|
---|
Category:REPORTABLE OCCURRENCE REPORT (SEE ALSO AO LER)
MONTHYEARML20216E5401999-09-0707 September 1999 Special Rept:On 990826,discovered That Meteorological Sys Upper Wind Speed Cup Set Broken,Causing Upper Wind Channel to Be Inoperable.Cup Set Replaced & Channel Restored to Operable Status on 990826 ML20210R1051999-08-0606 August 1999 Special Rept:On 990628,cathodic Protection Sys Was Declared Inoperable After Sys Did Not Pass Acceptance Criteria of Bimonthly Surveillance.Work Request 98085802 Was Initiated & Connections on Well Anode Were Cleaned or Replaced ML20206P2081998-12-31031 December 1998 Special Rept:On 981218,inoperability of Meteorological Monitoring Instrumentation Channels,Was Observed.Caused by Data Logger Overloading Circuit.Replaced & Repaired Temp Signal Processor ML20198B1341998-12-14014 December 1998 Revised Special Rept:On 980505,discovered That Certain Fire Barriers Appeared to Be Degraded.Caused by Removal of Firestop Damming Boards.Hourly Fire Watches Established in Affected Areas ML20196D4041998-11-19019 November 1998 Rev 1 to Special Rept:On 980618,determined That Method Used to Calibrate Wind Speed Instrumentation Loops of Meteorological Monitoring Instrumentation Sys Does Not Meet TS Definition for Channel Calibration.Procedure Revised ML20153B0531998-09-16016 September 1998 Special Rept:On 980817,errors in Implementation of Selected Licensee Commitment Testing Requirements on Fire Protection Sys Instruments,Was Discovered.Caused by Error in Interpretation of SLC Requirement.Will Revise Procedures ML20236M9151998-07-0707 July 1998 Special Rept:On 980611,determined That Required Firewatch Patrol Had Been Missed.Caused by Firewatch Being Performed on Wrong Unit Due to Human Error.Employee Was Verbally Counseled on Firewatches & Documentation Was Corrected ML20236G4451998-07-0101 July 1998 Special Rept:On 980618,declared Wind Speed Instrumentation Loops of Meteorological Monitoring Instrumentation Sys Inoperable.Caused by Failure to Meet TS Definition of Channel Calibr.Will Revise Selected Licensee Commitment ML20248K1431998-06-0202 June 1998 Special Rept:On 980505,discovered That Certain Fire Barriers Appeared to Be Degraded.Caused by Shrinkage of Foam & Improper Installation During Construction of Plant.Posted Fire Watches & Repaired Firestop F-AX-348-W-134 ML20247H5351998-04-12012 April 1998 Special Rept:On 980415,missed Insp of Fire Hose Caskets Was Discovered.Caused by Error in Transferring Info from One Procedure to Another.Planned Rev of Applicable Procedure to Include Gasket Insp at Appropriate Frequency ML20216B0211998-04-0606 April 1998 Special Rept:On 980325,determined That Loose Parts Monitoring Sys Being Inoperable for Greater than Thirty Days.Caused by Incorrect Testing.All Channels of Loose Parts Monitoring Sys Tested Utilizing Revised Test Method ML20217K9271998-03-26026 March 1998 Special Rept:On 971229,procedure Step for Closing Safety Injection Pump Cold Leg Injection Isolation Valve Was Inadvertently Skipped.Caused by Injection of Water Into RCS from Rwst.Simplified Procedures & Discussed Event ML20216D5641998-03-0505 March 1998 Special Rept:On 980204,discovered That Fire Detection Panel Was Apparently Not Communicating W/Several Local Fire Detectors.Caused by Faulty Computer Sys Cards.Replaced Four Computer Cards in Sys ML20202C4701998-02-0505 February 1998 Ro:On 971228:Unit 1 Loose Parts Monitoring Sys Channel 6 Was Declared Inoperable Due to Excessive Static on Channel. Caused by Loose Connection.Work Order Has Been Written to Pursue Repairs ML20138E6851997-04-24024 April 1997 Special Rept:On 970318,Unit 1 Loose Parts Monitoring Sys Channel 13 Was Declared Inoperable Due to Sporadic Electical Static.Channel Was Removed from Svc & Entered Into TS Action Item Logbook as Inoperable ML20149M7251997-01-20020 January 1997 Special Rept:On 961209,Unit 1 Loose Parts Monitoring (Lpm) Sys Channel 20 Declared Inoperable Due to No Signal