Text
i 7
x Commonwealth Edison i
> One First Nat>onal Pia:a Ch<ago, INno s
(
) X3 dress RepTyT5~PosTOMT767--
'N
/
Ch<a2o, lucis 60690 0767 September 8, 1988 U.S. Nuclear Regulatory Comission Attn: Document Control Desk Washington, D.C.
20555 Subject Dresden Str.tlon Units 2&3 Quad Cities Station Units 1&2 Zion Station Units 1&2 LaSalle County Station Units 1&2 Byron Station Units 1&2 Braldwood Station Unita 1&2 Response to NRC Bulletin 88-05 NRC Cocket Nos. 50-237/249, 50-254/265, 50-295/304, 50 - 3 DZ114,_.50: 45 (Li S 5 uand_502. gal ( 57 References (a): NRC Bulletin No. 88-05 dated May 6, 1988 (b): HRC Bulletin No. 88-05, Supplernent 1 dated June 15, 1988 (c): HRC Bulletin No. 88-05, Supplement 2 dated August 3, 1988
Dear Sir:
The above References (a), (b) and (c) requested that licensees submit information regarding materials supplied by Piping Supplies, Incorporated (PSI) at Tolsom, New Jersey and West Jersey Manufacturing Company (WJM) at Williamstcwn, New Jersey and to request that licensees 1) take actions to assure that materials comply with ASME Code and design specification requirements or are suitable for their intended service, o'; 2 ) replace such materials.
Adelitionally, Supplements 1 and 2 to the Bulletin (Ref erences (b) &
l (c)) providad additional information and required that holders of full power operating licenses report the results of their records review, testing, and analysis performed as of the date of the second supplement.
Comonwealth Edison has completed its review pursuant to the request outlined in the Bulletin and Supplements for Dresden, Quad Cities, Zlun, LaSalle County, Byron and Braidwood Stations.
The following Attachments provide a sumary of that review.
1 sso91;o:23 eso9os i
i PDR ADOCK 05000237 0
PDC l
~
4 4.
9 a
I 1
s
, r
{
i 1
i To the best of my knowledge and belief, the statoenents contained j
above are true and correct.
In some respect these statements are not based on
[
my personal knowledge, but obtained information furnished by other Cossmonwealth Edison employees, contrector employees, and consultants. Such information has been reviewed in cecordance with company practice, and I 1
believe it to be reliable.
(
I please address any questions that you or your staff may have i
concerning this response to this office.
l
}
6 1
Bespectfully, M
M
{
j W.E.
prgan
(
Nuclear Licensing Administrator j
4 i
j rf j
i Attactonents cci A.B. Davis Resident Inspectors - D/QC/L8C/2/BY/WW I
1 l
StAscribed ar.d bet e mejthig 1gra to 1
5 day e t, 3.L WYSJlh 1988 i
' 1 > 1_A 11 1 @
~
~50tniiFutil'c I
)
5092K i
s i
j I
i l
l
\\
l Commonwealth Edison Response to Bulletin 88-05 Nuclear Regulatory Commission (NRC) Bulletin 88-05 required Commonwealth Edison to submit information regtrding materials supplied by Piping Suppites, Incorporated (PSI) and West Jersey Manufacturing Company (HJM).
The Bulletin also requested that licensees take action to assure that msterials comply with ASHE Code and design specifications or are suitable for their intended service. A description of Commonwealth Edison's program for compliance with the requested actions of Bulletin 88-05 as modified by Supplements I and 2 follows.
fLKOR0_REYRH t
The scope of review at Commonwealth Edison's Nuclear stations consisted of A$HE Section !!! and/or safety related flanges and fittings, for our three never plants (Byron, Braidwood and LaSalle) the search involved original
(
construction as well as operational replacements and modifications.
Zion Quad Cities ano Dresden were all operational prior to January 1, 1976. Thertfore the record review encompassed Section !!! and/or safety related Mdifications and replacements only.
For all plants the record search it.volved a two step process.
- First, l
purchase and receipt documents were reviewed to determine if any HJM or PSI i
flanges or fittings were received. Next, these identified components were located in the plant.
An itemized list of received components is contained in Attachment A.
l k
l I
l l
l 1
1
i
[
4 9
?
I r
I J
Page 2 k
l At the time of receipt of Supplement 2 our record review status was as
[
l follows:
l l
Braidwood - The record search focused on specifications that could have l
supplied flanges or fittings.
These included site purchased pipe fittings and j
Q flanges, flanges for valves, pumps, electrical penetrations, flex hoses NSSS I
equipment and skid mounted equipment. Documents not yet reviewed involve NSSS
[
l and skid mounted equipment which are currently stored with the vendors.
i t
As of August 5th, 527 items were identified as being received at j
Braidwood. One hundred sixty five flanges were found on the shelves. One i
i hundred seventy eight flanges are installed in safety related systems, 50 of
(
l which were declared inaccessible for testir'. The balance of items, 184 l
flanges, are thought to be installed in nonsafety-related applications or have i
been discarded.
Since all safety-related bolting connections were reviewed t
for HJM and PSI materials, the unaccounted for flanges are not installed in safety-related applications.
Overall, Braldeood's review identified only HJM material (no PSI material) i being supplied to Braidwood Station. Of the HJM material, only flanges were l
identified either as individual componentr, or as subparts of flexible hoses, j
Byron - The review of records at Byron is complete with the exception of i
the NSSS and some skid mounted equipment records which are not available for I
revMw.
In addition, portions of the station's Quality Receipt Inspection i
l (QR.i reports have not been reviewed for HJM/ PSI fittings on multi item equipent (e.g. pumps with attached flanges),
i As of August 5th 117 items were received at Byron.
17 of these items were in stock, 93 installed in the plant of which 18 are inaccessible for testing.
l The balance of items, 7 flanges, are not installed in any safety-related systems. All items are HJM produced flanges.
LaSallt - The record review of construction and modification documents l
that may contain flanges and fittings is couplete. General Electric has substantially completed their review of NSSS related purchase orders and found i
no components furnished by the suspect manufacturers. A few items require l
additional vendor contact.
These items are not expected to contain HJM or PSI components.
l To date LaSalle has identified 132 items received 42 of these items were in stock. 60 items are installed with 17 1ccated in inaccessible areas of the plant. The remaining 30 items have been vertfled as not installed in l
safety-related systems.
t
)
1 i
i l
i i
I
i
)
l,*
i t
i Page 3 1
i I
Qf11 din - The document review at Oresden involved purchase orders dating back to January 1, 1976.
Since Dresden is a plant built to the ANSI B3).1 Code many items are received with Certificates of Conformance (C of C's) rather tlian i
Certified Material Test Reports (CMTR's).
This factor complicated the search since j
the original manufacturer was not always listed on the C of C document, j
I Based on the review of P.O.'s with documents traceable to component
[
manufacturer. Dresden has identified 12 HJM flanges. These flanges are installed I
in the plant but because of the temporary suspension of 88-05 activities their l
{
location has not been verified.
l i
Quad Cities - The record review at Quad, similar in scope to that at Dresden, uncovered 77 HJM flanges.
Five of these items are in the storeroom with the other j
l 72 located in the plant. Because of the temporary suspension, the accessibility of j
these flanges for testing has not been determined.
Zinn - Similar to Dresden and Quad, the review of station and contractor f
purchase and receipt documents extended back to January 1, 1976.
