- 9 September 28, 1998 Mr. Oliver D. Kingsley, President Nuclear Generation Group Commoawealth Edison Company Executive Towers West lll 1400 Opus Place, Suite 500 '
Downers Grove,IL 60515
SUBJECT:
APPLICATION OF THE APPROVED ENVIRONMENTAL QUALIFICATION OF 1
OKONITE TAPE SPLICES FOR BRAIDWOOD STATION TO THE SAME APPLICATION AT BYRON STATION (TAC NOS. MA3525 AND MA3526)
Dear Mr. Kingsley:
By letters dated January 26,1995, and July 17,1995, Commonwealth Edison Company (Comed) provided an analysis to demonstrate environmental qualification (EO) of Okonite tape splices for
" local submergence" due to a line break accident at Braidwood Station. By letter dated November 13,1995, the NRC staff provided a Safety Evaluation (SE) which concluded that Comed had demonstrated qualification for partial submergence for the Okonite tape eplices at Braidwood. The limited acceptance applied only to power and control Okonite tape splices that are located in junction and pull boxes.
By letter dated July 30,1998, Comed proposed the application of the January 26,1995, and July 17,1995, submittals and the November 13,1995, SE for Byron Station. Comed stated that the application of Okonite tape splices at Byron Station is the same as that at Braidwood Station.
l The staff finds that the application of the previously approved qualification for Braidwood Station to the sama application at Byron Station is acceptable. As before, the only tape splices that are acceptable are those at Byron Station in power and control circuits located in junction and pull boxes Any other use of the Okonite tape splices in submerged EQ applications must be evaluated separately by the staff.
l Should you have any questions, please contact me at (301) 415-3017.
Sincerely, ORIG. SIGNED BY
)O John B. Hickman, Project Manager 9810020249 980929
~
Project Directorate 111-2 j
Division of Reactor Projects - lil/lV PDR ADOCK 05000454 Office of Nuclear Reactor Regulation P
PDR g fg{Tf o\\
Docket Nos. STN 50-454, STN 50-455 cc: See next page
~
Distribution Docket File PUBLIC PDill-2 r,Y EAdensam SRichards CMoore ACRS oGC J. Hickman M. Jordan, Rll!
N. Hilton, Rlli DOC'JMENT NAME: G:\\CM\\ BRAID-BY\\B83525.LTR To receive a copy of this document, Indicate in the box 'c' = Copy without attachment / enclosure "E" = copy witn attachment / enclosure
- N' = No copy m
OFFICE PM:PDill-2
_ l d' l A$ul(2 lE BC: Set:5 #5L G l D.PDill-2 lE NAME JHICKMAN:sp 4/jt5y
(@B amasH.jcA & vo SRICHARDS 4W'
,DATE 9// 6 /98 9/ {d98 9/ 2 '//98 hv1C 9/2X198 OFFICIAL RECORD COPY
l ptM UD
[*,
k UNITED STATES g
j NUCLEAR REGULATORY COMMISSION f
WASHINGTON. D.C. 20666-0001
'***e September 28, 1998 Mr. Oliver D. Kingsley, President Nuclear Generation Gicup Commonwealth Edison Company Executive Towers West lil 1400 Opus Place, Suite 500 Downers Grove,IL 60515 l
SUBJECT:
APPLICATION OF THE APPROVED ENVIRONMENTAL QUALIFICATION OF OKONITE TAPE SPLICES FOR BRAIDWOOD STATION TO THE SAME APPLICATION AT BYRON STATION (TAC NOS. MA3525 AND MA3526)
Dear Mr. Kingsley:
By letters dated January 26,1995, and July 17,1995, Commonwealth Edison Company (Comed) provided an analysis to demonstrate environmental qualification (EQ) of Okonite tape splices for "iocal submergence" due to a line break accident at Braidwood Station. By letter dated Novemtv 13,1995, the NRC staff provided a Safety Evaluation (SE) which concluded that Comed had demonstrated qualification for partial submergence for the Okonite tape splices at Braidwood. Ti '
limited acceptance applied only to power and control Okonite tape spiices that are located in junction and pull boxes.