Being Received from Field.Lpm Channel 20 & 22 Operable & Providing Monitoring Coverage for Primary Side of 1D S/G ML20134K4901996-11-0606 November 1996 Special Rept:On 961009,selective Licensee Commitment for Operability of Fire Protection Sprinkler Sys Not Maintained. Continuous Fire Watch Established within One H Following Identification of Incorrect Remedial Action ML20134H1331996-11-0404 November 1996 Special Rept:On 961004,Unit 1B DG Failed Due to Failure of Motor Operated Pot,Electronic & Mechanical Governor,Governor Droop Relay & Mechanical Binding of Fuel Rack Control Linkage.Dg Procedures Will Be Revised ML20113A1801996-06-17017 June 1996 Special Rept:On 960521,declared Detectors A01 for Zone 69 & A04 for Zone 60 Inoperable Because Detectors Effectively Isolated from Area in Intended Protection.Detectors Relocated,Tested & Declared Operable on 960524 ML20100H9801996-02-20020 February 1996 Special Rept:On 960111,Unit 1 Loose Parts Monitoring Channel 21 Declared Inoperable,Due to Spurious,Unexplainable Electronic Bursts.Work Request Initiated to Pursue Corrective Action ML20100H9751996-02-20020 February 1996 Special Rept:On 960111,Unit 2 Loose Parts Monitoring Sys Channel 7 Declared Inoperable,Due to pre-amp Bias Voltage Indicating Zero Volts Twice During Previous Seven Days.Work Request Written to Pursue Corrective Action ML20097F5011996-02-11011 February 1996 Special Rept:On 960102,Unit 2 Loose Parts Monitoring Sys Channel 17 Was Declared Inoperable.Two Other Channels Operable & Providing Coverage Against Loose Parts ML20096E7731996-01-12012 January 1996 Special Rept:On 951214,unit 2 DG Valid Failure Occurred. Caused by Fuel Line Fitting Backing Off from Cylinder Head Connection,Which Resulted in Fuel Oil Leakage.Dg Successfully Started,Run & Declared Operable on 951215 ML20096A8761995-12-18018 December 1995 Special Rept:On 951120,during Periodic Surveillance Testing, Lpms Channel 5 Declared Inoperable.Caused by Erratic Preamp Bias Voltage Indications.Work Request 95048483 Initiated to Perform Corrective Maint During Unit 1 Cycle 9 ML20094Q5811995-11-13013 November 1995 Special Rept:On 951014,auxiliary Bldg Filtered Exhaust Sys Pump Room Heater Declared Inoperable Due to Blown Fuse & Not Restored to Operable Status within 7 Days Per Ts. Technical Investigation Will Be Performed ML20094B8291995-10-25025 October 1995 Special Rept:On 950919,loose Parts Monitoring Sys Channel 1 Declared Inoperable Due to Erratic Preamp Bias Indication. Work Request Written to Investigate & Repair Channel ML20098A4641995-09-19019 September 1995 Special Rept:On 950817,Unit 2 Lpms Channel 12 Was Declared Inoperable Due to Channel Sensor Failing Acceptance Criteria During Performance of PT/O/A4600/03 ML20092G6041995-09-14014 September 1995 Special Rept:On 950815,CNS Unit 1 DG 1A Invalid Failure Occurred Due to Main Bearing High Temp Trip Signal.Caused by Failed Splice Installed in Circuit for RTD 1LDRD5630.New RTD Installed in Main Bearing 5 ML20086H1401995-07-12012 July 1995 Special Rept:On 950615,Channel 4 Was Declared Inoperable Due to Noise Uncharacteristic of Healthy Channel Detected Via Vibration & Loose Parts Monitoring Sys.Corrective Maint Will Be Performed During 1EOC9 Outage ML20086H1431995-07-11011 July 1995 Special Rept:On 950608,Channel 13 Was Declared Inoperable. Trending of Bias Voltage & Background Rms Evaluated to Conclude Channel Was Experiencing Periodic Failures. Corrective Maint Will Be Performed During 1EOC9 Outage ML20086C6441995-06-29029 June 1995 Special Rept:On 950523,Unit 1 Train a Fuel Handling Ventilation Filter Heaters Declared Inoperable.Evaluation Done to Determine Fault ML20085M4061995-06-20020 June 1995 Special Rept:On 950501,lower Rv Tube 4 Was Declared Inoperable ML20084N7271995-05-25025 May 1995 Special Rept:On 950425,valid Failure of DG 1A Occurred. Caused by Jacket Water Thermostatic Control Valve Sticking in Position Which Reduced Engine Cw Flow Through