The search identified 244 HJM produced items.
Fifty-two were on the shelf, the remaining 192 have yet to be verified as installed.
l To date, the only 88-05 related items identified at Commonwealth Edison f
Nuclear Stations have been HJM flanges, j
In addition to document review, all stations have compiled lists of vendors, I
equipment and specifications for which CMTR's or other forms of traceability are I
[
not available on site.
[
_ TESTING Our testing program began on June 9th, 1988 with Commonwealth Edison's System Haterial Analysis personnel performing EQUOT!P hardness checks on all 165 in-stock i
flanges at Draidwood Station, r
j Initial results indicated a problem with the values obtained with heats LO900, 5448782, CEX, T433, 1855 and 958. Since these were small, light weight flanges and f
difficult to stabilize during testing it was suspected that the EQUOTIP readings l
were inaccurate.
g One flange from each of these heats was brcught into Commonwealth Edison's l
System Material Analysis Department (SMAD) Metallurgy Lab for Rockwell B hardness
}
checks.
l I
i i
Page 4 All derivsd Brinell hardness values from the lab tests on these six flanges l
exceeded the EQUOT!P ot*ained values.
(See Table 1).
Five of the sample flanges were within the hardness value acceptance range and l
as a result the remaining 72 flanges of those 5 heats were deemed acceptable. Heat LO900 although showing an improved hardness value was stiil slightly below the established lower bound.
Subsequent tests (Table 2) performed by Charles Kawin Metallurgical Laboratories confirmed that the strength of LO900 was indeed below SA 105 requirements.
In addition, a macro-etch of the flange revealed that the flange had been machined from plate rather than forged as required by the material specification.
This in it! elf was r-
'o declare heat LO900 nonconforming.
t Because of the uncertainties mD (QUOTIP testing of small stock itets ehich could not be adequately st
'T all stock items identified at Byron and LaSalle wore brought into the la aardness screening. Heat 57410, because of its poor hard9ess value, was also.,.. out for full mechanical and chemical tests (results in Table 2).
Attachment B contains Edison's hardness test data.
The listing does not enntain hardness values for 76 of Braidwood's HJH flanges.
This is because 72 flanges were qualified by tests per ormed on lab samples and 4 flanges, ahhough tested, are stainless steel for which hardness is not descrictive of mechanical i
properties.
l t
Those items with a "*" preceding thi Station I.D. are items which were tested i
in the lab.
The hardness values were obtained by converting from Rockwell numbers l
ustig the EQUOTIP conversion chart.
l t
Su'nmarizing our testing information, of the 165 stock flanges tested at i
Braidwood. 2 items from heat LO900 were declared nonconforming and flange #BR-006 (Line Item BH-009) from heat 217243 tetted above the high value of 187.
[
)
l Byron tested a total of 91 flanges,17 from stock.
Fif ty-seven of these are 1
acceptable and 34 are outside the range of 137 - 187.
Four of these 34 tv.ted high.
f 4
)
LaSalle had 62 of their HJM flanges tested. Nineteen of these items were from stock.
Forty-seven test results were acceptable, 15 tested outside the normal t
range.
}
4 1
1 i
l i
l
)
I J
I i
i
Page 5 i
MGIE ERING ANALYSIS In the course of our records review and test program several items were found l
to be nonconforming or inaccessible for testing.
Based on the requirements of the original bulletin and Supplement 1, all installed nonconforming components and inaccessible components were reported to the NRC by phone within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> of their discovery.
Engineering evaluations were performed for all discovered flanges (LaSalle 1&?,
Byron 1&2 and Braidwood 1&2) that were found to be nonconforming (hardness testing) or inaccessible for testing as required by the Bulletin 88-05.
Justifications for Continued Operation (JCOs) were prepared for each component.
Components identified or located after the issuance of Supplement 2 were not I
I tested nor had JCOs prepared.
In addition, a generic engineering evaluation was performed for flanges.
This generic evaluation provided, with a few size and system exceptions, justification for continued operation for LaSalle Units 102, Byron Units 1&2 and Braidwood 1&2.
These generic evaluations were perforr'ed assuming lower bound yield and ultimate values of 27.000 rsi and 44.000 psi respectively.
Thegenericjustificationis also applicable for many of the flunges in Dresden, Quad Cities, and Zion.
The generic analysis performed for these stations was more conservative because l
individual piping design pressures and temperatures were not available on a j
detailed line by line computerized data base.
It is expected that a detailed evaluation of any 7ecific item not covered by the generic justification would also be acceptable, j
\\
l t
[
l l
6287B/10-14 i
l r
\\
1 1
TABLE 1 EQUOTIP HARONESS VALUES VERSUS LAB DERIVIO HARDNESS VALUES STATION I.D.
HEA1 LINE ITEM BRINELL VALUE BRINELL VAltlE (EQUOTIP)
(ROCKHELL)
BR-110 LO900 BH-002 129 133 BR-112 958 BH-003 139 140 1
BR-069 CEX BH-021 136 152 i
BR-078 T433 BH-010 130 153
[
BR-109 5448782 BH-014 113 153 1
l BR-125 1856 BH-004 145 169
{
BR-015*
1663 B&011 160 178 "tr.sted for control purposes i
%LE 2
[
HECHANICAL +
EMICAL TEST RESULTS
(
i l
HECHANICAL TESTS l
STATION !.0. (HEAT) Y! ELD TENS!LE ELONGATION REDUCTION (PSI)
(PSI)
(PERCENT) 0F AREA (PERCENT) f BR-110 (LO900) 47,820 67,570 32.0 64.7 BY#4 (57410) 35,200 48,180 40.5 77.0 j
l CNEHICAL TESTS St Hn C
P S
Ni Cr Ho Cu BR-110 (LO900)
.25 1.00.18.020
.02
.02
.02
.01
.02 L
BY#4 (57410)
.01
.29
.08
.005
.006.01
.01
.01
.02 i
6287B/16
O t
I INDEX TO MATERIAL DATABASE-PLANT - Station which received the item. Since the field in only 6 characters wide some station names have been condensed.
I' LINE ITEM - A unique identifier derived from a single CMTR entry.
SIZE - Nominal pipe size (inches).
ITEM - Type of component, in all cases "FLG" for flange, j
PRESSURE RATING - Standard ANSI rating, e.g. 150 lb.
TYPE - Type of flange. BL - blind ; LJ - lapped joint ; RF - raised face ;
SO, slip on ; SH - socket weld ; TH = threaded ; HN - welding neck ; T&G -
tongue and groove.
SPEC / GRADE - ASTM material specification.
HEAT - Heat number listed on the CMTR.
Test code given ir, parentheses after heat number. Heat numbers preceded by "#" have items which have below i
normal hardness results.
i OATE OF CMTR - Date listed on CMTR.
i SUPPLIER - Vendor which supplied item to Commonwealth Edison (in most cases though a piping contractor).
ASHE CLASS - Class of component as listed on the CMTR.
"0" being a non-section III component.
TOTAL QUANTITY - Total number of that item received.
QUANTITY ACCESSIBLE - Total number of that item verified as installed in safety related systems.
QUANTITY INACCESSIBLE - Total number of that item thought to be installed in a safety related system which is not accessible for hardness testing durina olant oceration.
T 62878/15 a
1
m.-.
Page to.
