ML20151X020

From kanterella
Jump to navigation Jump to search
Submits Suppl to Request for Change to Tech Specs Re Ultimate Heat Sink Temp Limits.Util Determined,Info Contained in Attachment to Ltr Does Not Alter Conclusions Reached in 10CFR50.92
ML20151X020
Person / Time
Site: Hope Creek 
Issue date: 09/08/1998
From: Eric Simpson
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LCR-H98-02, LCR-H98-2, LR-N98406, NUDOCS 9809160226
Download: ML20151X020 (71)


Text

_

Pibc Sense Electre and Gas Cornpany E. C. simpson r i : Service Electnc and Gas Company P O. Box 236. Hancocks Bndge. NJ 08038 60 S 339-1700 Serwar V:ce Pre % cent. Nuc'ew Engeconna SEP 081998 LR-N98406 LCR H98-02 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 l

Gentlemen:

SUPPLEMENT TO A REQUEST FOR CHANGE TO TECHNICAL SPECIFICATIONS ULTIMATE HEAT SINK TEMPERATURE LIMITS HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NPF-57 DOCKET NO. 50-354 I

On June 12,1998, via letter LR-N98274, Public Service Electric & Gas (PSE&G)

Company transmitted License Change Request (LCR) H98-02 to the NRC to request a revision to the Technical Specifications (TS) for the Hope Creek Generating Station.

Specifically, LCR H98-02 requested, in part, a revision to the Hope Creek Ultimate Heat l

Sink (UHS) temperature limits contained in the TS. ~ On July 29,1998, PSE&G met with NRC representatives to review the Hope Creek LCR submittal. As a result of the NRC's continuing review of LCR H98-02, additional questions were raised. These questions, as well as PSE&G's responses, are contained in Attachment 1 of this letter.

PSE&G has determined that the information contained in the attachment to this letter does not alter the conclusions reached in the 10CFR50.92 No Significant Hazards analysis previously submitted with LCR H98-02. In accordance with 10CFR50.91(b)(1),

a copy of this submittal has been sent to the State of New Jersey.

Should you have any questions regarding this request, please contact James Priest at 609-339-5434.

l Sincerel,

l l

Affidavit Attachments (4) f;O ho j 9809160226 990908 PDR ADOCK 05000354 P

PDR h I[y*cNeaper

o

o SEP 081998 Document Control Desk LR-N98406 l

i C

Mr. H. Miller, Administrator - Region i l'

U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Mr. R. Ennis Licensing Project Manager - Hope Creek U. S. Nuclear Regulatory Commission One White Flint North l

Mail Stop 14E21 11555 Rockville Pike Rockville, MD 20852 Mr. S. Pindale (X24)

USNFO Senior Resident inspector - HC Mr. K. Tosch, Manager IV Bureau of Nuclear Engineering P. O. Box 415 Trenton, NJ 08625 i

i i

I 95-4933 l

_ =. -. -..... - -.

s SEP 0 81998 l

Document Control Desk,

LR-N98406 i

l JPP.

i-BC Senior Vice President - Nuclear Operations (X04)

Senior Vice President - Nuclear Engineering (N19)

General Manager - Hope Creek Operations (HO7)

Director - QA/NT/EP (X01)

Director-Licensing / Regulation and Fuels (N21)

L Director-Design Engineering l-Manager - Financial Control & Co-Owner Affairs (N07)

Program Manager - Nuclear Review Board (N38)

Manager - Hope Creek Operations (H01)

Manager - System Engineering - Hope Creek (H18)

Manager - Hope Creek Licensing (N21)'

Manager - Mechanical Design Engineering (N24)

R. De Night (N29)

J. Keenan, Esq. (N21)

NBU RM (N64)

Microfilm Copy l

Files Nos.1.2.1 (Hope Creek),2.3 (LCR H98-02) f l

i 3-

.e

C REF: LR-N98406 LCR H98-02 STATE OF NEW JERSEY )

) SS.

COUNTY OF SALEM

)

E. C. Simpson, being duly sworn according to law deposes and says:

I am Senior Vice President - Nuclear Engineering of Public Service Electric and Gas Company, and as such, I find the matters set forth in the above referenced letter, concerning Hope Creek Generating Station, Unit 1, are true to the best of my knowledge, information and belief.

/C y-Subscrib d and Sw to before me this_h day ln bm1bCL1998

" r'

&u,m

, w ptary Pubiic dr Wew JeMy My C-ission expires

& JM3

/

l l

l l

l ATTACHMENT 1 HOPE CREEK GENERATING STATION I

FACILITY OPERATING LICENSE NPF-57 DOCKET NO. 50-354 RESPONSE TO NRC QUESTIONS l

l 1.

The staff's understanding of Attachment (4) to [the LCR H98-02] submittal

', is that it is part of the analyses is from Amendment 106 (when SACS = 95 F). Please provide this spreadsheet for the various limiting configurations during normal operation.

A detailed spreadsheet was not compiled for the " normal" alignment. Under the

" normal" alignment, the plant is assumed to be operating at 100% power and one loop of the Safety Auxiliaries Cooling System (SACS) is aligned to the Turbine Auxiliaries Cooling System (TACS). One SACS toop with two SACS pumps operating carries the TACS loads and the second loop is running in standby with one SACS pump in operation. Since the majority of the normal operation heat load is carried by one SACS loop, with two operating pumps, a detailed single failure analysis was deemed unnecessary since SACS would not support the normal operation TACS heat loads with less than two pumps operating in one loop. Therefore, an analysis of one SSWS/ SACS loop operation was the only one necessary to determine the normal operation UHS temperature limit.

In the above configuration, abnormal system alignments (i.e., heat loads from the redundant SACS loop are cross connected to the operating SACS loop) can be accommodated as long as SACS operating temperatures remain below 95 F. If for any reason the operators can not maintain SACS temperature less than or equal to 95 F, the operators are procedurally directed to reduce the TACS heat loads on the operating SACS loop. This limitation on plant operation is imposed regardless of UHS temperature (as long as Technical Specification UHS temperature limits are not exceeded), and the plant would be required to shutdown if SACS temperature can not be maintained below 95 F (i.e., SACS would be considered inoperable). If SACS temperature can be maintained below 95 F during normal operations, then for any degraded SSWS/ SACS configurations continued plant operation (i.e., not operating in a Technical Specification shutdown Action Statement) will be governed by the Technical Specification LCOs, which would ensure adequate post-accident heat removal capability with the proposed UHS temperature limits.

l Page 1 of 3 l

\\

2.

[LCR H98-02] submittal Attachment 4, page 22 of 24, shows that the UHS temperature limit for " Normal Operations" is 89*F. Clarify what is meant by

" Normal Operations" (i.e., is it the most limiting condition allow by TSs in l

an LCO?).

" Normal Operations" assumes that the plant is oaerating at 100% power and one l

loop of SACS is aligned to cool the TACS loads This SACS loop, with two SACS l

pumps operating, carries the TACS loads while the second SACS loop is running in standby with one SACS pump in operation. As stated in the response to the previous question, normal plant operation is restricted by the ability of SACS support systems to maintain SACS temperature below 95'F, regardless of UHS temperature (below the Technical Specification UHS temperature limits). To maintain SACS temperature below 95 F, two SACS pumps must be running in the SACS loop supporting the TACS loads (i.e., normal operations). An i

evaluation of the maximum UHS temperature in this configuration resulted in the 89 F UHS temperature limit.

3.

[LCR H98-02] submittal Attachment 4, page 22 of 24, shows that the UHS temp.?rature limit for a LOP /SSE with "No Failures" is 91.1 F. Confirm that this case did or did not assume a single active failure.

J The UHS model run for "no failures" for a Loss-of-Offsite Power (LOP)/ Safe Shutdown Earthquake (SSE) listed in Attachment (3) of Engineering Evaluation H-0-EG-MEE-1301 assumed no active failures in the SSWS or SACS systems.

The SSWS flow rate is assumed to be through the safety-related emergency overboard line discharge path. The results of this analysis show that the UHS temperature limit would be 91.1 F. The analysis conservatively assumed that the RHR heat load is based on only one RHR heat exchanger being available since no additional operations or configuration limitations are imposed on RHR beyond those already contained in the Technical Specifications (e.g., LCO 3.6.2.3).

4.

[LCR H98-02] submittal Attachment 4, page 22 of 24, does not show a case for 1 SSWS pumpfloop (LOP /SSE). This was a limiting case. What is the new UHS temperature limit for this case?

As indicated in Attachment 2 of this letier, the UHS analysis under a LOP /SSE scenario with on SSWS pump in each loop of the SSWS system results in an UHS limit of 88.2 F (see Attachment 2). This case assumes that the SSWS flow rate to the RACS heat exchangers is unthrottled and discharges through the emergency overboard line. The UHS analysis under a LOCA/ LOP scenario with l

similar SSWS conditions has an UHS temperature limit of 89.7 F (see ).

Page 2 of 3 i

5.

Provida cdditinnil infermition concsrning the comput:r ccdsa u:cd fer the Hope Creek containment analysis and provide a summary of the results obtained when analyzing post-transient responses with a maximum SACS temperature of 100 F.

As indicated in General Electric's September 17,1996, letter EGT96:054 (see ), the General Electric proprietary code SHEX-03 was used for the FSAR analysis, with the results provided in UFSAR Section 6.2. In support of the UHS analyses supporting Hope Creek LCR H98-02, General Electric utilized the current version of the SHEX code to determine the required K values (Residual Heat Removal (RHR) heat exchanger heat transfer capacity coefficient) to keep the peak suppression pool temperature below the design limit of 212 F with the SACS temperature increased from 95 F to 100 F. The analyses used the May-Witt decay heat model to determine the required K value under the worst case limiting conditions (for the Hope Creek analysis, a loss of offsite power coincident with a single failure of an emergency diesel generator was determined to be the limiting event). The results of these analyses provided RHR heat exchanger K values that maintained suppression pool temperatures below 212*F, which were then used to determine the temperature limits described in LCR H98-02.