Heat Exchanger.Thermostatic Cv Internals Removed & Replaced ML20082L2711995-04-17017 April 1995 Special Rept:On 950308,Unit 2 Cathodic Protection Sys Was Declared Inoperable & Remained Inoperable Greater than 10 Days ML20081D4851995-03-13013 March 1995 Special Rept:On 950211,actuation of PORV 1NC32B Occurred. Procedure OP/1(2)/A/6100/02 Revised to Require More Emphasis on Monitoring Pressure Indication During Sensitive Evolutions ML20080Q8701995-03-0202 March 1995 Special Rept:On 950202,Unit 1 DG 1B Invalid Failure Due to Overcurrent Breaker Trip During Governor Troubleshooting ML20149H7821994-12-20020 December 1994 Special Rept:On 941129,discovered That Selective Licensee Commitment (SLC) for Visual Insp of Fire Rated Assemblies Exceeded Due to Misinterpretation of Requirements of SLC 16.9-5.Fire Barriers Visually Inspected ML20078R0021994-12-12012 December 1994 Special Rept:On 941103,Channel 3 (Upper Rv a) Declared Inoperable.Caused by Channel Sensor Failure of Acceptance Criteria During Performance of PT/0/A/4600/03.Repair Planned for End of 2EOC7 Outage Due to Containment Entry Required ML20078K7361994-11-17017 November 1994 Special Rept on 941021,DG 1A Invalid Failure Occurred Due to Main Bearing High Temp Trip.Operability Performance Test Successfully Completed & Engine Declared Operable on 941022 ML20149G8041994-11-0101 November 1994 Special Rept:On 940922,CNS,Unit 2 Cathodic Protection Sys Declared Inoperable & Remained Inoperable for Greater than 10 Days.Wo 94080948-01 Initiated to Replace Prepackaged Anode Well 1.WO Scheduled for 941114 ML20076F3191994-10-0404 October 1994 Special Rept:On 940908,valid Failure of D/G 1A Occurred Due to Air Start Valve Sticking Open.Maint Procedure MP/0/A/7650/99 Revised,New Air Roll Criteria Developed & Sixteen Starting Air Valves Replaced ML20072P4251994-08-23023 August 1994 Ro:On 940719,channel 9 (S/G a Channel 2) Declared Inoperable.Work Request Was Generated to Repair Channel During Future Outage of Sufficient Length Since Containment Entry Required for Work ML20072E5961994-08-15015 August 1994 Special Rept:On 940715,inoperability of Unit 2 Vibration & Loose Parts Monitoring System Channel 4 & 6 Occurred.Caused by Leds Not Lighting During Performance of PT/0/B/4600/03. Work Orders 94051250-01 & 94051251-01 Initiated ML20071N7441994-07-28028 July 1994 Special Rept:On 940711,delta-t Channel on Chart Recorder Found to Be out-of-tolerance Due to Drifting of Analog to Digital (A/D) Converter Card.A/D Card Replaced & delta-t Channel Chart Recorder Declared Operable ML20071N8511994-07-28028 July 1994 Special Rept:On 940711,main Steam Relief Valve Exhaust Monitors Declared Inoperable Due to Engineering Calculation Concerns.Engineering Calculation CNC-1229.00-00-0047 re-performed Using EPA-400 Methodology ML20070K0191994-07-18018 July 1994 Special Rept:On 940630,re Inoperability of Main Steam Line Radiation Monitor 2EMF12.Work Request 94026262 Generated to Reattach 2EMF12 to Main Steamline.Work Request Completed on 940701 ML20069H0861994-05-31031 May 1994 Special Rept:On 940501,Unit 2 DG 2A Invalid Failure Occurred Due to Right Bank Turbocharger Vibration Trip.Based on Cooper-Enterprise Recommendations,Procedure Changes Made to Calibr Procedures for All Four DGs ML20065K5011994-04-13013 April 1994 Special Rept:On 940314,invalid Failure of Diesel Generator 1B Occurred Due to Output Tripping During Calibration of Electronic Governor.Dg 1B Started Successfully on 940315 & Declared Operable ML20064G2911994-03-15015 March 1994 Special Rept:On 940203,SG Channels 9 & 11 Declared Inoperable.Channels Failed to Meet Band Limited Rms Acceptance Criteria During Performance of 18 Month Channel Calibr Test.Work Request Written to Repair Channels ML20064G2771994-03-0707 March 1994 Special Rept:On 940125,Channels 6,7 & 10 Were Declared Inoperable.Channels Failed to Meet Acceptance Criteria During Performance of 18 Month Channel Calibr Test.Work Request Written to Repair Channels 1999-09-07
