Provides Written Confirmation of 880829 Prompt Notification of Reportable Occurrence Re Fire Protection Program.License Condition 2.G Notification Not Required.Cause & Any Corrective Actions Will Be Submitted by 880912
ML20154C779
Person / Time
Site: San Onofre 
Issue date: 08/30/1988
From: Morgan H
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
NUDOCS 8809150021
Download: ML20154C779 (2)


Text

_ _ _ _ _ _ _

n M*'"

"/*'u,-

' ?,l NEGtd,j'CO Southem Califomla Edison Company y,

saw osorar svetran ocuraarino srAt

.5.?P g e o sox ine

./O.'ly sas coeursrc. cauroasia enn 44 c MORoaN T E L E Pe40.e g evar

. ~^*'"

August 30, 1988 U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 At stion:

John B. Martin, Regional Administrator De Sir:

Subject:

Docket No. 50 362 Prompt Report License Condition 2.C.(12)a San Onofre Nuclear Generating Station, Unit 3 This submittal provides written confirmation of our prompt notification of August 29, 1988, pursuant to License Condition 2.G to Facility Operating License NPF-15 for San Onofre Unit 3, of a reportable occurrence associated w:th the fire protection program.

License Condition 2.C.(12)a requires that SCE maintain in effect and fully implement the Fire Protection Plan as delineated in the Fire Hazards Analysis (FHA). Certain Appendix R fire scenarios require that one of the two Atmospheric Dump Valves (ADVs) be manually operated to achieve and maintain safe shutdown. A condition was discovered during performance of maintenance activities on 8/26/88 and 8/28/88 for valves 3HV-8421 and 3HV-8419, respectively, wherein the valves exhibited excessive resistance to manual operation.

It has been determined that this condition rendered both ADVs inoperable for manual operation.

This condition however, did not affect the capability to operate the valves remotely and therefore, the safety significance of this condition is limited to the use of the valves during postulated Appendix R fire scenarios.

Inspection of 3HV 8421 revealed that the aluminum threads of the handwheel shaft were galled and the mating threads of the bronze guide had sharp edges.

Inspection of 3HV 8419 identified that the handwheel shaft was slightly galled and the guide was poorly machined.

These observed conditions would account for the excessive resistance to manual operation.

Both valves have been subsequently repaired.

S 8809150021 800830 A00 ADOCK O g2 pDR lc1 Re6 Y M

Mr. J. B. Martin August 30, 1988 Both ADVs on Unit 2 have been manually operated and no problems were identified.

Therefore, this License Condition 2.G notification is not required for Unit 2.

The cause and any further corrective actions implemented will be the subject of the 14 Day Follow-up Report, which will be submitted by September 12, 1988.

If you require any additional information, please so advise.