6.

Provide additional information on what operators do to assess operability of SACS loops (reference TS 3.7.1.1) as described in the LCR submittal section below:

... the current SSWS abnormal procedure directs the operator to assess the operability of the associated SACS loop (i.e., be ensuring that a pump is operable and flow is established) and enter the appropriate SACS limiting condition"...

Operability of the SACS loop requires more than just verifying that the SACS pump is operable and that flow is established. The operability assessment process would also require an assessment of the SACS support system's (i.e.,

SSWS) capability to support the SACS safety functions under design basis conditions (i.e., remove post-accident heat loads under worst case conditions where plant operation is permitted). In other words, if the SSWS loop is declared inoperable, the operator would have to evaluate if SSWS has lost its ability to support the SACS safety functions. Ifit has, then SACS is also declared inoperable and the appropriate SACS TS LCO would be entered. If the operator can conclude that SACS will be able to perform its safety functions with the conditions rendering SSWS inoperable present, then the operator would remain only in the SSWS TS LCO.

Page 3 of 3

e m., i l

l g

PROTO-POwen CORPORATION t

15 THAMES STREET PHONE: (860) 446-9725 GROTON, CT 06340 FAX: (860) 448-4860-FAX COVER SHEET l

FILE No.: U -88#

DATE' W/W/9O TOTAL PAGES (INCLUDING COVER SHEET): 38 To:

AL A W4v FROM:

kk M6 Dim DEPT.

(4a9 fax No.:

) 88v **-

fax No.: -(860) 448-4860 REFE,RENCE:

MESSAGE' A,4 -

We 's A Nh. F I.

.,hv Gr- %v. s.ee w:#. 1 -

Jl ss tas.- - -

m%t :&

J w sF9

't% em v: M o o vs o w stars- :s 6 s. t. *? ^

t,.shdty w I.3 *f

.om w T a ty.

Ab l

To report transmittal problems or for confirmation, please call (860) 446-9725.

l e

e n w.

m all1/9810:19 PROTO-FLO 4.01 by Proto Pewer Corporatisn - Serict #PFL-0000 case t or 4 Public Servica Electric and Oss - OnPSEGil1 385\\New UHS \\STACSt.HS2.PDB - Revision 2.00 Hope Creek Generating Station. STACS Flow Summary Report Convergence Prewe=1.0E.5 Sum Q=1.0E-2 Fdettv=1,05 6 FCV-l OE 4 PCV-1.0E-3 Tempmtwe=$.CE.3 Po-t L.OP. I and 1 SSWS Flow Summary Title Diameter Flow Mm: mum Flow NPSHA NPSH 3

(in)

(2 pct)

(gpm)

(ft)

Ratio I A2E201 out 19.250 9,844.08 l

1 AIE201 out 19.250 9,376.64 1CP210 out 19.250 9,663.47 1AT203 out 1.500 42.07 1 AP210 out 19.250 9,633.96 IAE205 out 19.250 9,718.92 1DP210 out 19.250 9,330.40 1BP210 out 19.250 9.553.08 IBIE201 out 19.250 9,257.55 1BE205 out 19.2!0 9.445.06 1B2E201 out 19.250 9,588.51 1 AT205 recire.

1.939 23.21 1BT205 recire.

2.067 25.09 1 AP2021 out 0.957 24.03 1 AP202-2 out 0.957 10.17 lCP202-1 out 0 957 29.32 1CP202 2 out 0.957 10.64 1CVH210 out 3.068 L29.33 l

tGVH210 out 3.C68 135.02 IEVH210 out 3.068 147.13 l

1 AVH210 out 3.068 146.37 l

!! Reverse Flow Through Check Valve

&& Pump Flow is Past End of Curve

" Flow Below Minimum SS NPSH Avadable Below NPSH Required l

~

. ~ -

m

,yg s/11/98 10:19 PROTO FLO 4.01 by Proto-Pcwor Corporati:n - Serial #PFL-0000 r:se2 or4 Public Service Ele:tricand Oas GMSSGil1355\\New UHSiSTACSUHS2.PDB Revision 2.00 Hope Creek Generating Station. STACS i

~

Flow Summary Report Conw gence; besans-l.0C-5 Sum Q=1.0E.2 Mcdor:=l.0R 6 FCVal.0E 4 PCV-l.0L4 'lcepnaturc=3.0E4 Post LOP.1 and 1 SSWS Flow Summary Title Diameter Flow Minimum Flow NPSHA NPSH (in)

(gpm)

(gpm)

(ft)

Ratio 1 AVH209 out 3.068 79.48 1BVH209 out 3.068 108.30 l

1 AVH208 out 1.939 33.64 1BVH208 out 1.939 33.14 IFVH210 out 3.068 155.05 1BYH210 out 3.068 155.32 IBF2021 out 0.957 29.82 1BP202-2 out 0.957 10.62

~

IDP202-1 out 0.957 26.90 IDP202 2 out 0.957 10.44 IDVH210 out 3.068 151.01 1HVH210 out 3.068 l$0.87 1 AVH213 out 4.026 436.00 1GVH211 out 3 068 115.74 1CVH211 out 3.068 115.19 IFVH213 out 4.026 446.50 1BVH213 out 4.026 450.31 1CVH213 out 4.026 430.43 1DVH213 out 4.026 441.61 lEVH213 out 4.026 426.48 1 AK202 out 0 957 6.44 4

l

!! Revene Flow T1uough Check Valve

&& Pump hlow is Past End of Curve

" Flow Below Minimum

$5 NPSH Available BelowNPSH Required l

8/11/98 10.19 PROTO+FLO 4.01 by Proto-Psw:r Corporation = Serial #PFL-0000 pr 3 cr 4 Public Service Electric and Gas G:\\PSEG\\11385Wew UHSiSTACSUHS2.PDB Revision 2.00 Hope Creek Generati:

S 4 tation. STACS Flow Sununary Repon Convergence-Pregure=I 0E-5 5um Q=1.0E 2 Fnction.l.0E.6 FCv=1.0E-4 PCV=1.0E 3 To nperata=$ 08 3 Post LOP. I and 1 SSWS Flow Summary Title Diameter Flow Minimum Flow NPSHA NPSH (In)

(gpm)

(gpm)

(ft)

Ratio ID3%4V4 QUI V.yJ /

O.J 4 IHVH211 out 3.068

!!8.31 1DVH211 out 3.068 117.74 1FVH211 out 3.068 117.58 IBVH211 out 3.068 117.71 1 AVH211 out 3.068 114.65 1EVK211 out 3.068 114.62 1AE328/1BE328 comb. out 0.546 t 1.28 1 AE328/1BE328 out 0.546 11.28 1 AK400 out 6.065 2,153.03 1 AVE 412 out 6.065 464.38 IEVE412 6.065 543.57 1 EVE 412 out 6.065 544.04 1 AE408!405/404 out 7.981 1,113.86 1CVE412 out 6.065 468.23 IGVE412 out 6.065 548.55 tCE408/405/404 out 7.981 1,123.14 1BVE412 out 6.065 538.11 IFVE412 out 6.065 538.11 1DVE412 out 6.065 534.05 IHVE412 out 6.45 613.01

!! Reverse Flow Through Check Valve

&& Pump F ow is Past End of Curve

    • Flow Below Minimum

$$ NPS11 Available Below NPSH Required I

dNE~T'c TserrJJEnGETB P.aseat

~

8/l1/98 10:19 PROTO FLO 4.01 by Proto-Power Corporation - Serir.1 #PFL*0000 t'ase 4 or 4 Public Service Elecuic and Gu - OnPSEOT11 385\\New UH5\\STACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station - $T/.CS Flow Summary Report Ccevergence: Preuurv=1.04-$ Sum (=t.0E-2 hiedonal oE4 FCV=1.0R4 PCV=1,0E.3 Tempersture=5.0C.3 Post LOP. I and 1 SSWS Flow Summary Title Diameter Flow Maimum Flow NPSHA NPSH (in)

(spm)

(gpm)

(ft)

Ratio A DCTV5,9VJ/9V9 Out

/.751 1,4 WJ. 4 V 1BK400 out 6.065 1,890.96 1DE408/405/404 out 7.981 1,096.67 1 AK403 out 6.065 586.83 1BK403 out 6.065 595.95 RE4859D2 out 0.957 12.36 RE4859A2 out 0.957 11.46 ll Reverse Flow Through Check Valve

&& Pump Flow is Past End of Curve

" Flow Delow Muumurn

$$ NPSH Available Below NPSH Required 9

m m mrv n-x a m e s m re r w'n i

I s/ tit 9s 10:19 PROTO-FLO 4.01 by Proto-Power Corporatioti - Serial APF1-0000 Pase I of 26 Public Service Eler.trie and Gas 0:'ESEGT11 385\\New UHSTSTACSUHS2.PDB - Revision 2.00

~~

Hope Creek Generating Station STACS l

Heat Exchanger Data Report l

Comerger.cc: Pressure-l.0E 5 Sum Q-1.08-2 Medem=1.DE-6 FCV-l.0E 4 PCv=1.UE-3 Terrpencure=5 OE 3 Post LOP 1 and 1 SSWS 00E129 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfir: Bas:o,Inc.

Model: ES-24/18096 Dwgs: PM050 0039-3 System Fluid:

Heat Load =

500,000.00 BTU /hr 00K107 HX Type: Fhed Heat Load HX Status: On / Notin Flow Path Mfr: American Std.

Model: 06060 Dwas: PM050-0022-5 System Fluid.