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217H0201999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Catawba Nuclear Station,Units 1 & 2 ML20216E5401999-09-0707 September 1999 Special Rept:On 990826,discovered That Meteorological Sys Upper Wind Speed Cup Set Broken,Causing Upper Wind Channel to Be Inoperable.Cup Set Replaced & Channel Restored to Operable Status on 990826 ML20212B4711999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Catawba Nuclear Station,Units 1 & 2 ML20217H0321999-08-31031 August 1999 Revised Monthly Operating Rept for Aug 1999 for Catawba Nuclear Station,Units 1 & 2 ML20211B1281999-08-31031 August 1999 Dynamic Rod Worth Measurement Using Casmo/Simulate ML20211A9791999-08-20020 August 1999 Safety Evaluation Granting Licensee Request for Approval of Proposed Relief from Volumetric Exam Requirements of ASME B&PV Code,Section Xi,For Plant,Unit 2 ML20211F3441999-08-17017 August 1999 Updated non-proprietary Page 2-4 of TR DPC-NE-2009 ML20211C1291999-08-17017 August 1999 ISI Rept Unit 1 Catawba 1999 RFO 11 ML20210R1051999-08-0606 August 1999 Special Rept:On 990628,cathodic Protection Sys Was Declared Inoperable After Sys Did Not Pass Acceptance Criteria of Bimonthly Surveillance.Work Request 98085802 Was Initiated & Connections on Well Anode Were Cleaned or Replaced ML20210S2891999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Catawba Nuclear Station,Units 1 & 2 ML20212B4871999-07-31031 July 1999 Revised Monthly Operating Rept for July 1999 for Catawba Nuclear Station,Units 1 & 2 ML20209E4361999-07-0909 July 1999 SER Agreeing with Licensee General Interpretation of TS LCO 3.0.6,but Finds No Technical Basis or Guidance That Snubbers Could Be Treated as Exception to General Interpretation ML20196K6631999-07-0707 July 1999 Safety Evaluation Supporting Licensee 990520 Position Re Inoperable Snubbers ML20210S2951999-06-30030 June 1999 Revised Monthly Operating Rept for June 1999 for Catawba Nuclear Station,Units 1 & 2 ML20209H4501999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Catawba Nuclear Station,Units 1 & 2 ML20209H4561999-05-31031 May 1999 Revised Monthly Operating Rept for May 1999 for Catawba Nuclear Station,Units 1 & 2 ML20206T4771999-05-31031 May 1999 Rev 3 to UFSAR Chapter 15 Sys Transient Analysis Methodology ML20196L1881999-05-31031 May 1999 Non-proprietary Rev 1 to DPC-NE-3004, Mass & Energy Release & Containment Response Methodology ML20196A0001999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Catawba Nuclear Station,Units 1 & 2 ML20206P5201999-05-14014 May 1999 Safety Evaluation Accepting GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves ML20206N8391999-05-0404 May 1999 Rev 16 to CNEI-0400-24, Catawba Unit 1 Cycle 12 Colr ML20206R1811999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Catawba Nuclear Station,Units 1 & 2 ML20196A0041999-04-30030 April 1999 Revised Monthly Operating Repts for Apr 1999 for Catawba Nuclear Station,Units 1 & 2 ML20206N8261999-04-22022 April 1999 Rev 15 to CNEI-0400-24, Catawba Unit 1 Cycle 12 Colr. Page 145 of 270 of Incoming Submittal Not Included ML20205S5551999-04-21021 April 1999 Safety Evaluation Accepting Response to GL 96-06, Assurance of Equipment Operability & Containment Integrity During Design Basis Accident Conditions ML20205N3651999-04-12012 April 1999 Safety Evaluation Accepting IPE of External Events Submittal ML18016A9011999-04-12012 April 1999 Part 21 Rept Re Defect in Component of DSRV-16-4,Enterprise DG Sys.Caused by Potential Problem with Connecting Rod Assemblies Built Since 1986,that Have Been Converted to Use Prestressed Fasteners.Affected Rods Should Be Inspected ML20206R1931999-03-31031 March 1999 Revised Monthly Operating Repts for Apr 1999 for Catawba Nuclear Station,Units 1 & 2 ML20205P9521999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Catawba Nuclear Station,Units 1 & 2 ML20205P9561999-02-28028 February 