammonia Detection Sys from Chemical Detection Sys & Tech Spec for Ammonia Detection Sys.Fee Paid
ML20154N178
Person / Time
Site: Waterford 
Issue date: 09/21/1988
From: Dewease J
LOUISIANA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
Shared Package
ML20154N182 List:
References
W3P88-0963, W3P88-963, NUDOCS 8809290214
Download: ML20154N178 (12)


Text

.

LOUlBIANA 317 BARONNE STREET P. O. BOX 60340 POWER & LIGHT /

NEW ORLEANS, LOUl5fANA 70160 (504) 595 2781 N M ErsVE$

J. G. DE WE A$ t Ys? ort a September 21, 1988 W3P88-0963 A4.05 QA U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, D.C.

20555

SUBJECT:

Waterford SES Unit 3, Docket No. 50-382, License No. NPF-38 Technical Specification License Amendment NPF-38-88 Broad Range Toxic Gas Detection System and Ammonia System The purpose of this letter is to request NRC approval for a proposed change to the toxic chemical detection system.

Louisiana Power and Light through the past years has developed a program for the protection of Waterford 3 Control Room operators in the unlikely event of a toxic chemical release.

This program consists of physical systems as well as other compensatory measures, such as the Saint Charles Parish Emer-gency Preparedness Industrial Hot Line.

This program in large part was developed based on operating experience.

The Broad Range Toxic Gas Detection (BRTGD) System is a major part of the chemical detection system, and the system has been reliably operating since August 1986.

The BRTGD system provides toxic chemical detection for ammonia as well as for other chemicals and thus duplicates the function of the ammonia system.

After careful evaluation, LP&L believes that sufficient operating experience has been gained with the BRTGD system to conclude that there is no longer a need to keep both the ammonia and the BRTGD systems operable.

The BRTGD system provides equivalent ammonia detection, and thus having solely the BRTGD system for amonia detection is justified from a safety, regulatory, and cost benefit standpoint.

Particular ef fort has been expended to assure that equivalent amonia protec-tion will t,e provided by the BRTGD system.

Testing of the BRTGD system for ammonia detection as well as analyses were performed to assure that equiva-lent amonia protection will be provided.

The attached safety evaluation provides a detailed discussion of the testing and analyses which were performed.

The testing and analyses have demonstrated that the GRTGD system provides equivalent or better amonia protection than the amonia detection system.

MO 8809 M0214 880921 FDR ADOCK 050003S2 i

P PDC g

6 NS30760E to fCb8C f 0

"AN EQUAL OPPORTUNITY EMPLOYER"

$ 08~ 004

Pago 2 W3P88-0963 Accordingly, LP&L requests approval to delete the ammonia detection system from the chemical detection system and to delete the technical specification for the ammonia detection system.

The technical specification bases change is attached as well as a safety evaluation concluding that there is no significant hazards consideration for this proposed change.

Please contact me or Robert J. Murillo should there be any questions regarding this letter.

?

,6tvf Ed J.hTDewease

/ Senior Vice President Nuclear Operations JGD/RJM/smb Attachments: technical specification bases change & LP&L check no. 08-6304 cc:

E.L. Blake, W.M. Stevenson, J.A. Calvo, D.L. Wigginton, R.D. Martin, NRC Resident Inspector's Office (W3)

NS20760

P l

l UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION l

i In the matter of

)

)

Louisiana Power & Light Company

) Docket No. 50-382 Waterford 3 Steam Electric Station

)

f I

AFFIDAVIT t

L J.C. Dewease, being duly sworn, hereby deposes and says that he is Senior f

Vice President. Nuclear Operations of Louisiana Power & Light Company that he is duly authorized to sign and file with the Nuclear Regulatory Commission the attached Technical Specification Change Requesti that he is familiar

[

with the content thereofi and that the matters set forth therein are true and correct to the best of his knowledge, information and belief.

i

\\

e-

'/

dAJA J/C.'Dewease '

i

[

{enior Vice President t

Nuclear Operations f

i STATE OF LOUISIANA)

[

) ss I

PARISH OF ORLEANS )

f s

l 7

i aNotaryPublicdnandf the Parish Subscribed and sworn to before me,/d'/t_ day of (d_C/7re

/ A_ >

I and State above named this 1988.