1 09/07/88 ATTACHMENT A COMMONWEALTH EDISON'S 88-05 MATERIAL DATA 8ASE PLANT LINE SIZE / ITEM PRESSURE / TYPE SPEC / GRADE NEAT DATE OF SUPPLIER ASME TOTAL QUANTITY QUANTITY QUANTITY ITEM RATING CMTR CLASS QUANTITY IN STOCK ACCESF?BLE INACCESSIBLE
- SRAIDW 3RAIDW SW-001 4.00 FLG 300 RF W 105 1167 11/03/80 CUTON 2
1 0
1 0
BRAIDW SW-002 2.00 FLG 1500 RF SW 105
- LO900 10/28/86 JOLIET VALVE 2
6 2
0 3
SRAIDW SW-003 2.00 FLG 600 RF SW 105 958 03/03/82 CAPITOL PIPE 2
8 7
0 0
SRAIDW SW-004 2.00 FLG 600 RF SW 105 1855 03/03/82 CAPITOL PIPE 2
17 17 0
0 SRAIDW SW-005 0.75 FLG 1500 RF SW 105 Cox 04/07/86 JOLIET VALVE 2
6 3
0 3
BRAIDW SW-006 6.00 FLG 150 RF W 105 CND 01/03/86 JOLIET VALVE 2
4 2
2 0
SRAIDW BW-007 6.00 FLG 150 RF BL 105 CPC 01/03/86 JOLIET VALVE 2
4 2
2 0
SRAIDW SW-006 8.00 FLG 150 RF BL 105 217243 02/07/86 JOLIET WALVE 2
2 2
0
,0 i
4 BRAIDW SW-009 8.00 FLG 150 RF WM 105 217243 02/07/86 JOLIET VALVE 2
4 4
0 0
BRAIDW SW-010 1.50 FLC 300 RF SW 105 T433 02/18/82 CAPITOL PIPE 2
50 34 5
0 SRAIDW SW-011 2.00 FLG 150 RF SW 105 22614(A144) 02/18/82 CAPITOL PIPE 2
80 30 27 0
DRAIDW eW-012 1.50 FLG 150 RF SW 105 658C283(VK) 02/18/82 CAPITOL PIPE 2
80 29 12 0
j 3RAIDW SW-013 1.00 FLG 150 RF SW 105 1663(A79) 02/18/82 CAPITOL PIPE
-2 80 to 21 0
j 3RAIDW SW-014 0.75 FLG 150 RF SW 105 5448782(64C) 02/18/82 CAPITOL PIPE 2
- 50 2
13 0
SRAIDW eW-015 4.00 FLG 1500 RF W 182 89049 05/02/86 JOLIET VALVE 2
6 2
4 0
i SRAIDW SW-016 2.00 FLJ 1500 RF SW 105 22478 04/11/83 CHICACO TUBE 2
10 0
0 10 saAIDW SW-017 2.50 FLG 150 RF W 105 M45782 03/29/83 CHICACO TUSE 2
6 0
6 0
t m
..e
l l
Page so.
2 09/07/88 ATTACHMENT A COMMONWEALTN EDISON'S 88-05 MATERIAf DATABASE PLANT LINE SIZE / ITEM PRESSURE /TTPE SPEC /CRADE HEAT DATE OF SUPPLIER ASME TOTAL QUANTITY QUANTITY QUANTITY ITEM RATING OITR CLASS QUANTITY IN STOCK ACCESSISLE INACCESSIBLE GRAIDW SW-018 0.50 FLG 150 RF SW 105 18477 07/06/83 CAPITOL P!PE 2 _
12 0
0 0
BRAIDW SW-019 4.00 FLC 1500 RF W 182 F304 89346 05/02/86 JOLIET VALVE 2
6 2
4 0
SRAIDW au-020 24.00 FLG 150 RF SO 105 1684(2024) 05/22/86 JOLIET VALVE 3
2 0
2 0
SRAIDW EW-021 1.50 FLG 150 RF SW 105 CEx 05/28/86 JOLIET VALVE 2
20 17 2
0 SRAIDW SW-022 0.50 FLG 300 RF SW 182 F304 B334 09/15/86 JOLIET VALVE 2
2 0
1 0
BRAIDW su-023 3.00 FLG 159 RF W 105 CDNM 09/08/83 CHICAGO TUBE 2
2 0
4 0
SRAIDW SW-024 3.00 FLG 150 RF W 105 1533(CFW) 02/07/84 JOLIET VALVE 2
2 0
2 2
SRAIDW SW-026 6.00 FLG 150 RF W 105 1090 03/02/81 JOLIET VALVE 2
12 0
11 0
gAAIDW BW-027 6.00 FLG 900 EF W 105 A412234 03/02/81 JOLIET VALVE 2
2 0
0 0
BRAIDW SW-028 3.00 FLG 30(, RF G MIS 105 A95 02/05/81 BELLOWS
?
2 0
0 0
SRAIDW 59-029 16.00 FLG 150 RF W 105 4693 04/14/81 JOLIET VALVE 2
4 0
'l 0
BRAIDW SW-030 12.00 FLG 150 RF W 105 4612 04/14/81 JOLIET VALVE 2
1 0
2 0
SRAIDW BW-031 2.00 FLC 150 RF w 105 R6833 10/30/81 CAPITOL PIPE 2
4 0
0 0
BRAIDW sW-048 8.00 FLG 300 RF W MIS 105 9774 03/31/81 BELLOWS 2
2 0
0 0
SRAIDW 8W-049 6.00 FLG 150 RF W 105 04553 03/31/81 BELLOWS 2
2 0
2 0
sRAIDW SW-050 8.00 FLG 150 RF W 105 3887 03/31/81 BELLOWS 2
4 0
4 0
sRAlcW sW-05' 12.00 FLG 150 RF WM 105 4612 03/31/81 BELLOWS 2
2 0
0 0
Page No.
3 09/07/83 ATTACHMENT A COM0hWEALTN EfsIS0u'S 88-05 MATERIAL DATABASE PLAuf LINE SIZE / ITEM PRESSURE / TYPE SPEC / GRADE HEAT DATE nF SUPPLIER ASME TOTAL QUANTITY QUANTITY QUANTITY ITEM RA?ING O.TR CLASS QUAACITY In STOCK ACCESSIsLE IuACCESSIBLE BRAIDW sW-052 2.00 FLG 1500 LJ 105 7506(COP) 01/10/85 METAL BELLOW 3