1999 Revised Monthly Operating Repts for Feb 1999 for Catawba Nuclear Station,Units 1 & 2 ML20204C9111999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Catawba Nuclear Station,Units 1 & 2 ML20203A2581999-02-0505 February 1999 Safety Evaluation of TR DPC-NE-3002-A,Rev 2, UFSAR Chapter 15 Sys Transient Analysis Methodology. Rept Acceptable. Staff Requests Duke Energy Corp to Publish Accepted Version of TR within 3 Months of Receipt of SE ML20204C9161999-01-31031 January 1999 Revised Monthly Operating Repts for Jan 1999 for Catawba Nuclear Station,Units 1 & 2 ML20199K8711999-01-13013 January 1999 Inservice Insp Rept for Unit 2 Catawba 1998 Refueling Outage 9 ML20199E3071998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Catawba Nuclear Station,Units 1 & 2 ML20216F9931998-12-31031 December 1998 Piedmont Municipal Power Agency 1998 Annual Rept ML20205E9441998-12-31031 December 1998 1998 10CFR50.59 Rept for Catawba Nuclear Station,Units 1 & 2, Containing Brief Description of Changes,Tests & Experiments,Including Summary of Ses.With ML20206P2081998-12-31031 December 1998 Special Rept:On 981218,inoperability of Meteorological Monitoring Instrumentation Channels,Was Observed.Caused by Data Logger Overloading Circuit.Replaced & Repaired Temp Signal Processor ML20203A4101998-12-22022 December 1998 Rev 16 to CNEI-0400-25, Catawba Unit 2 Cycle 10 Colr ML20203A4041998-12-22022 December 1998 Rev 14 to CNEI-0400-24, Catawba Unit 1 Cycle 11 Colr ML20198B1341998-12-14014 December 1998 Revised Special Rept:On 980505,discovered That Certain Fire Barriers Appeared to Be Degraded.Caused by Removal of Firestop Damming Boards.Hourly Fire Watches Established in Affected Areas ML20196J8351998-12-0808 December 1998 Safety Evaluation Granting Relief Request Re Relief Valves in Diesel Generator Fuel Oil Sys ML20199E3221998-11-30030 November 1998 Revised MOR for Nov 1998 for Catawba Nuclear Station,Units 1 & 2 Re Personnel Exposure ML20198E3151998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Catawba Nuclear Station,Units 1 & 2 ML20196C0251998-11-27027 November 1998 SER Accepting Clarification on Calibration Tolerances on Trip Setpoints for Catawba Nuclear Station ML20196A6881998-11-25025 November 1998 Safety Evaluation Granting Relief Request 98-02 Re Limited Exam for Three Welds ML20196D4041998-11-19019 November 1998 Rev 1 to Special Rept:On 980618,determined That Method Used to Calibrate Wind Speed Instrumentation Loops of Meteorological Monitoring Instrumentation Sys Does Not Meet TS Definition for Channel Calibration.Procedure Revised ML20195E5521998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Catawba Nuclear Station,Units 1 & 2 ML20198E3261998-10-31031 October 1998 Revised Monthly Operating Repts for Oct 1998 for Catawba Nuclear Station,Units 1 & 2 ML20154M7661998-10-12012 October 1998 LER 98-S01-00:on 980913,terminated Vendor Employee Entered Protected Area.Caused by Computer Interface Malfunction. Security Retained Vendor Employee Badge to Prevent Further Access & Computer Malfunction Was Repaired.With 1999-09-07
[Table view] |
Text
.
,b :
[S Duk) Energy Corporati:n
/ e- i IU b @= Catawba Nuclear Station 4800 Concord Road York, SC 29745 Gary R. Peterson , (803) 831-4251 omCE MceIWsiderst (803) 831-3426 FAX l
l September 16, 1998 U.S. Nuclear Regulatory Commission
' ATTN: Document Control Desk Washington, DC 20555-0001
Subject:
Duke Energy Corporation Catawba Nuclear Station Units 1 and 2 Docket Nos. 50-413 and 50-414 Special Report: Fire Protection Program Errors'in Implementation of Selected Licensee Commitment Testing Requirements Pursuant to Facility Operating License Section 2F, License Conditions 2.C.(8) for Unit 1 and 2.C. (6) for Unit 2, and
-Selected Licensee Commitment 16.9.6, Fire Detection Instrumentation, attached is a Special Report concerning Errors in Implementation of Selected Licensee Commitment Testing Requirements on Fire Protection System Instruments.