By letter dated July 30,1998, Comed proposed the application of the January 26,1995, and July 17,1995, submittals and the November 13,1995, SE for Byron Station. Comed stated that the application of Okonite tape splices at Byron Station is the same as that at Braidwood Station.
The staff finds that (ne application of the previously approved qualification for Braidwood Station to the same application at Byron Station is acceptable. As before, the only tape ssices that are l
acceptable are those at Byron Station in power and control circuits located in junction and pull l
boxes. Any other use of the Okonite tape splices in submerged EQ applications must be evaluated separately by the staff.
Should you have any questions, please contact me at (301) 415-3017.
Sincerely, John B. Hickman, Project Manager Project Directorate Ill-2 Division of Reactor Projects - lil/IV Office of Nuclear Reactor Regulation Docket Nos. STN 50-454, STN 50-455 cc: See next page l
F O. Kingsley Byron Station Commonwealth Edison Company Units 1 and 2 cc:
l Michael 1. Miller, Esquire Ms. Lorraine Creek Sidley and Austin RR 1 Box 182 One First National Plaza Manteno, Illinois 60950 Chicago, Illinois 60603 1
Chairman, Ogle County Board Regional Administrator, Region til Post Office Box 357 U.S. Nuclear Regulatory Commission Oregon, Illinois 61061 801 Warrenville Road Lis,e, Illinois 60532-4351 Mrs. Phil!ip B. Johnson 1907 Stratford Lane Illinois Department of Nuclear Safety Rockford, Illinois 61107 Office of Nuclear Facility Safety l
1035 Outer Park Drive Attomey General l'
Springfield, Illinois 62704 500 S. Second Street l
Springfield, Illinois 62701 l-Document Control Desk-Licensing l
Commonwealth Edison Company Commonwealth Edison Company 1400 Opus Place, Suite 400 Byron Station Manager Downers Grove, Illinois 60515 4450 North German Church Road l
Byron, Illinois 61010-9794 l-Ms. C. Sue Hauser, Project Manage, l
Westinghouse Electric Corporation Commonwealth Edison Company Energy Systems Business Unit Site Vice President - Byron Post Office Box 355 4450 N. German Church Road l
Pittsburgh, Pennsylvania 15230 Byron, Illinois 61010-9794 l
Joseph Gallo Mr. David Helwig Gallo & Ross Nuclear Services Senior Vice President 1250 Eye St., N.W., Suite 302 Commonwealth Edison Company Washington, DC 20005 Executive Towers West lll 1400 Opus Place, Suite 900 l
Howard A. Leamer Downers Grove,IL 60515 Environmental Law and Policy Center of the Midwest Mr. Gene H. Stanley 35 East Wacker Drive PWR's Vice President Suite 1300 Commonwealth Edison Company c.
Chicago, Illinois 60601 Executive Towers West lll 1400 Opus Place, Suite 900 U.S. Nuclear Regulatory Commission Downers Grove,IL 60515 Byron Resident Inspectors Office 4448 North German Church Road Byron, Illinois 61010-9750 yev
-,n
- yr r
e
- w r
.,w--
w v
.-w
-y----r-inv-.-
c O. Kingsley Byron Station Commonwealth Edison Company Units 1 and 2 Mr. Steve Perry BWR's Vice President Commonwealth Edison Company Executive Towers West 111 1400 Opus Place, Suite 900 Downers Grove,IL 60515 Mr. Dennis Farrar Regulatory Services Manager Commonwealth Edison Company Executive Towers West lli 1400 Opus Place, Suite 500 Downers Grove,IL 60515 Ms. Irene Johnson, Licensing Director Nuclear Regulatory Services Commonwealth Edison Company Executive Towers West til 1400 Opus Place, Suite 500 Downers Grove,IL 60515 Commonwealth Edison Company Reg. Assurance Supervisor-Byron 4450 N. German Church Road Byron, Illinois 61010-9794 Mr. Michael J. Wallace Genior Vice President Commonwealth Edison Company Executive Towers West til 1400 Opus Place, Suite 900 Downers Grove,IL 60515 l
.