/

}

i r

/],

[

\\_. - -

CL/

/

bg LL Notary Public

,[

f c-1 i

My Commission expires il II V

[

t l

I l

SAFETY EVALUATION FOR DELETION OF AMHONIA SYSTEM

1. 0 Description of Proposed Change This is a request to delete the ammonia detection system technical specification, including LC0 3.3.3.7.2 and surveillance requirements 4.3.3.7.2, from the Waterford 3 technical specifications.

A correspond-ing change to technical specification bases 3/4.3.3.7 is also proposed.

2. 0 Description of Control Room Envelope Protection Protection pt 'ided to ensure control room operator habitability within the control room envelope is the following:

radiological protection, toxic gas protection, emergency air supply system, and other compensa-tory measures like industry hot line and written emergency procedures.

A description of these protective measures is herein provided:

i

  • Radiological Protection:

I The Airborne Radiation Monitoring (ARM) System provides information, both locally and in the main control room, for the purpose of main-taining low in plant personnel radiation exposure in accordance with 10CFR20 and Regulatory Guide 8.8 (March 1977).

The ARM system pro-vides information on the airborne activity levels inside the control room outside air intakes and in the event of detection of high airborne activity generates a signal to isolate the normal outside I

air intakes and start the emergency ventilation system.

The detec-tors also assist operators in picking one of two emergency intakes with the lowest airborne activity levels, thereby minimizing the amount of noble gases entering the control raom environment and also 1

minimizing the amount of emergency ventilation system filter loading.

  • Toxic Gas Protection:

Toxic Gas Protection is provided by the chlorine, ammonia, and broad range toxic gas detection systems.

Chlorine System:

Redundant chlorine detectors are provided near the Control Room Air Conditioning System normal outside air intake.

Upon detectic, r f chlorine, the control room envelope is automati-cally placed i.e the isolated mode.

The chlorine detectors are provided with outputs to sound an alarm in the main control room, and chlorine concentration readout is available from the plant computer. N520760E

The sensidyne chlorine detectors have been seismically qualified by Wyle Laboratories.

In addition, the chlorine detection equipment has been installed in stismically qualified structures.

Redundant chlorine detectors are powered from independent non-safety-related uninterruptible power supplies which in turn draw power from safety related buses.

The loss of power to a dctector is annunciated in the control room.

Ammonia System:

Redundant, non-seismic ammonia detectors are provided near the Control Room Air conditioning System normal outside air intake.

The ammonia detectors use derivative gas phase spectroscopy activation.

Upon detection of ammonia, the control room envelope is automatically placed in the isolated mode.

The ammonia detectors are provided with outputs to sound an alarm in the main control room and ammonia concentration readout is available from the plant computer.

Redundant ammonia detectors are powered from independent non-safety-related uninterruptible power supplies which in turn draw power from safety-related buses.

The loss of power to a detector is annunciated in the control room.

Broad Range Toxic Gas Detection System:

The broad range toxic gas detection system purchased from HNU Systems.

Inc., includes two redundant photoionization detectors (PID's), HNU Model 201.

These detectors monitor the atmosphere in the Reactor Auxiliary Building (RAB) outside air intake duct and generate a signal whenever the concentration of detectable gases exceeds a pre-set limit.

Upon detection of a toxic gas concentration above the BRTGD system setpoint of 3 ppm (acrolein), the control room is automatically placed in the isolated mode.

The BRTGO detectors are provided with outputs to sound an alarm in the main control room, and toxic gas concentration readout is available locally as well as in the control room.

Redundant broad range detectors are powered from independent non-safety-related uninterruptible power supplies which in turn draw power from safety-related buses.

The loss of power to a detector is annunciated in the control room.

The photoionizaton gas detector consists of an air pump, a sampling chamber, a high-energy ultraviolet lamp, a pair of electrodes that maintain an electric field across the chamber and associated electron-ics.

The sample atmosphere is drawn from the process stream, the air in the intake duct in this case, and pumped through the sample chamber.

As the sample flows through the chsmber, it is continuously irradiated by ultraviolet light emitted by the lamp. N520760

In a process called photoionization, a photon of ultraviolet light is absorbed by a gas molecule and one or more electrons are emitted, leaving a positively charged ion.

The electric field will cause these electrons to move across the chamber, creating an electric current in the associated circuit.

Ionization cannot occur if the energy of the incident photon is less than the ionization potential of the molecule.

The ionization poten-tial, the minimum energy required to ionize the molecule, is the same for all molecules of a given chemical.