Heat Load -

2,240,323.00B'IU/hr 10C150 HX Type: Fixed Heat Load HX Status: Off l

Mft:

Mod:1:

Dwas:

System Fluid:

Heat Load =

0.00 BTU /hr 10E1110 11X Type: Fhed Heat Load HX Status: On / Notin Flow Path Mfr: Basco,Inc.

Model: 8A24A08072 Dwgs: Pl.342287 l

System Fluid:

Heat Losd =

515,000.00 BTU /hr 10E114 HX Type: Fhed Heat Load HX Status: On! Notin Flow Path Mfr: Gen. Elect. Co.

Model: MDE0965400 Dwas: PM003-0-1-7 l

System Fluid:

I Heat Load =

42,300.00 BTlkhr 10E129 HX Type: Thed Heat Load HX S:stus: Ou / Not in Flow Path Mft: Basco. Inc.

Model. ES-24/18096 Dwgs: PM050-0039-3 System Fluid:

Heat Load =

10,750.00BRl/hr i

I'-

i l

s/l1/9s 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - Scrial #PFL-0000 Page 2 or 26 i

Public Service Elcetric and Gas - G:\\PSEO\\11-385 Wow UHS \\STACSUHS2.PDB Revnion 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report Concigence: Frusure-l.0E.5 Sum Qv1 CE.2 fnceanal.0E4 FCV=1 OE 4 PCVal.0E 3 Temperstare,10E-3 l

l Post LOP - 1 and i SSWS l

10K107 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfr American Std.

Modct: 06060 Dwas: PM050-0022 5 Systemfluid:

Heat Lead =

5,412,000.00 BTU /hr 1AIEll8 HX Type: Fixed Heat Load HX Statua: Off j

M&:DeLaval/IMO Model; MDE1328000 Dwgs: PM012-0099 l

System Fluid-Hast Lead =

0.00 BTU /hr 1A1E201 HX Type: Shell & Tube liX Status: On /in Flow Path Mft: Graham Mfg. Co.

Model: 92-6 504 CGN Dwgs: PM069Q-0058 l

Tube Fluid. Brackish Water 12 ppt Shell Fluid: Fmh Water Shell Flow - 9,414.63 Shell Temperatures = 117.60'F - 99.673F Tube Flow = 7,988.00 Tube Temperatures = 89.46*F - 110.6l'F Construction Type: TEMA-O 1 Shells, O She!! Passcs,4 Tube Passes Shell Min Area = 6.2530 ft^2, Design Shell Velocity = 3.900 ft/s, Shell Diarneter - 92.000 Baffle Info Spacing = 62.000 in, Thicicness = 0.000 in, Area = 0.000 ft^2, K = 0.000 Tubes: Da = 0.694 in Dout = 0.750 in, Length = 42.00 ft, K = 9.50 Tube Pitch :0.9375 in Tube Pitch Type = Triangular 5,700 of 5,700 Tubes Active UTubes = No Effecave Area-46,295.00 ft^2 Area Factor = 0.9849 Fouling = 0.0000 (inside) 0.0012 (outside)

HotT= 0.4888 l

LMTD = 8,4985 LMID Conee: ions FF = 0.7484 Fb = 1.0000 Heat Load =

83,549.877.81 BTU /hr UOverall = 283.74 B'!Uhr/ft^2fF l

?

1A2 Ell 8 HX Type: Fixed Heat Load HX Sta:us: Off Mft:DeLaval/IMO Model: MDEl328000 Dwgs: PM012 0099 System Fluid:

Heat Load =

0.00 BTU 4 r 9

4 l

l

e+

c*rar umr st4RN.

@.08/0t l'

S/11/98 10:19 PROTO-FLO 4.01 by Proto-P4wer Corpor2 tion - Serial #PFL-0000 Page 3 of 26 Public Service Electric and Gas - G:\\PSEGill.385Wew UHS 6TACSUHS2.PDB - Revision 2.00 Hope Creek Generaung Station-STACS Heat Exchanger Data Report Cornergence: Preuurr=1.0E-3 Sum Qal.0F.-2 Fricecn=1.0E 6 FCV-1 OE-4 PCV=1.ch-3 Terryerstate=5.0E-3 Post LOP - 1 and 1 SSWS IA2E201 HX Type: Shell & Tube HX Status: On / in Flow Path Mft:GrahamMfg Co.

Model: 92 6 504 CGN Dwgs: PM069Q-0058 Tube Fluid: Brackish Water 12 ppt ShellFluid: Flesh Water Shell Flow = 9,882.82 ShcIl Temperatures = 117.60*F-100.23'F Tube Flow = 7,954.00 Tube Temperatures = 89.46*F - 111.06*F Constmetion Type:IEMA-G 1 Shells, O Shell Passes, 4 Tube Passes Shell Min Area = 6 2530 ft^2, Design Shell Velocity = 3.900 ft/s, Shell Diameter = 92.000 l

Baffle info: Spacing = 62.000 in, Thickness = 0.000 in, Area = 0.000 ft^2, K = 0.000 Tubes: Din = 0.694 in, Dout = 0.750 in, Length = 42.00 ft, K - 9.50 Tube Pitch = 0 9375 in Tube Pitch Type - Triangular 5,700 of 5,700 Tubes Active UTubes = No Effective Area = 46,295.00 ft^2 Area Factor = 0.9849 Foulmg = 0.0000 (inside) 0.0012 (outside)

Hoff = 0.4888 LMTD = 8.4856 LMTD Corrections FF = 0.7543 Pb = 1.0000 Heat Lond -

84.941,317.07 BTU /h:

UOverall = 286.58 BTUAr/ft^2/*F l

1 AEl109 HX Type: Fixed Heat Load HX Status: Off Mfr: Basco Inc.

Model: 8A43A08048 Dwgs: PI-342287 System Fluid:

Heat Load =

0.00 BTC/hr 1AEl11 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: General Elect.

Modeh 264A4808 Dwgs: PM003-TR-18-5 System Fluid.

Heat Load =

515,000.00 BTU /hr i

l 1 AEl12 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path j

Mft: General Elect.

Model: 114D8270 Dwgs: PM003-G-1-7 System Fluid:

Heat Load =

42,300.00 BTU /hr l

NN6 F.@9 31 s/1 tr9s 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL 0000 case 4 of as Public Service Electric and Gas - 0:\\PSEG\\l1 385\\New UNSWTACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report convergence Presure+1.0E.3 3an Qwl.0E 2 Prt tional.0E.6 FCVal 0l!-4 PCV=1.0E 3 Temperatun=ioE-3 Post LOP - 1 and 1 SSWS 1 AEt15 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: H.K. Porter Co/

Model: T-140963X45 Dwgs: PE005-0012-9 System FMd.

Heat Load -

10,750.00 BTU /hr 1AEl16 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfr: General Elect Mooel: 155B8243P001 Dwss: PM003-T6-1-2 Sys:em Fluid:

Heat Load -

5,412,000.00 BTU /hr IAE117 HX Type: Fixed Heat Load HX Status: Off Mft: General Elect.

Model: MDE0924300 Dwgs: PM003-0-1-7 System Fluid:

Heat Load =

0.00 BTU /hr l AE126 HX Type: Fixed Heat Load HX Status: Off Mfr: Amerinn Std.

Model: 5-046-17-168-3 Dwgs: N1-931-St-120 System Fluid.

Heat Load =

0.00 BTU,tr 1 AE130 HXType: Fixed Heat Load HX Stams: off Mfr: Ametek/Whitlock Model; 4-W18HT 4 A CB Dwas: PM007-00313 System Fhad:

Heat Load -

0.00 BTU,tr IAE202 HX Type: Fixed Hea: Load HX Status: Off Mfr; Alfa-LavalInc.

Model: A-20-BXS Dwgs: PM071Q-0010 System Fluid:

Heat Losd -

0.00 BTUth:

i l.

l l

r trr_'Ts p,i3p,i -

8/12/98 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 Pase 5 of 26 Public Scryice Electric and Gas - G:\\PSEG\\l1-285Wew UHSLSTACSCHS2.PDB - Revision 2.00 l

Hope Creek Generating Station - STACS l

Heat Exchanger Data Report Convergenec: Prcnurcal.0E 5 Sam Q-l.CE 2 Prichon-!.0E-4 FCV-1.0E-4 PCV=1.0E-3 Temperarsc=$.0E.3 Post LOP 1 and 1 SSWS 1AE205 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Delin Southern Model: 21A9227AN Dwgs:.No-E11 B0015 System Fluid: Fresh Water Tube Flow - 9,655.52 Tube Temperatures - 99.96*F - 127.59'F Heat Load =

132.500.000.00 BTU /hr 1 AE214 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfr: CVIInc.

Model: C735 9934 Dwgs: PM04SQ-0071-4 System Fluid:

Heat Load =

19,300,000.00 BTU 41r 1AE218 HX Type: Fixed Heat Load HX Status: Off Mfr: CVIInc.

Model: C735-9934 Dwgs: PM048Q-007l 4 System Fluid:

Heat Load =

0.00 BTU /hr 1AE278 HXType: Fixed Heat Load HX Status: off Mfr CVIInc.

Model:

Dwgs: PM048Q System Fluid:

Heat Load =

0.00 BTU /hr l

lAE328 HXType: Fixed Heat Lead HX Status: On!in Flow Path Mft: Parker-Hanison Model: HDTC-SS-6 2 Dwgs:

System Fluid:

Shell Flow = 5.19 Shell Temperatures = 99.96'F 121.30*F Heat toad =

55,000.00 BIL*/hr

[

\\

m rmm-m m

S/l1/9810:19 PROTO-FLO 4.01 by Proto-Power Comoration S:: rial (lPFL-0000 Pase 6 or 26 Public Service Electne and Gas - On.PSEO\\11-385\\New UHS \\STACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report Conms;ence Preuurt=1.0E-5 Sum Q=1 OE 2 Frictiel.0E-6 FCV=t.0E-4 PCv=1.0F.-3 Tcmpc10 te 5.0E 3 Post LOP. I and I SSWS 1AE404 HX Type: Fixed Heatload HX Status: On / in Flow Path Mfr: American Std.