16 0
0 16 BRAIDW sW-054 1.50 FLG 1500 LJ 105 CIx(3340) 11/13/84 METAL BELLOW 3
16 0
0 16-
- Subtotat **
527 165 130 50
- SYRom sYRou SY-001 3.00 FLG 300 RF W 105 1757 01/10/83 CAPITOL 3
8 4
4 0
STRou BY-002 4.00 FLG 300 RF Wu 105 1167 11/03/80 GUY 0st 2
3 1
2 0
STRom sv-003 3.00 FtG 150 RF BL 105 8 57410(A94) 12/10/81 BARR-SAuuDER 2
12 to 2
O s? Rom sY-004 3.00 FLG 150 RF st 105 A94 05/13/81 BARR-SAUNDER 2
5 0
1 0
SYRom 37-005 16.00 FLG 300 RF nas 105 91710 07/29/81 BARR-SAUNDER 2
1 0
0 0
SYRou ST-006 3.00 FLG 150 RF SO 105 A39 06/2'./81 JOLIET-VALVE 2
4 1
1 1
SYRou 8Y-007 6.00 FLG 150 RF st 105 s 93R 12/01/81 BARR-SAUNDER 2
3 0
3 0
9YRou 87-008 6.00 FLG 150 RF SO 105 03543 12/01/81 sARR-SAUuDER 2
3 1
2 0
SYRou SY-000 3.00 FLG 150 R. nas 105 8 4706 12/01/81 BARR-SAUNDER 2
18 0
18 0
SYRon SY-010 3.00 FLG 150 RF nas 105 4645(GDFU) 07/12/82 BARR-SAUNDER 2
24 0
23 1
SYRnu SY-011 14.00 FLG 150 RF SO 105
- T796023 01/24/78 PULLMAN 0
3 0
8 0
BYRom 37-012 16.00 FLG 150 RF Wu 105 4692 09/24/81 BARR-SAUuDER 2
4 0
3 0
BYeou sv-013 18.00 FLG 150 RF nas 105 W2573 05/30/84 WESTIuGNOUSE 2
8 0
8 0
...~
~
l a
4 Dage No.
4 09/07/88 ATTACHMENT A C0 pee 0NWEALTN EDISON'S 88-05 MATERIAL DATABASE
(
PLANT LINE SIZE / ITEM PRESSURE / TYPE SPEC / GRADE HEAT DATE OF SUPPLIER ASME TOTAL QUANTITY QUANTITY QUANTITY ITEM RATING CMTR CLASS QUANTITY IN STOCK ACCESSIBLE INACCESSISLE sYROM SY-014 2.00 FLG 1500 LJ 105 COP (7506) 12/20/84 METAL SEtt0W 3
8 0
0 8
AYROM SY-015 1.50 FLc 1500 LJ 105 COP (75fA) 11/13/84 METAL SELLOW 3
1 0
0 1
SYROM SY-016 1.50 FLG 1500 LJ 105 C:X(3340) 11/13/84 METAL SELLOW 3
7 0
0 7
" Stetotat **
117 17 75 18
" DRESDN DRESDN DR-001 2.00 FLG 1500 T&C 105 22478 01/28/83 SARR COMPANY 0
7 0
0 0
DRESDN DR-002 2.00 FLG 1500 T&G 105 1215(GDES) 01/28/83 8ARR COMPANY 0
4 0
0 0
i 9EESDN DR-003 2.00 FLG 1500 T&G 105 1102(CDON) 01/28/83 sARR COMPANY 0
1 0
0 0
1
- O Stbtotat **
12 0
0 0
" LASALL LOSALL LS-001 6.00 FLG 150 RF SO 105 03543 12/04/80 BARR-SAUNDER 3
2 0
0 1
LOSALL LS-002 3.00 FLG 150 RF SO 105 3453 11/14/83 GUYON 2
4 0
4 0
LCSALL LS-003 8.00 FLG 150 RF SL 105 30195 11/14/80 CUYON 2
2 9
2 0
LOSALL LS-006 1.00 FLG 150 RF SW 105
- A79 04/13/81 SARR-SAUNDER 3
6 0
6 0
LOSALL LS-005 1.00 FLG 1500 RW SW 105 2095 07/07/81 SARR-SAUNDER 2
8 0
4 6
LASALL LS-006 2.00 FLG 300 RF TN 105 T2095 05/12/81 TYLER-DAWSON 2
4 0
2 0
LASALL LS-007 3.00 FLG 150 RF SL 105 A94 08/27/81 TYLER-DAWSON 2
4 0
1 0
u Dage so.
5 09/0F/88 ATTACHMENT A C0fe90NWEALTH EDISOC'S 88-05 MATERIAL DATABASE PLANT LINE SIZE / ITEM PRESSURE /TTPE SPEC / GRADE HEAT DATE OF SUPPLIER ASME TOTAL QUANTITY QUANTITY OUANTITY ITEM RATING CMTR CLASS QUANTITY IN STOCK ACCESSIBLE INiiCESSISLE LASALL LS-006 3.00 FLG 150 RF WM 105 4504 08/27/81 TYLER-DAWSON 2
3 0
3 0
LASALL LS-009 3.00 FLG 150 RF WM 105 4706 08/27/81 TYLER-DAWSON 2
1 0
1 0
LCSALL LS-010 1.00 FLG 1500 RF SW RED 105 6579 11/02/81 TYLER-DAWSON 3
8 0
0 8
LASALL LS-011 1.00 FLG 1500 RF SW 105 2095 11/02/81 TYLER-DAWSON 3
16 0
0 8
j i
LASALL LS-012 1.00 FLG 600 RF SW 1%
84 11/04/81 TYLER-DAWSON 2
12 0
0 0
LCSALL LS-013 12.00 FLG 150 WM 105 37862 12/14/82 CONAX 2
2 0
2 0
LA W L LS-014 1.00 FLG 150 RF SW 105 1663(A79) 07/09/82 JOLIET VALVE 3
6 0
6 0-LASALL LS-015 0.50 FLC 1500 RF SW 105 N76277(GDED) 07/15/82 SARR-SAUNDER 3
6 0
6 0
l LCSALL LS-016 1.00 FLG 150 RF SW 105 8 50816 10/16/86 JOLIET VALVE 2
12 8
4 0
LASALL LS-017 1.00 FLG 1500 RF SW 105 6579 11/05/81 SARR-SAUNDER 2
11 11 0
0 l
LOSALL LS-018 1.00 FLG 1500 RF SW 105 80503 10/22/81 SARR-SAUNDER 2
5 5
0 0
LCSALL LS-019 1.50 FLG 1500 RF SL 105 8 CDP 01/09/87 JOLIET VALVE 1
1 1
0 0
LASALL LS-020 2.50 FLG 300 RF SL 105 CDP 01/09/87 JOLIET VALVE 1
1 1
0 0
LASALL LS-021 1.00 FLG 150 RF SL 105 50816 07/22/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-022 1.00 FLG 150 RF SW 105 50816 07/22/86 JOLIET VALVE 1
2 2
0 0
LASALL LS-023 1.00 FLG 600 RF SW 105 CDOU 07/22/86 JOLIET VALVE 1
2 2
0 0
l LASALL LS-024 3.00 FLG 600alF SL 105 CDP 07/22/86 JOLIET VALVE 1
2 2
0 0
.(
Page No.
