Notice of Violation from Insp on 880718-22.Violation Noted: Solenoid Operated Valves Relocated W/O Initiating Rev to Plant post-fire Safe Shutdown Procedures Due to Failure to Perform Adequate Evaluation Per App R Design Guidelines
ML20154J397
Person / Time
Site: North Anna  Dominion icon.png
Issue date: 09/13/1988
From: Herdt A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20154J392 List:
References
50-338-88-13, 50-339-88-13, NUDOCS 8809230014
Download: ML20154J397 (1)


Text

i l L

t ENCLOSURE 1 [

NOTICE OF VIOLATION I

Virginia Electric and Power Company Docket Nos. 50-388,339 .

North Anna License Nos. NPF-4,7 l During the Nuclear Regulatory Comission (NRC) inspection conducted on  !

July 18-22, 1988, a violation of NRC requirements was identified. In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1987), the violation is listed l below:  ;

i Technical Specification 6.8.1.f requires written procedures to be [

established, implemented, and maintained for the fire grotection program.

Section 4.1.1.d Plant Standard STD-GN-0021, Appendix R" Design Guide- f lines, requires any potential concerns related to fire protection or .

compliance with Appendix "R" to 10 CFR 50 to be identified on an t Appendix "R" Design Checklist for all Design Change Packages (DCPs).  ;

t Contrary to the above, the requirements of Section 4.1.1 of STD-GN-0021 l were not implemented for DCPs 87-01 and 87-02. The preparing ongineers  !

for these two DCPs failed to perform an adequate evaluation of the impact i of the design changes on compliance with Appendix R. DCPs 87-01 and 87-02 ,

relocated the solenoid operated valves (SOVs) associated with the steam l inlet trip valves for the Unit 1 and Unit 2 Turbine Driven Auxiliary l Feedwater Pumps from the Main Steam Valve House to the Quench Spray Punp .

House. Plant procedures for a fire in the Control Room require the local ;

operation of the SOVs in the Main Steam Yalve House; however, due to the l inadequate evaluation the SOVs were relocated without initiating a '

revision to plant postfire safe shutdown procedures. l t

This is a Severity level V violation (Supplement I).