Model: 17072 CPT Dwgs: PM01SQ System Fluid: Fresh Water Tube Flow = 1,113.19 Tube Temperatures = 115.44*F - 117.90*F Heat Load =

1,353,000.00 BTU /hr lAE405 HX Type: Fixed Heat Load HX Status: On / In Flow Path Mfr: American Std.

Model: 19084 CPT Dwgs: PM01SQ System Fluid: Fresh Water Tube Flow - 1,110.68 Tube Temperatures = 105.62T 115.44'F Heat Load =

5,412,000.00 BTU /hr IAE408 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Ameri:an Std.

Model: 19198 Dwgs: PM018Q System Fluid; Fresh Water Tube Flow a 1,109.35 Tube Temperatures - 99.96*F 105 62T Heat Load 3,118,000.00 BTU /hr 1 AK111 HX Type: Fixed Heat Load HX Status: On / Fot in Flow Path Mft: Carner Corp.

Model: 19FA553B5005932 Dwgs: PM623-0002-9 System Fluid:

HeatLoad-502,781.00 BTU /hr IAK202 HX Type: Fixed Heat Load llX Status: On/ in Flow Path Mft: CVIInc.

Model: C'35 9909 Dwgs: PM048Q-0044-2 SystemFlu!i Fresh Water Tube Flow = 6.42 Tube Temperatures = 99.967 - 11f.64T Heat Lead =

50,000.00 BTUfor

r

-sm r, cc, u a 81/1t/9810:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial flPFL-0000 Pasi7 or 26 Public Service Electric and Gas. G:\\PSEGil 1-385\\New UHTSTACSUHS2.PDB - Revision 2.00

~~

Hope Creek Genenting Station. STACS Heat ExchangerData Report Cornergence: Presurre=1.0E 5 3 m Q=1 DE-2 Fr6ction=L05-6 FCV=1 C5 4 PCV=1 CE4 7ergernwre-f OE-3 Post LOP 1 rad I SSWS IAK400 HX Typc: Fixed Heat Load HX Status: On/ m Flow Path Mir: Carrier Corp.

Model: 19FA455B122022 Dwgs: PM723Q System Fluid: Fresh Wuer Tube Flow - 2.149.79 Tube Temperatures = 99.96'F - 107.01'F Heat Load =

7,530,700.00 BTU /hr

' 1AK403 HX Type: Fixed Host Load HX Status: On / in Flow Path Mfr Camer Coro.

Model 19FA441Bt142020 Dwgs: PM723Q System Fluid: Fresh Water Tube Flow - $85.74 Tube Temperatures - 99.967 - 108.517 Heat Load =

2,515,340.00 BTU /hr 1 AP176 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfr: Carrier Corp.

Model: 19FA999-100718 Dwgs: PM623118 System Fluid:

Heat Load =

100,000.00 BTU /hr LAP 202-1 HX Type: Fixed Heat Load HX Status: Oc / in Flow Path Mfr:GrahamMfg Co.

Model: 8X4C-12 Dwgs: N1 F.11-C002-51 System Fluid: Fresh Water Tube Flow = 23.86 Tube Temperatures = 99.967 - 129.497 Heat Load -

350,000.00 BTU /hr IAP202 2 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Graham Mfg. Co.

Model: 992C430BX Dwgs: N1-E11-C002-6 SystemFluid: Freshwater Tube Flow = 10.16 Tube Temperatures = 99.967 - 101,94*F Heat Load =

10,000.00 BTU /hr l

l t

ancm re; Tyre n 8/t1/9810:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 Pase a of a6 Public Service Electric and Gas - 0 \\PSEO\\11-385Wew LTIS'STACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report Cucveraence; honore-1.0E 3 Sum Q-l.0E 2 Frie::o:el.CE 6 FCV-1 CE-4 PCV-1 OE 3 rempmu.w=5.0C-3 Post LOP I and 1 SSWS 1 AVE 412 HX Typ:: Fixed Heat Lead HX Status: On / in Flow Path Mfr: Trane Co.

Model: MDE1291600 Dwgs: PM731Q System Fluirt Fresh Water Tube Flow = 463.91 Tube Temperatures = 99.96*F - 104.74'F Heat Load =

1,100,000.00 BTU /hr 1 AVIll13 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: Amer. Air Fitr.

Model: H36MPACYA Dwgs: PM611A-00304 System F1uid:

Heat Load =

502,781.00 BTU /hr 1AYHI16 HX Type: Fixed Hut Load HX Status: On / Notin Flow Path Mft: Amer. Air Fltr.

Model: H36MPACYA Dwas: PM611 A-0033-4 System Fluid:

Heat Lead -

530,000.00 BTU /hr 1AVH208 HX Type: Fixed Heat Lead HX Status: On /in Flow Path Mft: Amer. Air Fitr.

Model: MDE1572400 Dwgs: PM7IIQ System Fluid: Frcsh Water Tube Flow - 33 62 Tube Temperatures " 100.00'F 102.70'F Heat Load -

45,000.00 BTU /hr 1AVH209 HX Type: Fixed Heat Load 11X Status: On / in Flow Path Mft: Amer. Air Fitt.

Model: MDE1571400 Dwgs: PM71IQ System Fluid: Fresh Water Tube Flow - 79A3 Tube Temperatures = 99.96*F - 102.88'F Heat Load =

115,000.00 BTU /hr l

--wvvmarsraw i c i e r..-.s6 8/l1/98 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - S: rial (!PFL-0000 pag.o or 26 4

Public Service Electric and Gas. G3PSEG\\11-385iNew UHS \\STACSUHS2.PDB. Revision 2.00 Hope Creek Generating Station - STACS Heat Exchanger Data Report Ceer;;ence Prenareal.0E-5 Sam Q=1 OE 2 Frictiel.004 FCV=1.0E4 PCVal.0E 3 Tempemwe=$.0E4 Post LOP. I and 1 SSWS 1AYH210 HXType: FixedHeatLoad HX Stams: On / in Flow Path Mfr: Amer. Air Fltr.

Model: MDE1570300 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow = 146.28 Tube Ternperatures = 99.96'F - 102.83'F Heat Load -

210,000.00 BIU/hr 1 AVH211 HX Type: Fixed Heat Load HX Sts:us: Off Mft: Amer. Ai:Fiz.

Model: MDE1573500 Dwgs: PM711Q System FMd: Fresh Water Heat Load =

0.00 BTUthr IAVH213 HX Type: ' Fixed Heat Load HX Status: Off M&: Amer. Air Fitt.

Model: MDE2478600 Dwas: PM786Q System Fluid: Fresh Wa:et Heat Losd =

0 00 BTU /hr 1B1Ella HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mh: DeLava14MO Model: MDE1328000 Dwgs: PM012-0099 System Fluid:

Heat Load =

400,000.00 BTU /hr g

sv:nwrne v-~m.) gi '

L*

Sn1/9810;19 PROTO-FLO 4.0t by Proto Power Corporation = Serial #PFL-0000 Pase to of 26 j

Public Service Electric and Gas GAPSEO;11-385 dew UHSLSTACSUHS2.PDB - Rev sion 2.00 Hope Creek Genera mng Station - STACS I

Heat Exchanger Data Report Convergece: Pmsun=1.0E 5 Sum Q=105 2 Friction-1.CG4 FCV=1.064 PCV=lE3 Tmperaturewi Of.3 Post LOP - I and 1 SSWS 1B11!201 HX Type: Shell & Tube HX Statas: On /.n Flow Path Mfr: Oraham Mfg.Co.

Model: 92 6 504 CON Dwgs: T w69Q 0058 Tube Fluid: Brackish Waser 12 pt ShellFluid: Fresh Water P

Sbell Flow -9,295.56 shellTemperatures = 117.977 99.84'F Tube Flow = 7.832.00 Tube Temperatures = 89.46*F - 110.987 Construction Type: TEMA-G i.

I Shells, O Shell Passes. 4 Tube Passes Shell Min Area = 6.2530 ft^2, Design Shell Velocity = 3.900 ft's, Shell Dwneter = 92.000 Bafne Info: Spacing = 62.000 in. Thickness = 0.000 in, Area = 0.000 ft^2, K = 0.000 Tubes: Din = 0.694 in Dout = 0.750 in. Length = 42.00 n, K = 9.50 l

Tube Pitch = 0.9375 m Tube Pitch Type = Triangular 5,700 of 5.700 Tubes Active LTubes = No EEcetive Arca -46,295.00 ft^2 Area Factor = 0.9849 l

Fouting = 0.0000 (inside) 0.0012 (outside) hoe-- 0.4883 LMTD = 8.5665 LMTD Corrections FF = 0.7453 Fb = 1.0000 I

Heat Load -

83,361,928.06 BrU/hr L'Overall-282.05 BTU /hr/ft#2rF IB2El18 HX Type: Fixed Heat Load MX Status: On/ Notin Flow Path Mh:DeLaval/1MO Model: MDE1328000 Dwgs: PM012-0090 System Fbid:

Heat Load -

- 400,000.00 BW/hr i

I l

I L

\\

1-

l' s/t1/9810:19 PROTO-FLO 4.01 by Proto-P wet Corporation - Serial #PFL-0000 Pese 1I of 26 Public Service Electric and Gas - GAPSEG\\11-385\\New UHS \\STACSUHS2.PDB - Revision 2.00 Hope Creek Generating Sution - STACS t

. Heat Exchanger Data Report convergcrtce: PrCMJrc=1.0F. 5 Surn Q-1.05 2 Friction-1054 FCY=1 OPA PCV-1.0E-3 Tempers:ure=10E4 Post LOP. I and 1 SSWS IB2E201 HX Type: Shell & Tube HX Status: On /in Flow Path Mfr: Graham Mfg. Co.