6 09/07/88 ATTACHMENT A C0fet0NWEAtTN EDISON'S 88-05 MATERIAL DATABASE PLANT LINE SIZE / ITEM PRESSURE / TYPE SPEC / GRADE MEAT DATE OF SUPPLIER ASIE TOTAL QUANTITY QUANTITY GUANTITY ITEM RATING CMTR CLAtS QUANTITY IN STOCK ACCESSIstE INACCESSIBLE LASALL LS-025 3.00 FLG 150 RF st 105 CDP 07/22/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-026 3.00 FLG 300 RF st 105 CDP 07/22/86 JOLIET VALVE 1
2 2
0 0
LASALL LS-027 3.00 FLG 150 RF st 105 CDP 10/02/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-028 2.00 FLG 150 RF st 105 CON 10/02/86 JOLIET VALVE 1
1 1
0 0
LASALL LS,J29 1.00 FLG 150 RF st 105 50816 05/01/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-030 2.00 FLG 150 RF st 105 CON 12/19/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-031 3.00 FLG 150 RF SW 105 COX 12/19/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-032 3.M FLG 600 RF SL 105 6026843 10/16/86 JOLIET VALVE 1
1 1
0 0
LASALL LS-033 8.00 FLG 150 RF st 105 521x 11/19/80 GUYON 2
2 0
2 ~
0
" Sahtotat "
132 42 43 17
" QUAD QUAD QC-001 1.00 FLG 1500 RF SW 105 1533(CFW) 11/23/83 GUYON 0
18 2
0 0
QUAD QC-002 2.00 FLG 1500 RF SW 105 3916(CNN) 11/23/83 GUYON O
6 2
0 0
GUA0 QC-003 2.00 FLG 1500 RF st 105 3916(CHN) 11/23/83 GUYON O
8 0
0 0
QUA0 QC-004 2.00 FLG 1500 SW 105 3916(Cust) 11/23/83 GUYON O
16 0
0 0
QUAD QC-005 2.00 FLG 150 RF SW 105 8602(CFY) 01/10/84 CUYON 0
4 0
0 0
0U40 GC-006 2.00 FLG 1500 RF WW 105 2167(CND) 02/08/84 CUYON O
5 1
0 0
l J
b Page no.
7 09/07/88
~
ATTACleMENT A 00MM0uWEALTH EDISON'S 88-05 MATERIAL DATABASE PLANT LINE SIZE / ITEM PRESSURE / TYPE SPEC / GRADE HEAT DATE OF SUPPLIER ASME TOTAL QUANTITY QUANTITY QUMTITY ITEM RAT!uG CMTR CLASS QUANTITY IN STOCK ACCESSIBLE IMACCESSISLE QUAD QC-007 1.00 FLG 150 RF SW 105 AAY-84(2903) 11/27/84 Cu!CAGO TUBE 3
6 0
0 0
QUAD OC-006 8.00 FLG 300 RF SL 105 844 09/10/82 SARR-SAUNDER 0
5 0
0 0
QUAD QC-009 8.00 FLG 300 RF W 305 4304 09/02/82 BARR-SAUNDER 0
5 0
0 0
i QUA0 QC-010 20.00 FLG 150 RF W 105 E0330(EU0C) 02/12/82 BARR-SAUNDER 2
4 0
0 0
1 l
l
" Saetotat **
77 5
0 0
l
" ZIou ZION 21-001 1.00 FLG 150 RF SW 105 E1413 03/23/81 BARR-SAUNDER 2
12 0
0 0
ZION 21-002 0.75 FLG 150 RF SW 105 64(
G3/23/81 BARR-SAUNDER 2
12 0
0 0
210m 21-003 0.50 FLG 150 RF SW 105 VP 03/23/81 BARR-SAUNDER 2
12 5
0 0
ZION 21-004 1.50 FLG 150 RF SW 105 1663(A79) 04/25/83 8ARR COMPAsi 0
13 7
0 0
ZIOu 23-005 1.00 FLG 150 RF SW 105 1663(A79) 04/2Si33 SARR COMPANY 0
1 1
0 0
ZION 21-006 1.50 FLG 150 RF SW 105 9903 04/25/83 BARF *nMPANY 0
7 7
0 0
l l
j 210m 21-007 1.00 FLG 150 RF SW 105 1705 04/25/83 BARR COMPANY 0
19 0
0 0
2I04 21-006 0.50 FLG 150 RF SW 105 KG 08/1d 81 Cu!CAGO TUBE 3
24 2
0 0
ZION 21-009 0.50 FLG 150 RF Tu 105 KG 08/12/81 CNICAGO TUBE 3
12 4
0 0
ZIOu 21-010 1.50 FLG 150 RF SW 105 1663(A79) 02'*1/83 BARR-SAUNDER 0
32 18 0
0 ZIou 21-011 1.00 FLG 150 RF SW 105 535 %
08/12/86 JOLIET VALVE 2
24 6
0-0
..n-.-..
_ ~
.~. _~..
O Page No.
8 09/07/88 ATTACHMENT A COMMONWEALTN EDISON'S 88-05 MATERIAL DATASASE PLANT LINE SIZE / ITEM PRESSURE / TYPE SPEC / GRADE NEAT DATE OF SUPPLIER ASME TOTAL QUANTITF QUANTITY QUANTITY ITEM RATING CMTR CLASS QUANTITY IN STOCK ACCESSIBLE INACCESSISLE 2 ION 21-012 1.50 FLG 150 RF SW 105 N86973(GDEN) 07/27/82 SARR-SAU@ER 0
5 1
0 0
ZION 21-013 0.50 FLG 150 RF SW 105 82D 02/16/81 SARR-SAUNDER 0
12 0
0 0
ZION 21-014 0.75 FLG 150 RF SW 105 9C 02/16/81 SARR-SAUNDER 0
12 0
0 0
ZION 21-015 1.00 FLG 150 RF SW 105 E1413 02/16/81 SARR-SAUNDER 0
12 0
0 0
ZION 21-016 0.50 FLG 150 RF SW 105 CST 05/21/86 JOLIET VALVE O
8 1
0 0
ZION 21-017 1.50 FLG 150 RF SW 105 N86973(GDEN) 07/27/82 SARR-SAUNDER 0
20 0
0 0
ZION 21-018 1.50 FLG 150 RF SW 105 N86973(GDEN) 12/13/82 SARR-SAU WER 0
4 0
0 0
ZION 21-019 10.00 FLG 150 RF SO 105 4470 09/29/82 SARR-SAUNDER 0
3 0
0 0
- Sehtotat **
244 52 0
0
- Totat =
1109 281 248 85
e e
Page No.
1 08/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PLANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS CYRON
- BYi4 BY-003 3.00 150 RF BL 105 i 57410(A94) 99 CYRON
- BYf5 BY-003 3.00 150 RF BL 105 8 57410(A94) 99 CYRON
- BYf6 BY-003 3.00 150 RF BL 105 8 57410(A94) 99 CYRON
- BYg7 BY-003 3.00 150 RF BL 105
- 57410(A94) 99 CYRON
- BYf8 BY-003 3.00 150 RF BL 105
- 57410(A94) 99 CYRON
- BY#9 BY-003 3.00 150 RF BL 105
- 57410(A94) 99 CYRON
- BYfl0 BY-003 3.00 150 RF BL 105 8 57410(A94) 99 CYRON
- BY#11 BY-003 3.00 150 RF BL 105
- 57410(A94) 100 CYRON
- BY312 BY-003 3.00 150 RF BL 105
- 57410(A94) 100 LASALL *LA-A LS-016 1.00 150 RF SW 105
- 50816 103 LASALL *IA-C LS-016 1.00 150 RF SW 105 8 50816 103 LASALL *IA-B LS-016 1.00 150 RF SW 105 i 50816 104 CYRON
- BYg13 BY-003 3.00 150 RF BL 105
- 57410(A94) 104 LASALL IAS-002 LS-016 1.00 150 RF SW 105
- 50816 106 IASALL IAS-004 LS-016 1.00 150 RF SW 105
- 50816 106 LASALL *IA-F LS-016 1.00 150 RF SW 105
- 50816 106 IASALL *IA-H LS-016 1.00 150 RF SW 105
- % 816 112 CYRON T796023-1 BY-011 14.00 150 RF SO 105
- T796023 113
-- _. _ _ _ _ ~
C Page No.