This condition was discovered on August 17, 1998. ;
Commitments associated with this Special Report are provided in the Corrective Action Section.
Questions regarding this Special Report should be addressed to M.H. Chernoff at (803) 831-3414.
Very tr ' yours, f a
G. R. eterson ga
's \
J
,, /
Attachment 3z 9909220297 900916 9 '
PDR ADOCK 050004137 I S PDRjj
_ ,c U.S. Nuclear Regulatory Commission September 16, 1998 Page 2 xc: L. A. Reyes U. S. Nuclear Regulatory Commission Regional Administrator, Region II Atlanta Federal Center 61 Forsyth St., SW, Suite 23T85 Atlanta, GA'30303 P. S.. Tam NRC Senior Project Manager'(CNS)
U. S. Nuclear Regulatory Commission Mail Stop O-14H25 Washington, DC 20555-0001 D.J. Roberts Senior Resident Inspector (CNS)
U. S. Nuclear Regulatory Commission Catawba Nuclear Site
{
_ m .- _ _ . _ _ . _ . . _ - - - .. . . . - _ _. __ _
i U.S.-Nuclear Regulatory Commission
- i September 16,-1998 Page 3 i
e
, I I
Attachment l L Special Report l
l l
Abstract:
u On August 17, 1998 with Unit 1 in Mode 5,. Cold Shutdown, and j Unit 2 operating in Mode 1 (Power Operation) at 100% power, l it was determined that the 6 month visual inspection of the !
spot type heat. detectors for the Auxiliary Feedwater Pump and Diesel Generator rooms was not being performed once per 1 six' months as required by the Fire Protection Program in l l Selected Licensee: Commitment (SLC) 16.9.6. This occurred
- l. because the detectors were grouped with the associated Carbon Dioxide system and were not included in the
. procedures which govern visual inspection of Fire Detection Instruments. The inspections were subsequently performed satisfactorily.
On August 18, 1998, it was discovered that the SLC-16.9.6 requirement to test 2 percent of the non-restorable spot type heat detectors every five years was not being !
performed. In 1992, this type of detector, with the exception of 12 Control Room detectors, was excluded from L
the SLC. During implementation of this change the tests on these 12 detectors were erroneously deleted. These 12 detectors were replaced.
On August 21, 1998, during a thorough review of SLC required fire detector testing, it was discovered that not all
-inaccessible restorable spot type heat detectors were being tested each Refueling Outage. This was due to an error in interpretation of the SLC requirement. For Unit 1, the i required tests were pert __med and failed detectors were replaced. The tests will be done on the Unit 2 detectors '
during the current outage.
The appropriate testing procedures will be revised to be consistent with the SLC Testing Requirements.
~
l U.S. Nuclear Regulatory Commission September 16, 1998 Page 4 l Introduction i
Catawba Nuclear Station Units 1 and 2 are four loop Westinghouse Units. Catawba Nuclear Station Unit 1 and Unit
{
2 Facility Operating Licenses NPF-35 and NPF-52 require that i Duke Energy Corporation implement and maintain in effect all I provisions of the approved Fire Protection Program, as amended. It was determined that the events described in this-report constitute noncompliance with this license condition.
Consequently, these events were reported within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of I discovery. pursuant to the provisions of Facility Operating l License Section 2F. This written follow-up is being provided within 30 days of the first event.
At the time of these events, Unit 1 was in Mode 5, Cold Shutdown, and; Unit 2 was in Mode 1, Power Operation, at approximately 100 percent rated thermal power.
Background
Selected Licensee Commitment (SLC) 16.9.6, Fire Detection Instrumentation, is a part of the Catawba Fire Protection
[EIIS:KP] Program and is subject to the provisions of the Catawba Facility Operating License Condition 2.C. (8) for NPF-35 (Unit 1) and License Condition 2.C.(6)for NPF-52 (Unit 2). SLC 16.9.6 specifies that the detection instrumentation for each fire detection zone listed in Table 16.9-3 be i operable whenever the equipment protected by the fire l detection instrument is required to be operable. The SLC also provides Testing Requirements to verify operability of the instruments and Remedial Actions to be taken if an instrument is inoperable. The events described in this report involve errors in implementing three of the Testing Requirements applicable to heat detectors delineated in the SLC.