Each ultraviolet lamp has an energy spectrum that is characteristic for that type lamp, i.e.,

photons emitted by the lamp have energies that are uniquely distributed over a fixed range.

In some cases, none of the photons emitted by a given lamp may have enough energy to ionize the molecules of a particu-lar gas.

Such a gas will then not be detectable by a PID equipped with that type lamp.

The normal constituents of the atmosphere, nitrogen, oxygen, argon, carbon dioxide, etc. have ionization potentials that are higher than the energies of the lamps in the PID's, and these gases will therefore not be registered by the detectors.

  • Emergency Air Supply:

An Emergency Air Supply System for the Main Control Room (MCR) is provided to ensure a minimum six hour supply of air for control room and security personnel.

The system is designed to provide Grade D breathable air (as defined by the Compressed Gas Association standards) at a rate of 6 scfm for each of 17 individuals.

An air storage system with a capacity of 50,000 scf at 2000 psig is provided to maintain a supply of air for use upon demand.

  • Other Compensatory Measures:

Other compensatory measures are provided to ensure the habitability of the control room envelope is maintained.

For example, Waterford-3 is a participant in the St. Charles Parish Emergency Preparedness / Industrial Hot Line System.

This is a dedicatei communication network between St. Charles Parish Emergency Operations Center (EOC) and industries in St. Charles Parish.

In the event of an emergency, the affected industry would promptly notify the EOC of the class of emergency, the type of incident and the recommended actions.

The E0C will then notify affected neighboring industries.

Additionally, LP&L has in place wrP 1 procedures to be initiated in the event of a toxic chemical rele.

ithin or near Waterford 3.

Procedures are also in place coveru

.vacuation of personnel.

3.0 Testing of BRTGD System For Ammonia l

Tests, utilizing the installed BRTGOs system at Waterford 3, were performed on July 28 and 29, 1988 to verify the capability of the BRTGD system to detect ammonia and the response times of the BRTGD system.

Both BRTGD system monitors "A" and "B" were tested. j NS20'50 l

i

The following test procedure was used.

Certified concentrations of ammonia, in air, were purchased from Lincoln Big Three Incorporated in New Orleans.

The ammonia concentrations were provided in three pres-surized bottles at a pressure of 2000 psig and at concentrations of 34 ppm, 40 ppm, and 90 ppm, respectively.

The ammonia concentrations, one concentration at a time, were injected upstream of the BRTGD rotameter to control the discharge flow to the detector.

The BRTGD system times to alarm for monitors "A" and "B" were then recorded.

The BRTGD system monitor "A" was tested on July 28, 1988, and the BRTGD system monitor "B" was tested on July 29, 1988.

The test showed that for ammonia concentrations of 34 ppm, 40 ppm, and 90 ppm, the BRTGD system monitor "A" would isolate the control room in 1.90,1.07, and 0.30 minutes respectively, with an environmental back-ground of 1.2 ppm acrolein.

The test showed that for ammonia con-centrations of 34 ppm, 40 ppm, and 90 ppm, the BRTGD system monitor "B" would isolate the control room in 0.65, 0.45, and 0.15 minutes respectively with an environmental background of 2.1 ppm acrolein.

3.0 Safety Evaluation The Threshold Limit Value* (TLV) for ammonia is 50 ppm.

The current setpoint for the ammonia system is 50 ppm ammonia.

The response time for the ammonia system is 0.33 minutes.

The response time for the ammonia system is a fixed constant irrespective of the ammonia concen-tration, that is, ammonia concentrations less than 50 ppm will not initiate a system response, and ammonia concentrations greater than 50 ppm will cause the system to respond in 0.33 minutes.

The BRTGD system response time, however, is a function of the concentration of the chemical being detected.

Higher concentration of a particular chemical will cause a faster system response time.

Therefore, a direct compari-son of the ammonia and BRTGD system cannot be made.

However, it can be shown that for low concentrations of ammonia (about 90 ppm), the TLV for ammonia, 50 ppm, will not be reached in the control room envelope and for higher concentrations of ammonia, the BRTGO system will have a faster response time than the ammonia system.

Such a comparative evaluation thus demonstrates equivalent or better ammonia protection by the BRTGD system than the ammonia system.

