3
( )sMun SACRAMENTO MUNICIPAL UTILITY DISTRICT O 62o1 S Street, P.o. Box 1583o. Sacramento CA 95852-183o,1916) 452 3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA GCA 88-314 MAY 19 M Director of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Statinn P1-137 Washington, DC 20555 Docket No. 50-312 Rancho Seco Nuclear Generating Station License No. DPR-54 CR/TSC HABITABILITY, AMMONIA ANALYSIS
Reference:
G.C. Andognini to F.J. Miraglia, Jr. letter dated February 25, 1988
Dear Sirs:
In the referenced letter the District committed to resolve the Control Roca habitability concern with respect to ammonia.
This commitment was reiterated by the NRC staff in NUREG-1286, Supplement 1, with a date of June 1,1988, for resolution.
Pursuant to this commitment the District evaluated the use of ammonia on site and as a result will reduce the concentration of the bulk ammonia storage tank from 28 to 20 weight percent by June 1,1988.
Attached are the assumptions and results of the re-evaluation of the ammonia spill assuming a 20 weight percent solution.
Adequate time exists from odor detection until donning of breathing apparatus (Regulatory Guide 1.78);
therefore, the lowering of the ammonia concentration will result in an acceptable Control Room environment in the event of a postulated ammonia spill.
Members of your staff with questions requiring additional information or clarification may contact Mr. David Swank at (209) 333-2935, extension 4920.
1 l
Sincerely,
. Carl Andogni i Chief Executiv Officer, l
Nuclear Attachment cc:
A. D' Angelo, NRC, Rancho Seco b dl J. B. Martin, NRC, Walnut Creek
\\
l 8805260128 880519 PDR ADOCK 05000312 HANCHU btCU NULLtAH ut MAIINu bl AlloN O 1444o Twin Cities Road, Herald, CA 95638-S799; (209) 333-2935