Model: 92-6-504 CON Dwgs: PM069Q 0058 Tube Fluid: Brackisb Water 12 ppt ShellFluid: Fresh Water l

Shell Flow - 9.627.27 ShellTetnperatures = 117.97'F 100.15'F Tube Flow = 7,894.00 Tube Temperatures = 89 46*F - 111.20*F Construction Type: TEMA4 1 Shells, O Shen Passes. 4 Tube Passes Shell Man Arca - 6.2530 ft^2, Design Shell Velocity - 3.900 fVs, Shell Diameter = 92.000 Baffle Info: 5 pacing = 62.000 in. Thickness = 0.000 in. Area = 0.000 ft^2, K = 0.000 j

Tubes: Din = 0.694 in, Dout = 0.750 in, Length = 42.00 ft. K = 9.50

' Tube Pitch - 0.9375 in Tube Pitch Type -Triangular 5,700 of 5,700 Tubes Active UTubes = No Effective Area 46,205.00 A^2 Area Factor = 0 9849 Fouling = 0.0000 (inside) 0.0012 (outside)

Ho!T = 0.4888 LMTD = R.5797 LMTD Conections FF = 0.7504 Ib = 1.0000 Heat Load =

84,849,437.77 BTU /br Uoverall = 284.67 BTU /hr/ft^2/*F 1 bel 109 EX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mft: Basco Inc.

Model: 8A44A08048 Dwgs: P1-342287 Systeta Fluil Heat Load =

481.650.00 BTU /hr 1 bel 11 HXType: Fixed Heat Load HX Status: On / Not in Flow Patit Mft: General Elect.

Model: 264A4808 Dwgs: PM003-TR 18 5 System Fluid:

Heat Load -

9,360,000.00 BTU /br IBE112 HX Type: Fixed Heat Load HX Status: On / Not in Flow Pa*h Mfr: General Elect.

Model: ll4D8270 Dwgs: PM003-O-t-7 Systern Fluid:

Heat Load =

3,487,500.00 BTU /hr l

I i

n g ; u,,p l

8/l!!98 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - St-ial #PFL-0000 p.tte12 of 26 Nhlic Service Electric and Gas - 0:\\PSEOi!1-385\\New UHSiSTACSCHS2.PDB Revision 2.00 1

Hope Creek Genc sting Station STACS Heat Exchanger Data Report Convergence. Presstrc=1.0E4 Sum Q=1.02-2 Friction =1.0E 6 FCV-1.0E 4 PCV 1 CE4 Ternpersare=5 oE-3 Post LOP. I and l SSWS IBEll5 HX Type: Fixed Heat Load EX Status: On / Not in Flow Path Mfr, ILK. Porter Co.

_ Model: T 140963X45 Dwgs: PE005.0012 9 System Fluid:

1 Heat Load =

515,000.00 BIL%r 1 DEI 16 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfh General Elect.

Model: 155B8243P001 Dwgs: PM003-T6-1 2 System Fluid-HeatLoad-42,500.00 BTU /hr 1DE117 HX Type: Fixed Heat Load HX Status: On / Not m Flow Path Mfr: General Elect.

Model: MDE0924300 Dwgs: PM003-G 17 System Fhid:

Heat Load -

8,030,000.00 BTU /hr 1BE126 HX Type: Fixed Heat Load HX Stanis: On / Notin Flow Path Mfr: American Std.

Model: 5-0046-17-168-3 Dwgs: N1-B31-Sl 120 System Fluid:

Heat Load =

5,630,000.00 BTU,tr 1BE130 HX Type: Fixed Heat Load FDC Status: 03 / Not in Flow Path Mft: Ametek/Whidock Model: 4 Wl8HT 4.A CB Dwgs: PM007-00313 System Fluid:

Host Load -

42,300.00 BTU,tr IBE202 HX Type: Fixed Heat Load HX Status: off Mfr: Alfa Lavallac.

Model: A-20-BXS Dwas: PM071Q-0010 System Fluid:

Heat Load =

0.00 BTU &r l

i

N-mnrr3 snrzTe Q/a1 i

1

'8/11/98 10:19 PROTO-FLO 4.01 by Prot:,-Power Corporation - Serial #PFL-0000 Pese 13 of 26 Public Service Electric and Gas - 0:\\PSEG\\11 385\\New UHSiSTACSUHS2.PDB - Revision 2.00 Hope Crwk Generanng Station STACS Heat ExchangerData Report Convergen::e: Pressurc=1.0E-5 5;;m Qal.05-2 Fricta=1.05-6 FCV-l.CE 4 (O'-1.CE 3 TernperuurMUE 3 Post LOP I and 1 SSWS IBE205 HX Type: Fixed Heat Load HX Status: Ou / in Flow Pai Mft: Delta Southern Model: 21A9227AN Dwgs: NO EL1 B0015 System Fluid: Fresh Water Tube Flow = 9,381.39 Tube Tempe...

00 00*F - 128 A3*F Heat lead -

132,500,000.00 BTU /hr IDE214 HX Type: FixedIIeat Load HX Status: On / Not in Flow Path Mfr. CVIInc.

Model: C735-9934 Dwgs: PM048Q-007I 4 System Fluid:

Heat Load =

9,565 00 BTU /hr IBE218 HX Type: Fixed Heat Load HX Stams: On / Not in Flow Path M(r: CVT inc.

Modeh C735-9934 Dwgs: PM048Q 00714 System Fluid:

Heat Losd e 10,750.00 BTU /hr l

IBE278 HX Type: Fixed Heat Load HX Status: On / Notin flow Path Mft: CVI Inc.

Model:

Dwgs: PM048Q Systern Fluid:

Heat Load -

6,000.00 BTU /hr IBE328 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mfr: Parker Hamson Model: HDTC-SS 6-2 Dwgs:

System Fluid:

Shell Flow - 6.04 Shell Temperatures - 99.96'F - 118.29*F Heat load =

$5,000.00 BTU /hr f

l

*J'N6~FrW~~W~TWFJ a)@ t 21 e p, i 9,? a l

i 8/11/98 10:19 PROTO-FLO 4.01 by Proto Power Corporation - Serial #PFL-0000 Pase 14 of 26 Public Service Electric and Gas - G:\\PSEGil1385\\New L'HS\\STACSURS2.PDD - Revision 2.00 i

~~

Hope Creek Generatina Station - STACS Heat Exchanger Data Report Convergence: Pnewst=1.06 5 Sum Qel CE.2 Fr(etion=I DE4 FCV=1.0F..a PCV=1.0E.1 Tempemtute*5 OE.3 Post LOP - 1 and 1 SSWS 1BE404 HX Type: Fixed Heat Load HX Satus: On /in Flow Path Mfr: American Std.

Model: 17072 CPT Dw3s: PMOISQ Systern Fluid. Fresh Water Tube Flow = 1,102.52 Tube Temperature.s = 115,63'F - 118.t l'F Heat Load =

1,353,000.00 BTU.t.r IBE405 HX T)pe: fixed Heat Load HX Status: On / in Flow Path Mir:American Std.

Model: 19084 CPT Dwgs: PM01SQ System Fluid: Fresh Water Tube Flow - 1,100.01 Tube Temperatures = 10$,71*F - 115.63*F Heat Load =

5,412,000.00 BTU /hr 1BE408 HX Type: Fixed Heat Lead HX Status: On/in Flow Path i

Mfr: American 5:d.

Model: 19198 0wgs: PM018Q

' System Fluid: Fresh Water Tube Flow = 1,098.68 Tube Temperatures = 100.00'F - 105.71'F HeatLoad=

3,118,000.00 BTU /hr i

i 1BK111 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: Carrier Corp.

Model: 19FA553B5005932 Dwgs: PM623-0002-9 i

System Fluid:

i Heat Load =

19,500,000 00BTUar i

i 1BK202 HX Type: Frxed Heat Load HX Status: Os /in Flow Path i

Mfr:CVIInc.

Model: C735 9909 Dwgs: PM04 SQ-0044-2 System Fluid: Fresh Water Tube Flow = 6.30 Tube Ten:peratures = 100.00'F 115.99'F j

Heat Load =

50,000.00 BTU /hr i

i l

I I

i l-l.

e aa 8/11/98 10:19 PROTO-FLO 4.01 by Proto+ Power Corporation - Scrial #PFL-0000 pap is or 26 Public Service Electric and Osa GAPSEO\\11 385\\New UHS $TACSGS2.PDB - Revision 2.00 Hope CreekGenerating Station STACS l

Heat Exchanger Data Report

(*nnvergen:c: Pressure =1.0E S Sum Q=1.CE-2 Friction =1.oE-6 FCVal.0E-4 PCV=1.CE-3 Terrperuurces.0FA Post LOP 1 and 1 SSWS l

1BK400 HX Type. Fixed Heat Load HX Status: On /in Flow Path Mfr: Camer Corp.

Model; 19FA455B122022 Dwgs: PM723Q System Fluid: Fresh Water Tube Flow = 1,887.70 Tube Temperatures = 100.004 - 108.03Y Heat Load =

7,530,700.00BTUihr IBK403 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mfr: Carner Corp.

Model: 19FA441B'142020 Dwgs: PM723Q System Fluid: Fresh Water Tube Flow = 594.86 Tube Temperatures - 100.007 - 10b.51Y Heat Load =

2,515,340.00B'IU/hr

!BPl?6 HX Type: Fe,ed Heat Load HX Status: Ou / Not in Flow Path

~

Mfr. Carrier Corp.