The following equation for computation of a chemical concentration of a controlled volume is used to demonstrate that the TLV will not be ex-ceeded for low concentrations of ammonia:

C(t) = X * (1-exp (-Vt) where C(t):

is the instantaneous volume concentration X:

is the inflow concentration V.

is the total volume rate change t:

is the time in minutes

  • TLVs, Threshold Limit Values and Radiological Exposures and Diseases for 1987-1988, American Conference of Governmental Industrial Hygienist, Cincinnati, Ohio.,

NS20760

The foregoing equation is based on the equation for measuring concentra-tions provided in Nuclear Chemistry Theory and Applications, G.R. Choppin and J. Rydberg, 1980, formula 17.6b.

The values for the parameters used in the foregoing equation are based on the following.

3 The control room envelope has a volume of approximately 220,000 ft,

reference FSAR Section 6.4.2.2.

The normal outside air intake flow during the normal ventilation mode is 2200 cfm, reference FSAR Figure 6.4-1.

The control room isolation valves operate in less than 3 seconds after receipt of a closure signal, reference FSAR Section 6.4.4.2.

The control room in-leakage is 0.06 volume changes per hour, reference LP&L Letter W3P85-3154, dated January 24, 1986.

The control room envelope volume rate change as a result of air intake and in-leakage is given by:

0.011 volume changes per minute.

V=2 00

+ 0.001

=

The following values of ammonia are calculated assuming that the outside ammonia concentrations of 34 ppm, 40 ppm, and 90 ppm went undetected for 10 minutes:

C(t) = 34 * (1-exp (-0.011 * (10 + 1.90)) = 4.17 ppm, C(t) = 40 * (1-exp (-0.011 * (10 + 1.07)) = 4.58 ppm, C(t) = 90 * (1-exp (-0.011 * (10 + 0.30)) = 9.64 ppm.

In fact, using the foregoing equation, even after 63 minutes, the am-monia concentrations in the control room envelope will be half the outside concentration or 17, 20, and 45 ppm, below the Ammonia TLV.

The tests and analysis also demonstrate that for ammonia concentrations Feater than 90 ppm, the response times of the BRTGD system monitors will be faster than the response time of the ammonia system.

Therefore, the BRTGD system monitors will provide better ammonia detection than the current ammonia system.

5. 0 Significant Hazards Consideration The proposed change shall be deemed to involve a significant hazards consideration if there is a positive finding in any of the following areas:

1.

Will operation of the facility in accordance with the proposed change involve a significant increase in the probability or con-l sequences of any accident previously evaluated?

Response

No. N520760

The BRTGD system provides toxic chemical protection for ammonia.

The BRTGD system duplicates the function of the ammonia detection system, and thus the ammonia detection system is not required to protect the control room envelope from an ammonia toxic chemical release.

The BRTGD system will isolate the control room before the Immediately Dangerous To Life and Health * (IDLH) concentration for ammonia is reached.

The BRTGD system has operated reliably since August 1986.

Additionally, technical specification 3.3.3.7.3 requires that the control room ventilation system be maintained in the isolation mode should the required LCO for the BRTGD system not be met.

Therefore, the proposed change will neither increase the 4

probability or consequences of any accidents previously evaluated.

2.

Will operation of the facility in accordance with the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated.

Response

No.

i The function of both the BRTGD and ammonia systems is solely to isolate the control room in the unlikely event of a toxic chemical 4

release in the area.

The BRTGD and ammonia system do not provide any other protective function.

Since the BRTGD system will provide ammonia detection, the deletion of the ammonia detection system will not create the possibility of a new or different kind of accident from any accident previously evaluated.

l 3.

Will operation of the facility in accordance with the proposed chance involve a significant reduction in a margin of safety?

Response

No.

1 The ammonia detection system setpoint is currently 50 ppm ammonia.

The BRTGD system setpoint is 3 ppm (acrolein) which corresponds to a setpoint of 7.1 ppm ammonia.

Tests of the BRTGD system were i

performed in July 1988, and the tests of the BRTGD system verified i

the capability of the system to detect ammonia and the response i

times of the BRTGD system monitors.

The test analysis demonstrated that for ammonia concentrations of 90 ppm or less, the TLV for ammonia would not be exceeded, even for the incredible situation where an ammonia release was assumed to be undetected for 63 minutes.

The test analyses also demonstrated that for ammonia concentrations higher than 90 ppm, the resporise times of the BRTGD system monitors would be faster than the resuonse time of the ammonia system.