One Testing Requirement associated with the SLC requires that all spot-type heat detectors which are accessible during plant operation be visually inspected at least once per 6 months.
l l Another Testing Requirement requires, in part that for non-restorable spot-type detectors, at least two detectors out of every 100, or fraction thereof, be removed every 5 years and functionally tested. For each failure that occurs on l
l
,. U.S. Nuclear Regulatory Commission l September 16, 1998
.Page 5
(~
the detectors removed, two additional detectors shall be removed and tested, i l
- l. The non-restorable spot-type heat detectors at Catawba are
- . " rate of rise / fixed temperature" detectors. These two l' features are independent of each other. The rate of rise
}. feature is restorable and there are different Testing l Requirements for this feature. The " fixed temperature" feature is the non-restorable function of the detector and is subject to this Testing Requirement. This Testing Requirement applies to 12 detectors in the Control Room.
For these 12 detectors, both the rate of rise and fixed L ' temperature features are credited.
j For restorable spot-type detectors that are inaccessible during plant operation, the SLC Testing Requirement requires l performance of a Trip Actuation Device Operational Test l during each refueling outage. This Testing Requiremont applies to 4 rate.of rise heat detectors in each containment (8 total).
SLC 16.2.7 allows a 2 .our period to perform a missed SLC Testing Requirement pr cr to initiating Remedial Actions.
The Remedial Action for more than one-half of the Function A (early warning fire detection and notification only)
~ detection instruments in any fire zone shown in the SLC table, or with any Function B (actuation of fire suppression system and early warning and notification) detection instruments shown in the Table inoperable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish a fire watch patrol to inspect the' zone (s) with the inoperable instrument (s) at least once per hour, unless
'the instrument (s) is located inside the containment, then inspect that containment zone at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or monitor the containment air temperature at least once per hour at specific locations.
Description of Event
\.
August 17, 1998 Approximately 1600 It was discovered that the visual l inspection on the Function B spot heat detectors for l the Auxiliary Feedwater Pump and the Emergency Diesel Generator rooms for Units 1 and 2, required to be performed once per 6 months, was not included in the Catawba Surveillance Program. Function B is defined as
I l l L !
U.S. . Nuclear Regulatory Commission l September 16, 1998 Page G actuation of fire' suppression system and early warning and notification.
r-The affected detectors were declared inoperable. Wcrk Requests were written to conduct a visual inspection of these detectors during the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> permitted to conduct'the testing prior to imposition of the Remedial Action.
August.18, 1998 Approximately 0450 The visual inspection was completed L with no problems noted. )
0945 Review of the inspection results was completed, and the detectors were restored to operable status.
Approximately 1555 During a procedure review, it was discovered that the pre-defined Work Request for the ,
procedure used to satisfy the requirement to test 2 out l of every 100 non-restorable spot detectors every five
'l years had been deleted. 1 Approximately 1835 .The 12 affected Control Room detectors were declared inoperable, and the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> permitted to conduct the testing prior to imposition of the Remedial Action was invoked.
August 19, 1998 Approximately 0405 The 12 Control Room detectors were I replaced.
0953 The detectors were restored to operable status.
A thorough review was initiated of fire detection instrumentation testing requirements as delineated in the SLCs.
August 21, 1998 Approximately 1215 The review of SLC Fire Detection
, Instrumentation Testing identified that the SLC Testing Requirement for inaccessible restorable spot type heat detectors was not being properly implemented. The L procedure required only one detector per zone be tested i each refueling outage, rather than requiring testing of
! all the inaccessible restorable spot type detectors.
r t
r + -v,
U.S. Nuclear Regulatory Commission September 16, 1998 Page 7 The affected detectors are associated with the Filter Bed Units in the Reactor Buila ogs.
A Work Request was initiated to test the heat detectors for Unit 1 prior to plant start-up. A Work Request has been e'stablished to test the rate-of-rise detectors on
' Unit 2 during its End of Cycle 9 Refueling Outage, which began on September 5, 1998. Remedial Actions as specified in SLC 16.9.6 are being implemented for Unit 2,
pending restoration of the detectors to operable status.
y Several of the detectors on Unit 1 failed the test and were replaced. The detectors were restored to operable status following successful completion of the testing.