2 l
03/25/88 ATTACHMENT B l
88-05 FIELD TEST RESULTS PIANT STATION 7.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS LASALL LAS-003 LS-016 1.00 150 RF SW 105 8 50P.16 114 LASALL *LA-G LS-016 1.00 150 RF SW 105
- 50816 114 CYRON T796023-4 BY-011 14.00 150 RF SO 105
- T796023 120 CYRON T796023-7 BY-011 14.00 150 RF SO 105
- T796023 120 LASALL *LA-D LS-016 1.00 150 RF SW 105 8 50816 120 LASALL *LA-E LS-016 1.00 150 RF SW 105
- 50816 120 CYRON T796023-3 BY-011 14.00 150 RF SO 105 i T796023 121 CYRON T796023-6 BY-011 14.00 150 RF SO 105
- T796023 121 BYRON T796023-2 BY-011 14.00 150 RF SO 105
- T796023 122 LASALL LAS-001 LS-Ol6 1.00 150 RF SW 105
- 50816 124 CYRON A94-6 BY-003 3.00 150 RF BL 105
- 57410(A94) 125 CYRON 93R-2 BY-007 6.00 150 RF BL 105
- 93R 126 CYRON T796023-5 BY-011 14.00 150 RF SO 105
- T796023 127 CYRON 4706-3 BY-009 3.00 150 RF WN 105 8 4706 129 CYRON 93R-1 BY-007 6.00 150 RF BL 105
- 93R 130 CYRON 4706-2 BY-009 3.00 150 RF WM 105
- 4706 130 CYRON 4706-6 BY-009 3.00 150 RF WN 105
- 4706 130 CYRON 4706-7 BY-009 3.00 150 RF WN 105
- 4706 130
.=,
G Page No.
3 CO/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PLANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS CYRON 4706-14 BY-009 3.00 150 RF WN 105
- 4706 130 LASALL LAS-028 LS-004 1.00 150 RF SW 105
- A79 130 CYRON 4706-1 BY-009 3.00 150 RF WN 105 8 4706 131
\\
CYRON 4706-9 BY-009 3.00 150 RF WN 105
- 4706 131 CYRON 4706-8 BY-OO9 3.00 150 RF WN 345 i 4706 132 CYRON T796023-8 BY-011 14.00 150 RF SO 105
- T796023 133 BRAIDW *BR-110 BW-002 2.00 1500 RF SW 105 1 ID900 133 IASALL *IA-004 IS-019 1.50 1500 RF BL 105
- COP 135 CYRON 4706-17 BY-009 3.00 150 RF WN 105
- 4706 136 BYRON 4706-13 BY-009 3.00 150 RF WN 105 8 4706 137 IASALL IAS-016 LS-002 8.00 150 RF SO 105 3453 137 IASALL LAS-017 LS-002 8.00 150 RF SO 105 3453 137 IASALL LAS-018 LS-002 8.00 150 RF SO 105 3453 137 LASALL IAS-048 LS-00".
3.00 150 RF WN 105 4706 137 CYRON 93R-3 BY-007 6.00 150 RF BL 105
- 93R 138 BYRON 4692-1 BY-012 16.00 150 RF WN 105 4692 138 BYRON 4692-3 BY-012 16.00 150 RF WN 105 4692 138 LASALL LAS-032
. LS-011 1.00 1500 RF SW 10*
2095 138
\\
=
4 Page No.
4 03/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PLANT STATION I.D.
LINE ITEM SIZE RAT 1.4G / TYPE SPEC / GRADE HEAT HARDNESS IASALL LAS-020 LS-003 8.00 150 RF BL 105 30195 139 CYRON 4706-16 BY-OO9 3.00 150 RF WM 105 8 4706 140 IASALL LAS-015 LS-002 8.00 150 RF SO 105 3453 140 BRAIDW *BR-112 BW-003 2.00 600 RF SW 105 958 140 CYRON 4706-11 BY-009 3.00 150 RF W; 105 8 4706 141 IASALL *IA-005 IS-032 3.00 600 RF BL 105 6026843 141 cYRON 1757-3 BY-001 3.00 300 RF WN 105 1757 142 CYRON 1167-1 BY-002 4.00 300 RF WN 105 1167 142 CYRON 1167-2 BY-OO2 4.00 300 RF WM 105 1167 142 IASALL IAS-022 LS-033 8.00 150 RF BL 105 521X 142 IASALL IAS-092 LS-015 0.50 1500 RF SW 105 N76277 (GDED) 142 IASALL IAS-021 LS-033 8.00 150 RF BL 105 521X 143 CYRON 1757-4 BY-OO1 3.00 300 RF WN 105 1757 144 CYRON 4706-10 BY-009 3.00 150 RF WN 105 9 4706 144 CYRON W2573-6 BY-013 18.00 150 RF WN 105 W2573 144 IASALL IAS-040 LS-006 2.00 300 RF TH 105 T2095 144 LASALL LAS-091 LS-015 0.50 1500 RF SW 105 N76277 (GDED) 144 LASALL IAS-098 LS-013 12.00 150 WN 105 37862 144
s 9
Page No.
S CO/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS BRAIDW BR-145 BW-011 2.00 150 RF SW 105 22614(A144) 144 BRAIDW BR-159 BW-011 2.00 150 RF SW 105 22614(A144) 144 LASALL *LA-DO3 LS-020 2.50 300 RF BL 105 COP 144 LASALL *IA-007 IS-023 1.00 600 RF SW 105 GDDU 144 CYRON 4706-12 BY-009 3.00 150 RF WN 105
- 4706 145 CYRON W2573-2 BY-013 18.00 150 RF WN 105 W2573 145 LASALL LAS-097 LS-013 12.00 150 WN
'105 37862 145 BRAIDW BR-161 BW-011 2.00 150 RF SW 105 22614(A144) 145 CYRON W2573-7 BY-013 18.00 150 RF WN 103 W2573 146 LASALL LAS-026 LS-004 1.00 150 RF EW 105
- A79 146 CYRON A94-2 BY-OO4 3.00 150 RF BL 105 A94 147 BRAIDW BR-137 BW-011 2.00 150 RF SW 105 22614(A144) 147 BRAIDW BR-162 BW-011 2.00 150 RF SW 105 22614(A144) 147 LASALL *LA-OO6 LS-031 3.00 150 RF SW 105 COX 147 LASALL *LA-009 LS-022 1.00 150 RF SW 105 50816 147 CYRON
- BY#1 BY-002 4.00 300 RF WN 105 1167 147 CYRON 4706-4 BY-009 3.00 150 RF WN 105
- 4706 148 LASALL LAS-031 LS-011 1.00 1500 RF SW 105 2095 148
~
o l
Page No.