Model: 19FA999-1007-l8 Dwgr PM623118 SystemFluid:

Heat Load =

100,000.00 BTU /hr IBP2021 HX Type: Fixed Heat Load HX Status: On/ in Flow Path Mft: Oraham Mfg. Co.

Model: 8X4C-12 Dwas N1.E11 C002 51 SysteciFluid: Fresh Wa:er Tube Flow - 29.66 Tube Temperatures = 100.00*F - 123.76T Heat Load =

350,000.00 BIU/hr 1BP202-2 HX Type: Fixed Heat Load HX Status: On / in Flow Padt MA:Oraham Mfg Co.

Model: 992C4'30BX Dwgs: Nt.E11 C002 6 System Fluid. Fresh Water Tube Flow - 10.62 Tube Temperatures = 100.007 101.90T Heat Load =

10,000.00 BTU /hr s

i 1

i

-+

mm l

)

8/11/98 10.19 PROTO-FLO 4.01 by Proto Pcwer Corporation - Serial #PFL-0000 Pase 16 er 26 Public Service Electric and Gas - G:\\PSEGill.385Wew UHSWTACSCHS2.PDB. Revision 2.00 Hope Creek Generadng Station STACS Heat Exchanger Data Report Converpr.ce:Presurt=1.DE.5 Sum Q=1 CE 2 Frictien-l 0E 6 FCV=1.06A PCV=153 Terrpe-ature=$.0E-3 Post LOP. I and 1 SSWS 1BVE412 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mrt: Trase Co.

Model: MDE1291600 Dwgs: PM731Q System Fluid: Fresh Water Tube Flow - 537.63 Tube Ternperacu es - 100.00*F 104.12*F Heat Load "

1,100,000.00 BnJ/hr 1Bvill13 HX Type. Fixed Heat Load HX Status: orr Mfh Amer. Air Fitr.

Medel: H36MPACYA Dwgs: PM611 A-0030-4 System Fluid:

Heat Load =

0.00 BTU /hr 1BVH116 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mft: Amer. Air FItr.

Model: H36MPACYA Dwgs: PM611A-0033 4 System Fluid:

Heat Load -

530,000.00 BTU /br 1BVH208 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mft: Amer. Air Fitt.

Model: MDE1572400 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow - 33.12 Tube Ternperatures = 100.00'F 102.74'F Heat Load -

45,000.00 BTU /hr IBVH209 HX Type: Fixed Ilest Load HX Status: On /in Flow Path Mft: Amer. Air Fitt.

Model MDE1571400 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow = 108.25 Tube Temperatures = 99.96'F 102.10*F Heat Load -

115,000.00 BTU /hr i

mn I

l

~*

8/lI/9810:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 Pase 17 or 26 Public Service Electric and Gas G:\\PSEG\\11-385Wew UHS'STACSUHS2.PDB - Revinon 2.00 Hope Creek Generating Station - STACS Heat ExchangerData Report (hvergence: Prawrr='.0L;.5 Sm Q-1.0E-2 Friction-1.066 FCV-1 CE 4 PCV-1,0E 3 Teqwran.re-10E-3 Post LOP - I and 1 SSWS 1BVH210 HX Type: Fixed Heat Load HX Status: On / in Flow Path L

Mft: Amer. Air Fit.

Model: MDE1570300 Dwas: PM71IQ System Fluid: Fresh Water Tube Flow = 155.24 Tube Temperatures = 100.00*F - 102.73*F Heat Load -

210,000.00 BTU /hr IDVH211 HX Type: Fixed Heat Load HX Status: Off Mfh Amer. Air Fitr.

Model. MDE1573500 Dwgs: PM711Q j

SystemFlund: Fresh Water Heat Load =

0.00 BTU /hr IBVH213 HX Type: Fixed Heat Load HX Status: Oty Mfr:Anacr. Air Fitr.

Model: MDE2478600 DwEs: PM786Q System Fluid: Fresh Water Heat Load -

0.00BTV/hr 1C1ElI8 HX Type: Fixed Heat Load HX Status: On/ h*otin Flow Path Mft: DeLaval/IMO Model: MDE1328000 Dwgs: PM012 0099

- System Fluid:

Heat Load =

400,000.00 BTC/hr IC2EI18 HX Type: Fixed Heat Lead HX Status: On / Notin Flow Path Mfr DeLaval/IMO Model: MDE1328000 Dwas: PM012-0099 System Fluid:

Hea: Load =

400,000.00 BTU /hr ICEl12 tiX Type: Fixed Heat Load FX Status: On / Not in Flow Path Mir: General Elect.

'Model. 114D8270 Dwgs: PM003-G 1-7 System Fluid:

Heat Load -

5,487,500.00 BTU /hr t

osw nwmeaac'rrTammnncm a:p 31 s/11/98 10:19 PROTO-FLO 4.01 by Proto Power Corporation - S: rial #PFL-0000 P:g3 is er a Put:lic Semce Electric and Gas G;\\PSEGil1385Wew UHS \\STACSUllS2.PDB. Revision 2.00

~~

Hope Creek Generating Station. STACS Heat Exchanger Data Report Convergena Prmuta=1 OE-3 Sam Q-l.0R 2 Prietional OE 6 FCV-1.0E-4 PCv=1.0E-3 Temperacyv3.0E-3 Post LOP. I and 1 SSWS ICE 130 '

HX Type: Fixed Heat Load RX Status: On / Not in Flow Path M!h Ametek%itlock Model. 4 W18HT 4-A CB Dwas. PM007-00313 System Fluid:

i Heat Load =

42,300.00 BTUh ICE 404 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfx: American Std.

Model: 17072 CPT Dwgs: PM018Q SystemFluid; Freshwater Tube Flow - 1,122.47 Tube Temperatures = 115.31'F - 117.75'F Heat Lead =

1,353,000.00 BTU /hr 1

ICE 40$

HX Type: Fixed Heat Load HX Status; On / in Flow Path Mth American Std.

Model: 19084 CPT Dwas: PM016Q i

System Fluid: Fresh Water Tube Flow = 1,119.96 Tube Temperatures = 105.57'F - 115.31Y Heat Load =

5,412,000.00 BTU /br ICE 408 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Amer:can Std.

Model: 19198 Dwgs. PM018Q System Fluid Fresh Water Tube Flow - 1,118.64

'Ibbe Temperstmes = 99.96*F 105.57'F Heat Load =

3,118,000.00BTUh ICK111 HX Type: Fixed Heat Loral HX Status: On / Notin Flow Path Mfr: Carrier Corp.

Model 19FA553B$005932 Dwas: pM623-0002 9 System Fluid:

Heat Load =

19,500,000.00 BTU /hr I

1

=

s9w c'tm~4W5^~57.'srr~Ytr T6Y:fM0T218 P.2uO1 s/ll/9810:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 Page 19 ot 26 Public Service F.lectric and Gas G:\\PSEG\\11-385\\New L'HS\\STACSUHS2.PDB - Redsion 2.00 Hope Creek Generating Station STAC$

Heat Exchanger Data Report conwgese: heuurel.0E 3 Surr Q=1.062 Fnction=1.Ch4 FCV-1 OE4 PCV-l.0E-) Terrperan:rsa5 OE4 Post LOP - 1 and 1 SSWS l

1CP176 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: Carrier Corp.

Model: 19FA999-1007-18 Dwgs: PM623-118 System Fluid:

Heat Load -

100,000.00 BW!hr j

ICP2021 HX Type: Fixed Heat Load HX Status: on / in Flow Path Mfr: Graham Mfg. Co.

Model: 8X4C 12 Dwgs: N1-E11 C002-51 System Fluit ShellFlow e 29.16 Shell Temperatures - 99.99F - 124.13*F 1 feat Lead -

350,000.00 BTU /hr ICP202-2 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mft: Graham Mfg. Co.

Model 992C430BX Dwgs: Kl E11 C002 6 System Fluid: Fresh Water Tube Flow - 10.64 Tube Temperatures - 99.96'F - 101.86'F

. Heat Load =

10,000.00 BK/hr 1CVE412 HXType: Fixed Heatload HX Status: On /in Flow Path Mft:Trane Co.

Model: MDE1291600 DwEs: PM731Q System Fluid: Fresh Water Tube Flow - 467.76 Tube Temperatures - 99.96*F 104.70*F Heat Load =

1,100,000.00 DTU/hr 1CVH113 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: Amer. Alr Fitr.

Model: H36MPACYA Dwas: PM611A-0030-4 System Fluid:

Heat Load =

302,781.00 BTU!hr e

..u.a.

a.

8/11s 8 10 19 PROTO-FLO 4.01 by Proto+ Power Corporation - Serial #PFL-0000 Pass:0 of 26 Public Service Electric and Gas - G:\\PSEGill.3 BS\\New UHSTSTACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station. STACS Heat Exchanger Data Report Convergence: P' essure-l CE.$ Sum Q-1.0E-2 Friction =1.0E4 FCV=l.0F. 4 PCV-l.0E-3 Temperaturc=5 OE 3 Post LOP. I and 1 SSWS ICVH210 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mfr: Amer. Air Fltr.

Model: MDEl570300 Dwgs: PM71IQ SystemFluid: Fresh Water Tube Flow = 129.25 Tube Temperatures = 99.96'F - 103.08aF Heat Load =

200,000.00 BW/hr ICVH211 HX Type: Fixed Heat Load HX Status: OIT Mfh Amer. Air Fitt.