Cause Of Event The visual inspections on the heat detectors for the Auxiliary Feedwater Pump and Diesel Generator rooms were not included in the Surveillance Program because these detectors are associated with the suppression systems in these rooms, rather than the detection systems. Visual inspection of these detectors was inadvertently omitted from the series of procedures that govern fire detection instrumentation visual inspections.
Deletion of the Model Work Order for testing of the Control Room heat detectors was the primary cause of the failure to perform the 5 year test on the non-restorable spot type heat detectors. This has been attributed to an oversight that occurred in 1992. In 1992, based on the results of a design study, all but 12 fixed temperature heat detectocs were deleted from the scope of the SLC's. The subsequent deletion of the Model Work Order removed the work control vehicle for tasting of the fixed temperature heat detectors.
Additionally, the testing procedure did not contain an all inclusive list of the fixed temperature heat detectors.
The error in testing the restorable spot type heat detectors located in inaccessible areas has been attributed to a lack of clarity in the SLC requirements. The lack of clarity resulted in a misinterpretation of the SLC requirements.
Corrective Actions The semi-annual Auxiliary Feedwater and Emergency Diesel Generator Carbon Dicxide system performance tests will be revised to add a visual inspection for the heat detectors.
l t
.- -- . - . - . .~ ~ - .. -- - . - . . - - ~ . - - .
U.S. Nuclear Regulatory Commission September- 16,'1998 ;
Page 8 Procedures"affected are PT/1(2)/A/4450/13D (Aux FDWP CO2 System Semi-Annual Test) and PT/1(2)/A/4450/10D (Diesel Generator CO2 System Semi-Annual Test). '
Selected Licensee Commitment 16.9.6 will'be revised to remove the Control Room heat detectors. Each of these detectors.is paired with an ionization detector located directly adjacent to them. Based on the combustible loading in the Control Room and the effectiveness of the ionization detectors themselves, deletion of the heat detectors from the scope of the SLC's is appropriate.
Procedures IP/0/A/3350/031 (032) (EFA System Detector Test Procedure for Data Gathering Panel 28 (29)) will be revised
'to ensure all restorable spot type heat detectors located in inaccessible areas are tested during each refueling outage.
Additionally, an evaluation will be performed to determine ,
if the inaccessible heat detectors can be removed from the scope of the SLC's.
Additional Information The failure to perform the required visual inspection of the.
heat. detectors in the Auxiliary Feedwater Pump rooms did not degrade the performance of the fire protection system. The visual inspection is conducted to ensure there are no obvious signs of' damage to the detector and that there are no obstructions that.would impair functioning of the detector. The location of these detectors and the controls associated with the modification program <would greatly reduce the likelihood of damage or obstructions. The visual inspections were conducted with no problems noted.
The failure to test 2 percent of the heat c.etectors with a non-restorable feature in the Control Roor. likewise did not degrade performance of the fire protection system. There is a smoke detector adjacent to each heat detector in the Control Room. The smoke detectors are appropriate for the l type of combustibles in the Control Room and would provide a l quicker response than heat detectors. Furthermore, the Control Room is continuously manned, thereby ensuring early l detection and response to a developing fire.
l There are additional' fire protection system features that can be relied'upon'to compensate for the inoperability of the inaccessible heat. detectors. There are smoke detectors i adjacent to each of these heat detectors. These detectors
, are associated with Lower Containment Ventilation System 3- Filter' Bed Units in the Reactor Building. The Filter Bed 4
- p. .
l U.S. Nuclear Regulatory Commission September 16, 1998 l
Page 9 l Units are serviced by a fan unit that is part of the Reactor Building Ventilation System. The fan unit contains a '
thermal detector that-alarms in the Control Room and is in service any time the. filter-bed fan is in service. The smoke detectors.and the Ventilation System temperature sensors would have provided adequate early warning detection i capability.
l The health and safety of the public and site personnel were i
.not jeopardized by the events described in this report.
A search of the corrective action database for the previous two years for events involving Fire Detection System Testing Requirements did not identify any previous similar occurrences. One event involving a failure to inspect Fire l Hose Gaskets was discovered on April 15, 1998. This )
occurrence was reported in a Special Report, submitted on
, May 12, 1998. That event was attributed to a failure to transfer inspection requirements from one procedure to o another and was considered to be historical in nature.
There are no EPIX reportable failures associated with the occurrences described in this report ~.
1 I
l l
l l
I l
1 l
t
_