6 l
C8/25/88 ATTACilMENT B 88-05 FIELD TEST RESULTS PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS BRAIDW BR-053 BW-012 1.50 150 RF SW 105 658C283(VK) 148 BRAIDW BR-160 BW-011 2.00 150 RF SW 105 22614(A144) 148 CYRON
- BY#16 BY-001 3.00 300 RF WN 105 1757 148 CYRON W2573-1 BY-013 18.00 150 RF WN 105 W2573 149 IASALL LAS-093 LS-015 0.50 1500 RF SW 105 N76277 (GDED) 149 BRAIDW BR-027 BW-005 0.75 1500 RF SW 105 COX 149 BRAIDW BR-143 BW-011 2.00 150 RF SW 105 22614(A144) 149 BRAIDW BR-150 BW-011 2.00 150 RF SW 105 22614(A144) 149 BRAIDW BR-151 BW-011 2.00 150 RF SW 105 22614(A144) 149 BRAIDW BR-152 BW-011 2.00 150 RF SW 105 22614(A144) 149 CYRON 03543-1 BY-008 6.00 150 RF SO 105 03543 150 CYRON 03543-2 BY-008 6.00 150 RF SO 105 03S43 150 BRAIDW BR-026 BW-005 0.75 1500 RF SW 105 COX 150 BRAIDW BR-048 BW-012 1.50 150 RF SW 105 658C283(VK) 150 BRAIDW BR-140 BW-011 2.00 150 RF SW 105 22614(A144) 150 BRAIDW BR-ISS BW-011 2.00 150 RF SW 105 22614(A144) 15e CYRON
- BYJ1/
BY-Oc1 3.00 300 RF WN 105 1757 150 CYRON GDFU-17 BY-010 3.00 150 RF WN 105 464S(GDFU) 151 1
._=..__
i l
o l
i Page No.
7 C8/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PIANT STATION I.D. LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS LASALL LAS-029 IS-011 1.00 1500 RF SW 105 2095 151 LASALL LAS-094 LS-015 0.50 1500 RF SW 105 N76277 (GDED) 151 BRAIDW BR-003 BW-007 6.00 150 RF BL 105 CPC 151 BRAIDW BR-025 BW-005 0.75 1500 RF SW 105 COX 151 CYRON W2573-4 BY-013 18.00 150 RF WN 105 W2573 152 BRAIDW BR-009 BW-006 6.00 150 RF WN 105 CND 152 BRAIDW BR-021 BW-013 1.00 150 RF SW 105 1663(A79) 152 BRAIDW BR-138 BW-011 2.00 150 RF SW 105 22614(A144) 152 BRAIDW BR-142 BW-011 2.00 150 RF SW 105 22614(A144) 152 BRAIDW BR-158 BW-011 2.00 150 RF SW 105 22614(A144) 152 BRAIDW BR-164 BW-011 2.00 150 RF SW 105 22614(A144) 152 BRAIDW *BR-069 BW-021 1.50 150 RF SW 105 CEX 152 IASALL IAS-039 LS-006 2.00 300 RF TH 105 T2095 153 BRAIDW BR-016 BW-013 1.00 150 RF SW 165 1663(A79) 153 BRAIDW BR-017 BW-013 1.00 150 RF SW 105 1663(A79) 153 BRAIDW BR-038 BW-012 1.50 150 RF SW 105 658C283(VK) 153 BRAIDW BR-049 BW-012 1.50 150 RF SW 105 658C283(VK) 153 BRAIDW-BR-052 BW-012 1.50 150 RF SW 105 658C283(VK) 153
Page No.
8 C3/25/88
~ ~,
ATTACHMENT B 88 -05 FIELD TEST RESULTS l
PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS BRAIDW BR-136 BW-011 2.00 150 RF SW 105 22614(A144) 153 BRAIDW "3R-156 BW-011 2.00 150 RF SW 105 22614(A144) 153 BRAIDW BR-163 BW-011 2.00 150 RF SW 105 22614(A144) 153 IASALL *IA-008 LS-023 1.00 600 RF SW 105 GDDU 153 BRAIDW *BR-109 DW-014 0.75 150 RF SW 105 5448782(64C) 153 BRAIDW *BP.-078 BW-010 1.50 300 RF SW 105 T433 153 CYRON 1757-1 BY-001 3.00 300 RF WN 105 4757 154 CYRON 1757-2 BY-001 3.00 300 RF WN 105 1757 154 CYRON A94-1 BY-004 3.00 150 RF BL 105 A94 154 BRAIDW BR-042 BW-012 1.50 150 RF SW 105 658C283(VK) 154 BRAIDW BR-141 bW-011 2.00 150 RF SW 105 22614(A144) 154 BRAIDW DR-146 BW-011 2.00 150 RF SW 105 22614(A144) 154 IASALL IAS-095 LS-015 0.50 1500 RF SW 105 N76277(GDED) 155 BRAIDW BR-035 BW-012 1.50 150 RF SW 105 658C283 (VK) 155 CYRON A39-2 BY-006 3.00 150 RF SO 105 A39 156 SYRON GDFU-23 BY-010 3.00 150 RF WN 105 464S(GDFU) 156 LASALL IAS-019 LS-003 8.00 150 RF BL 105 30195 156 i
BRAIDW BR-028 BW-012 1.50 150 RF SW 105 658C283(VK) 156 l
1
. _. -... - - - =
L Page No.
9 CO/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS BRAIDW BR-045 BW-012 1.50 150 RF SW 105 658C283(VK) 156 IASALL *IA-002 LS-024 3.00 600 RF BL 105 CCP 156 IASALL *IA-010 LS-029 1.00 150 RF BL 105 50816 156 IASALL *IA-011 IS-021 1.00 150 RF BL 105 50816 156 CYRON W2573-8 BY-013 18.00 150 RF WM 105 W2573 157 8RAIDW BR-024 BW-013 1.00 150 RF SW 105 1663(A79) 157 BRAIDW BR-032 BW-012 1.50 150 RF SW 105 658C283(VK) 157 BRAIDW BR-051 BW-012 1.50 150 RF SW 105 658C283(VK) 157 BRAIDW BR-149 BW-011 2.00 150 RF SW 105 22614(A144) 157 CYRON 4692-2 BY-012 16.00 150 RF WN 105 4692 158 BRAIDW BR-165 BW-011 2.00 150 RF SW 105 22614(A144) 158 CYRON GDMJ-7 BY-010 3.00 150 RF WN 105 464S(GDFU) 159 i
CYRON W2573-3 BY-013 18.00 150 RF WN 105 W2573 159 IASALL IAS-096 LS-015 0.50 1500 RF SW 105 N76277(CDED) 159 BRAIDW BR-037 BW-012 1.50 150 RF SW 105 658C283(VK) 159 IASALL *IA-001 LS-026 3.00 300 RF BL 105 COP 159 CYRON
- BYt15 BY-001 3.00 300 RF WN 105 1757 159 l
l BRAIDW BR-039 BW-012 1.50 150 RF SW 105 658C283(VK) 160 l
l
- - =
e l
1 1
Page No.