Model. MDE1573500 Dwgs: PM71IQ SystemFluid: Freshwater Heat Load =

0.00 BTU /hr ICVH213 HX Type: Fixed Heat Load HX Status, off Mft: Amer. Air Fitr.

Model: MDE2478600 Dwgc PM786Q System Fluid: Fresh Water Heat Load =

0.00 BTU /hr IDE!12 HX Type: Fixed Heat Load HX S' tatus:- On / Notin Flow Path Mfr: General E1cet.

Model: tl4D8270 Dwgs: PM003-G-1 7 System Fluid:

Heat Load =

5,487,500.00 BTU /hr i

1DE404 HX Type: Fixed Heat Load HX Status. On/in Flow Path l

Mfh American Std.

Model: 17072 CPI Dwgs: PM018Q

{

System Fluid: Fresh Water l

Tube Flow = 1,096.01 Tube Temperatures 2 i15.72'F 118.22*F l

Heat Load =

1,353,000.00 BTU /hr

)

I'

\\

l l

7_

.e

.-m r;cg233 l

8/11/98 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial CPFL-0000 r

Paseal of 26 Public Service Electric and Oas 0:\\PSEO\\11-385\\New UHS \\STACSL'HS2.PDB. Revision 2.00 l

Hope Creek Generatmg Statoo - STACS Heat ExchangerData Report Cur.sergence. Preautr=1.uli-5 km Q=1. uni-2 Frieron=1.0E4 FCV=1 OE t PCV=1.0Ed Temperatwe=$.0E-3 Post LOP-1 and 1 SSWS IDE405 HX Type: Fixed Heat Load HX Status On /ivi Flow Path Mfr American Std.

Model; 19084 CPT Dwgs. PM018Q SystemFluid Freshwater Tube Flow = 1.093.40 Tube Temperatures = 105.75'F - 115.72*F Heat Lead =

5.412,000.00 BTUihr IDE408 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr:American Std.

Model: 19198 Dwgs: PM015Q System Fluid: Fresh Water Tube Flow 1,092.16 lbbe Teraperatures 100.00*F - 103.75'F Heat Load =

3,118,000.00 BTU /hr 1DK111 HX Type: Fixed Heat Load HX Stams: On/ Notin Flow Path Mt Camer Corp.

Model: 19FA553B5005932 Dwgs: PM623-0002-9 System Fluid:

Heat Lead =

19,500,000.00 BTU /hr IDP176 HX Type: Fixed Heat Load HX Status: On/ Not in Flow Path Mfr: Carrier Corp.

Model: 19FA9991007-18 Dwgs: PM623-118 System Fluid:

Heat Load =

100,000.00 BTU /hr IDP2021 HX Type: Fixed Heat Load HX 5tatus: On / in Flow Path Nft: Graham Mfg. Co.

Model: 8X4C 12 Dwgs: N1.El1.C002 51 SystemFluid: Freshwater Tube Flow = 26.73 Tube Ten:peratures = 100.00'F.126.36'F Heat Load =

330,000.00 BTU /br G

8/11/98 10:19 PROTO-FLO 4.01 by Proto-Power Corpor tion - Serial #PFL-0000 P;se 22 or 26 Public Service Electric and Gas - G:\\PSEG\\ll 385\\New UHS \\STACSUHS2.PDB - Revision 2.00 Hope Creek Generstmg Station - STACS Heat Exchanger Data Report Converg:nce: Pres are=1.0E-! Sum Q=1.0E.2 Fnction=1.0G4 FCV=t OG-4 PCV=t.06. 3 '1cmperan:re=$.0E.3 Post LOP - 1 and 1 SSWS 1DP202-2 HX Type: Fixed Heat Load IOC Sta:us: On / in Flow Path Mfh Graham Mfg. Co.

Model: 992C430BX Dwgs: N1.E11 C002 6 System Fluid: Fresh Water Tube Flow = 10.44 Tube Temperatures - 100.00*F - 101.93'F Heat Load =

10,000.00B1U/hr l

IDVE412 HX Type: Fixed Heat Lead HX Status: On /in Flow Path Mfr.Trane Co.

Modci; MDE1291600 Dwas: PM731Q j

System Fluid. Fresh Water Tube Flow - 533.59 Tube Temperatures ' 100.00*F - 104.15'F j

Heat Load -

1,100,000.00 BTU /hr j

!DvH113 HX Twe: Fixed Heat 1. cad HX Status: On / Not in Flow Path Mft: Amer. AirFitr.

Model: H36MPACYA Dwgs: PM611A 0004 7 System Fluid:

Heat Load =

502,781.00 BTU /hr l

.I 1DVH210 HX Type: Fixed Heat Load HX Status: On / in F:ow Path Mfr. Amer. Air Fitt.

Model: MDE1570300 Dwgs: PM711Q System Fluid: Fresh Water i

Tube Flow = 150.92 Tube Temperatures = 100 00*F 102.67'F j

Heat Load -

200,000.00BIU/hr i

IDVH211 HX Type: Fixed Heat Load HX Status: Off l

Mfr. Amer. Air Fitr.

Model: MDE1573500 Dwgs: PM71IQ SystemFluid Fresh Water Heat Load =

0.00 BTU /hr

,rw r.waa l

8/11/98 10:19 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 Page 23 of 26 Public Service E!cctric and One 0:\\PSEG\\11-385;New UNSWTACSUHS2.PDB Revision 2.00 Hope Creek Generatmg Station STACS Heat Exchanger Data Report Convergence: Pressm=1 USS Sum Q=1.0E-2 Friction =1.0E-6 FCv=t.0W 4 PCv=1 Oh.) Temperaxre=S.CE-3 Post LOP - I and i SSWS I

1DVH213 HX Type: Fixed Heat Load HX Status: Off Mfr Amer. Att Fit,

Model: MDE2478600 Dwgs: PM786Q

]

Sys:cm Fluid: Fresh Water Heat Load =

0 00 BTU /hr 1 EVE 412 HX Type: Fixed Heat Load IIX Status: On/ in Flow Pad Mir:Trane Co.

Model: MDE1291600 Dwgs: PM731Q SystemFiuld: Fresh Water l

Tube Flow = 543.57 Tube Temperatures = 99.96'F - 104.04T Heat Load -

1.100,000.00 BTU /hr IEVH113 HX Type: Fixed Hea: Load HX Status: On/Noch flow Path Mfr: Amer. Air Fitr.

Model: H36MPACYA Dwas: PM611A-0004-7 System mid.

Heat Load -

502,781.00SIU/hr s

1EVH210 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Amer. Air Fitr.

Model: MDE1570300 Dwgs: PM71IQ j

System mid. Fresh Water j

Tube Flow = 147.04 Tube Temperatures - 99.96'F - 102.84*F

)

Heat Load =

210,000.00 BTU /hr

)

IEVH211 HX Type: Fixed Heat Load HX Sta:us: ott Mft: Amer. Air Fitr.

Model: MDE!S73500 Dwgs: PM711Q System Fluid: Fresh Water Heat Load -

0.00 BTU /hr i

i lEVH213 liX Type: Fixed Heat Load IIX Status; otr Mft: Amer. Air F!tr Model: MDE2478600 Dwas: PM786Q System Fluid: Fresh Water Heat Load =

0.00 BTU /br i

1

)

1 i

-+

erwarW m o F 2 9, ;3 g

-l

~

8/l1/98 10:19 PROTO FLO 4.01 by Prot > Power Corporation - Serial !!PFL-0000 Pase 24 of 26 Public Service Electric and Oas - 0:\\PSEGT11-385\\New UHS'STACSL'HS2.PDB - Revision 2.00 Hope Creek Generatin5 tation - STACS S

Heat ExchartgerData Report

(%versces: theswe=1.0E-3 Sum Q-l.0E 2 Friction =1.0E 6 TCV=l.0E4 PCY=1.0E-3 TempersmM=3.DE J Post LOP - 1 and 1 SSWS -

IFVE412 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mft: Tranc Co.

Model: MDE1291600 Dwgs: PM731Q SystemFluid: Fresh Water Tbbe Flow - $37.64 hbe Tempe stures - 100.00*F - 104.12*F Heat toad -

1,100,000.00BW/hr IFVHI13 HX Type: Fixed Heat Load HX Staras: On/ Notin Flow Path Mfr:Amet. Air Fltr.

Modeh H36MPACYA Dwgs: PM6t l A-0004 7

- System Fluid:

Heat Load =

$02,781.00 DTU/hr IFVH210 HXType: Fixed Heat Load HX Status: On/in Flow Path i

Mft: Amer. Air Fitr.

Model: MDEI570300 Dwgs: PM71IQ System Fluid: Fresh Water Tube Flow = 154.97 Tube Temperatures = 100.00*F - 102.73'F

. Heat Load =

210,000.00 BTUMr 1FVH211 HX Type. Fued Heat Load HX Status: Off Mfr: Amer. Air Fltr.

Model: MDE1573500 Dwgs: PM711Q System Fluid: Fresh Water Heat Load -

0.00 BTU /hr iFVH213 HX Type: Fixed Heat Load HX Status: off Mfr: Amer Air Fltr.

Model: MDE2478600 Dwgs: PM786Q System Fluid: Fresh Water Heat Load =

0.00 BTU /hr l

l l.

T

mmsmrvmn-minrenca.1a e. sm i 8/lI/9s 10:19 PROTO-FLO 4.01 by Proto Power Corporation - Serial CPFL-0000 Pase 23 of 26 Public Service Electric and Gas 0:\\PSEO\\11-385\\New UHS \\STACSCHS2.PDB Revision 2.00

~-

Hope Creek Generating Station STACS Heat Exchanger Data Report Converpnet P1ssure=LCE-3 Sum Q=1.CE 2 FricWr=l CE4 FCV 1 OG4 PCV*l.CM Terrpersuc=5.0E-3 Post LOP I and 1 SSWS IGVE412 HXType: Fixed Heat Load HX Status' On /in Flow Path

)

Mft Trace Co.