Accordingly, while the BRTGD system has different response characteristics than the ammonia system, the margin of safety would not be reduced, and in fact, the BRTGD system provides better ammonia detection than the ammonia system for higher concen-trations of ammonia.

1 l

  • National Institute of Occupational Safety and Health (NIOSH) Pocket Guide To Chemical Harards, U.S. Department of Health and Human Services, Public Health Service Centers for Disease Control, NIOSH, Septemter 1985. NS20760

e

  • 9 ATTACHMENT A NPF 88 EXISTING i

i

.I i

t I

4 e

i i

l l

l NS20760

INSTRUMENTATION CHEMICAL DETECTION SYSTEMS

/J4MONIA DETECTION SYSTEM LIMITING CONDITION FOR OPERATION 3.3.3.7.2 Two independent ammonia detection systems, with'their alarm / trip setpoints adjusted to actuate at an ammonia concentration of less than or equal to 50 ppm, shall be OPERABLE.

APPLICABILIITY:

All MODES.

ACTION:

With one ammonia detection system inoperable, restore the inoperable a.

detection system to OPERABLE status within 7 days or within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> initiate and maintain operation of the control room ventilation system in the recirculation mode of operation, b.

With no armonia detection system OPERABLE, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> initiate and maintain operation of the control room ventilation system in the recirculation mode of operation.

The provisions of Specification 3.0.4 are not applicablo.

c.

SURVEILLANCE REQUIREMENTS 4.3.3.7.2 Each ammonia detection system shall be demonstrated OPERABLE by performance of a CHANNEL CHECK at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, a CHANNEL FUNCTIONAL TEST at least once per 31 days and a CHANNEL CALIBRATION at least once per 18 months.

4 WATERFORD - UNIT 3 3/4 3-48 EX S"ING

EXF3G INSTRUMENTATION BASES 3/4.3.3.6 ACCIDENT MONITORING INSTRUMENTATION The OPERABILITY of the accident monitoring instrumentation ensures that suf ficient information is available on selected plant parameters to monitor and assess these variables following an accident.

This capability is consistent with the recommendations of Regulatory Guide 1.97, "Instrumentation for Light-Water-Cooled Nuclear Plants to Assess Plant Conditions During and Following an Accident," Oecember 1980 and NUREG-0578, "THI-2 Lessons Learned Task Force Status Report and Short-Term Recommendations." Table 3.3-10 includes Regulatory Guide 1.97 Category I key variables.

The remaining Category I variables are included in their respective specifications.

The Subcooled Margin Monitor (SM), the Heated Junction Thermocouple (HJTC), and the Core Exit Themocouples (CET) comprise the Inadequate Core Cooling (ICC) instrumentation required by Item II.F.2 NUREG-0737, the Post THI-2 Action Plan.

The function of the ICC instrumentation is to enhance the ability of the plant operator to diagnose the approach to existence of, and recovery from ICC.

Additionally, they aid in tracking reactor coolant inventory.

These instruments are included in the Technical Specifications at the request of NRC Generic Letter 83-37.

These are not required by the accident analysis, nor to bring the plant to Cold Shutdown.

In the event more than four sensors in a Reactor Vessel level channel are inoperable, repairs may only be possible during the next refueling outage.

This is because the sensors are accessible only after the missile shield and reactor vessel head are removed.

It is not feasible to repair a channel except during a refueling outage when the missile shield and reactor vessel head are removeJ to refuel the core.

If only one channel is inoperable, it should be restored to OPERABLE status in a refueling outage as soon as c onably possible.

If both channels are i Mperable, at least one channel shall be restored to OPERABLE status in the nearest refueling outage.

3/4.3.3.7 CHEMICAL DETECTION SYSTEMS The chemical detection systems are the ammonia, chlorine, and broad range toxic gas detection systems.

The OPERABILITY of the chemical detection systems ensures that sufficient capability is"available to promptly detect and initiate protactive action in the event of an accidental chemical release.

The chemical detection systems provide prompt detection of toxic gas re-leases which could pose an actual threat to safety of the nuclear power plant or significantly hamper site personnel in performance of duties necassary for the safe operation of the plant.

The broad range toxic gas detection system operates on the principle of gas photoionization, and therefore, the system is sensitive to a broad range of gases.

The system is therefore sensitive to both atmospheric and chemical composition normal fluctuations affecting the Waterford 3 site.

The setpoint WATERFORD - UNIT 3 8 V4 3-3 AMENDHENT NO. 24, 20 EX S" \\ G