10 03/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS l
BRAIDW BR-148 BW-011 2.00 150 RF SW 105 22614(A144) 160 BRAIDW BR-157 BW-011 2.00 150 RF SW 105 22614(A144) 160 BYRON
- BY$14 BY-OO1 3.00 300 FF WM 105 1757 160 CYRON GDFU-15 BY-010 3.00 150 RF WM 105 4645(GDFU) 161 BRAIDW BR-144 BW-011 2.00 150 RF SW 105 22614(A144) 161 CYRON GDFU-19 BY-010 3.00 150 RF WN 105 4645(GDFU) 162 CYRON W2573-5 BY-013 18.00 150 RF WN 105 W2573 162 LAs%LL IAS-027 LS-004 1.00 150 RF SW 105 i A79 162 BRAIDM BR-046 BW-012 1.50 150 RF SW 105 658C283(VK) 162 BRAIDW BR-056 BW-012 1.50 150 RF SW 105 658C283(VK) 162 BRAIDW BR-139 BW-011 2.00 150 RF SW 105 22614(A144) 162 BRAIDet BR-147 BW-011 2.00 150 RF SW 105 22614(A144) 162 BRAIDW BR-153 BW-011 2.00 150 RF SW 105 22614(A144) 162 CYRON GDFU-9 BY-010 3.00 150 RF WM 105 4645(GDFU) 163 CiRON CDFU-22 BY-010 3.00 150 RF WN 105 4645(GDFU) 163 IASALL IAS-030 LS-011 1.00 1500 RF SW 105 2095 163 l
BRAIDW BR-044 BW-012 1.50 150 RF SW 105 658C283JVK) 163 CYRON
- BYi2
- BY-008 6.00 150 RF SO 105 03543 163
. - - _ _ _ = _. _, -..
e Page No.
11
~
l 08/25/88 i
ATTACHNENT B l
88-05 FIELD TEST RESULTS PIJurr STATION I.D.
LINE ITEN SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS CYRON GDFU-3 BY-010 3.00 150 RF WN 105 464S(GDFU) 164 CYRON GDFU-S BY-010 3.00 150 RF WN 105 464S(GDFU) 164 CYRON GDFU-21 BY-010 3.00 150 RF WN 105 464S(GDFU) 164 BRAIDW BR-020 BW-013 1.00 150 RF SW 105 1663(A79) 164 BRAIDW BR-034 BW-012 1.50 150 RP SW 105 658C283(VK) 164 BRAIDW BR-047 BW-012 1.50 150 RF SW 105 658C283(VK) 164 BYRON GDFU-8 BY-010 3.00 150 RF WN 105 464S(GDFU) 165 BRAIDW BR-050 BW-012 1.50 150 RF SW 105 658C283(VK) 165 BRAIDW BR-154 BW-011 2.00 150 RF SW 105 22614(A144) 165 CYRON GDFU-4 BY-010 3.00 150 RF WM 105 464S(GDFU) 166 CYRON GDFU-16 BY-010 3.00 150 RF WM 105 464S(CDFU) 166 CYRON GDFU-20 BY-010 3.00 150 RF WM 105 464S(GDFU) 166 IASALL IAS-087 LS-014 1.00 150 RF SW 105 1663(A79) 166 BRAIDW BR-019 BW-013 1.00 150 RF SW 105 1663(A79) 166 BRAIDW BR-041 BW-012 1.50 150 RF SW 105 658C283(VK) 166 BRAIDW BR-OSS BW-012 1.50 150 RF SW 105 658C2d3(VK) 166 BRAIDW BR-040 BW-012 1.50 150 RF SW 105 658C283(VK) 167 CYRON GDFU-14 BY-010 3.00 150 RF WN 105 464S(GDFU) 168
_ _. _ _ = _.. _ _ _. _-
-_=.- __.
. _ ~
Page No.
12
~
CD/25/88 ATTACIDtENT B 88-05 FIELD TEST RESULTS PLANT STATION I.D. LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT liARDNESS BRAIDW BR-001 BW-008 8.00 150 RF BL 105 217243 168 BRAIDW BR-010 BW-006 6.00 150 RF WN 105 CND 168 BRAIDW BR-029 BW-012 1.50 150 RF SW 105 658C283(VK) 168 BRAIDW BR-036 BW-012 1.50 150 RF SW 105 658C283(VK) 168 BRAIDW BR-054 BW-012 1.50 150 RF SW 105 658C283(VK) 168 CYRON GDFU-12 BY-010 3.00 150 RF WN 105 4645(GDFU) 169 CYRON GDFU-13 BY-010 3.00 150 RF WN 105 4645(GDFU) 169 BRAIDW BR-022 BW-013 1.00 150 RF SW 105 1663(A79) 169 BRAIDW BR-031 BW-012 1.50 150 RF SW 105 658C283(VK) 169 BRAIDW *BR-125 BW-004 2.00 600 RF SW 105 1855 169 BRAIDW BR-005 BW-009 8.00 150 RF WN 105 217243
-170 BRAIDW BR-008 BW-009 8.00 150 RF WM 105 217243 170 CYRON GDFU-18 BY-010 3.00 150 RF WN 105 4645(GDFU) 171 BRAIDW BR-023 BW-013 1.00 150 RF SW 105 1663(A79) 171 LASALL IAS-044 IS-007 3.00 150 RF BL 105 A94 172 l
BRAIDW BR-043 BW-012 1.50 150 RF SW 105 658C283(VK) 172 CYRON
.n
I Page No.
13 CO/25/88 ATTACHMENT B 88-05 FIELD TEST RESULTS PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS BRAIDW BR-033 BW-012 1.50 150 RF SW 105 658C283(VK) 173 CYRON GDFU-2 BY-010 3.00 150 RF WM 105 4645(GDFU) 174 CYRON 4706-15 BY-009 3.00 150 RF WN 105 f 4706 175 CYRON GDFU-11 BY-010 3.00 150 RF WN 105 4645(GDFU) 175 IASALL IAS-045 LS-008 3.00 150 RF WM 105 4504 175 IASALL IAS-046 IS-008 3.00 150 RF WM 105 4504 175 IASALL LAS-088 LS-014 1.00 150 RF SW 105 1663(A79) 175 BRAIDW BR-004 BW-008 8.00 150 RF BL 105 217243 176 IASALL IAS-023 LS-004 1.00 150 RF SW 105 i A79 178 BRAIDW BR-002 BW-007 6.00 150 RF BL 105 CPC 178 BP.AIDW BR-007 BW-009 8.00 150 RF WN 105 217243 178 BRAIDW *BR-015 BW-013 1.00 150 RF SW 105 1663(A79) 178 IASALL IAS-024 LS-004 1.00 150 RF SW 105
- A79 180 IASALL IAS-085 IS-014 1.00 150 RF SW 105 1663(A79) 180 IASALL IAS-090 LS-014 1.00 150 RF SW 105 1663(A79) 181 IASALL IAS-025 LS-004 1.00 150 RF SW 105 i A79 182 BRAIDW BR-030 BW-012 1.50 150 RF SW 105 658C283 (VK) 184 IASALL IAS-086
,LS-014 1.00 150 RF SW 105 1663(A79) 185
b
. - :7 9
s Page No.
14 CO/25/88 I
ATTACHNENT B f
88-05 FIELD TEST RESULTS i
PIANT STATION I.D.
LINE ITEM SIZE RATING / TYPE SPEC / GRADE HEAT HARDNESS IASALL IAS-089 LS-014 1.00 150 RF SW 105 1663(A79) 186 CYRON GDFU-10 BY-010 3.00 150 RF WN 105 464S(GDFU) 189 LASALL IAS-047 LS-OO8 3.00 150 RF WN 105 4504 190 BRAIDW BR-OO6 BW-OO9 8.00 150 RF WN 105 217243 190 CYF.2ON GDFU-24 BY-010 3.00 150 RF WM 105 464S(GDFU) 193 CYRON 4706-5 BY-OO9 3.00 150 RF WM 105
- 4706 195 CYRON GDFU-6 BY-010 3.00 150 RF WM 105 464S(GDFU) 199
,.-r,,.
~..
-.,---..-r
r--4-,-..-
uw-
- +
w-r
+e
.