Model: MDE1291600 Dwge: PM731Q L

System mid: Fresh Water Tube Flow = 543.08 Tubc Temperatures ' 99.96*F 104.00*F l~

Heat Load =

1,100,000.00 BTU /br 1GVH210 HX Type. Fixed Heat Load HX Staats: On / in Mow Path Mft: Amer. Air Flrr.

Model: MDE1570300 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow = 134.94 Tube Temperatures = 99.96'F - 102.93*F i

Heat Lead -

200,000.00 BTU /hr

~

- 1GVH211 HX Type: Fixed Heat Load HX Starns: Off Mfh Amer, air Fitr.

Model: MDE1573500 Dwas: PM711Q System mid: Fresh Wattr liest Load =

0.00 BTU /hr INVE412 HX Type: Fixed Heat Load HX Status: On/in Flow Path Mft: Trane Co.

Model: MDE1291600 Dwgs: PM731Q System Fluid: Fresh Water Tube Flow = 622.54 Tube Temperatures = 100.00'F 103.56T Heat Load -

1,100,000.00 BTU /hr 1HVH210 HX Type:' Fixed Heat Load HX Status: On /in Flow Path Mft: Amer. AirFiv.

Model: MDE1570300 Dwgs: PM711Q System Fluid: Fresh Weter Tube Bow = 150.79 Tube Te:nperatures = 100.00'F 102.67'F Heat Losd =

200,000.00 BTU /ht l

l' l

i.

s/t t/9810:19 PROTO-FLO 4.01 by Proto-Power Caporation - Serial #PFLo0000 p.,e u or u Public Service Electric and Oes - 0:\\PSEO\\ l 1-385\\New L11S\\STAC5 UHS 2.PDB. Revision 2.00 Hope Creek Generstmg Station - STACS Heat Exchangx Data Report cawerynce Prvine-1.05 5 5utn Q-1.0E-2 Fricaon=1.0E-6 FCV=l.0E-4 PCV=1 GE.31emperature*5.0E4 Post LOP-1 and 1 SSWS IHVH211 HXType; Fixed Heat Load HX Status: Off Mft; Amet. Air Fitr.

Model: MDE1573500 Dwgs: PM71IQ System F:uid: Fresh Water Heat Load -

0.00 BTU /hr 1

l

~

l 1

i i

I I

    • TOTAL PAGE.001

==

i i

i 1

o-es7 t;ee c =wc 7V'~TEWFTJUUT2 3 8 F.J1e27 g

PROTo-POWER CORPORATION 15 THAMES STResT PHONE: (880) 448-9726 GROTON, CT 06340 fax: (880)446-8292 FAxCovenSHEET Flue No.: I/- 36f DATE: _0['#/9 8 TOTAL PAGES (INCLUDING COVER SHEET): 17 To:

Roh

% y;g.T pggy fgu. A.s y v j

)

DEPT. __

FAX No.:

I ((c4)3 M-saiS fax No.: (880)446-8292

REFERENCE:

i MESSAGE: kb.

3dere 's Poit-Gc)CA w h *1 t a., d n S s uss nd +, sFp l: e.

m N t'e-ahed.

V W.S s

B*t.T

  • P W

To report transmittal problems or for confirmation, please call (860) 446-9725.

Ask for.

' N ~VI.'E N Td3381218 P,a2e27 s>10s9814:16 P:1,OTO-FLO 4.01 by Pr:to-P:wer Corporation Serial #PFL-0000 P: sit er 26 Public Service Electnc and Gas - G:\\PSEGi11-385Wcw UHS \\STACSUHS2.PDD - Revision 2.00 Hope Creek Ger.erating Station STACS Heat Exchanger Data Report Convergence; Pitssss=1.0E4 Surn Q=1.0F-2 Friccon=1.0E4 PCV=1.0E-4 K:Y=1.UE-3 Terrperature=5.00 3 LOCA - Fa1111 eat - 1 and 1 SSWS - SFP 00E129 RXType: Fixed Heat Load HX Status: Ori /Not in Flow Path Mft: Basco,Inc.

. Model: ES-24/18096 Dwas: PM050 0039-3 Syom Fluid:

Heat Load -

500,000 0081Uh 00K107 HX Type: Fixed Heat Load HX Status: Oc / Not in Flow Path Mfr. American Std.

Model: 06060 Dwgs: PM050-0022-5 System Fluid:

Heat Load -

2,240,323.00 BTU /hr 10C150 HX Type: Fixed Heat Load HX Status: Off Mfr:

Model:

Dwgs:

System Fluid:

Heat Load -

0.00BTUh 10E!110 HX Type: Fixed Heat Load HX Stan:s: On/ Notin Flow Path Mfr Basco,Inc.

Model. 8A24A08072 Dwas: PI-342287 System Fluid:

Hea Load-515,000.00 BTU /hr 10El14 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfr Gen. Elect Co.

Model: MDE0965400 Dwas: PM003-O-1-7 System fluid:

Heat Load -

42,300 00BTUh 10E129 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfr: Basco, Inc.

Model: ES-24/18006 Dwgs: PM050-0039-3 System Fluid:

Heat Load =

10,750.00 BTU /hr I

-]

l

i l

l

. 'a/10/9814:16 PROTO1FLO 4.01 by Proto Power Corporation - Serial #PFL-0000 Pase 2 of 26 l

Public Service Electric and Gas - 0:\\PSEO\\11 385\\New UHS \\STACSUHS2.PDB - Revision 2.00 Hope Crcck Generut:ng Station - STACS j

Heat ExchangerData Report Cor. vergence: Pressure =1.0Li-S Surc Q-l.0E-2 Frict:on=1.0E-6 FCV=1.0E4 PCV-1.00 3 Temp mm-5.0E-3 l

LOCA - Full Heat-1 and 1 SSWS - SFP 10K107 HX Type: Fixed Heat Load HX Status: On/ Notin Flow Path Mfr: American Std.

Model: 06060 Dwgs: PM050-0022-5 System Fluid-

)

Heat Load =

5,412,000.00 BTU /hr

AIEl18 HX Type: Fixed Heat Load HX Status: Off M&:DeLaval/IMO Model: MDE1328000 Dwgs: PM012 0099 System Fluid:

Heat Load =

0.00 BTU /hr l

f 1AIE201 HX Type: Shell& Tube HX Status: On / La Flow Path Mfh Graham Mfg. Co.

Model: 92-6-504 CGN Dwgs: PM069Q-0058 Tube Fluid. Braeldsh Water - 12 ppt ShellFluid: Presh Water ShellFlow = 9,743.00 Shell Teraporatures = 116.58'F - 99.74*F Tube Flow - 8,920.00 Tube Temperatures = 91.02*F 100.43'F l

Construction Type: TEMA-O 1 Shells, O Shell Passes,4 'Itbe Passes Shell Min Area = 6.2530 ft^2, Design Shell Velocity = 3.900 ft's, Shell Diameter = 92.000 Baffle Info: Spectrig = 62.000 in, Thickness = 0.000 in, Arsa = 0.000 ft^2, K = 0.000 Tubes: Din = 0.694 in. Dout = 0.750 in, Length = 42.00 ft, K = 9.50 l

Tube Pitch = 0.9375 in Tube Pitch Type =Triangulac l

5,700 ef 5,700 Tubes Active UTubes - No Effective Area = 46.295.00 D^2 Area Factor = 0.9849 Fouling = 0.0000 (inside) 0.0012 (outside)

Hoff = 0.4888 I

LMTD = 7.9062 LMTD Corrections FF = 0.7604 Fb = 1.0000 Heat Load =

81,182,802.23 BTU:br LJOverall = 291.71 BTU /hr/ft^2/'F l

1A2El18 HX Type: Fixed Heat Load HX Status: Off Mfr:DeLasal/IMO Model: MDE1328000 Dwgs. PM012-0099 l

System Fluid:

- Heat Load =

0.00 BTU /hr l

l

- w m 7n e m enrr m p,a4 m 1

' s/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 p.,a3 of26 Public Service Electric and Gas GAPSEGi11385\\New UHSiSTACSUHS2.PDB Revision 2 00 Hope Creek Gewrating Station - STACS Heat ExchangerData Report Convergenc:: Precurc=LDE-3 her: Qal.0E-2 Frie ton =1.0E-6 FCV=1.DE-4 PCV=1.0P. 3 Ternperarirc=5 0E 3 LOCA - Full Heat - 1 and 1 SSWS - SFP IA2E201 IIX Type: Shell& Tube HX Status: On /in Flow Path M&: Graham Mfg. Co.

Model: 92-6-504 CGN Dwas: PM069Q-0058 Tube Fluid: Brackish Water-12 ppt ShellFluit Fresh Water Shell Flow = 10,225.65 Shell Temperatures - I l 6.58'F - 100.24*F Tube Flow = 8,883.00 Tube Temperatures = 91.02'F 109.85'F Construction Type: TEMA-G 1 Shells, O She'1 Passes,4 Tube Passes Shell Mm Area = 6.2530 ft^2, Design Shell Velocity = 3.900 ft/s Shelj Diameter = 92.000 Banic Info: Spacing = 62.000 in, 'Ihickness - 0.000 in. Area = 0.000 ti^2, K = 0.000 Tubes: Din = 0.694 iT. Doat.= 0.750 In, length = 42.00 ft, K = 9.50 Tube Pitch = 0.9375 in Tube Pitch Type = Triangular 5,700 of 5,700 Tubes Active UTubes = No Effcetive Area = 46,205.00 ft^2 Area Factor = 0.9849

~

Fouting = 0.0000 (inside) 0.0012 (outside)

Hoff = 0.4888 LMTD = 7.9102 LMTD Corrections FF = 0.7662 Pb = 1.0000 Hcs: Load =

82,668,249.33 BTU /hr.

UOverall = 294.64 BTU /hr/ft^2FF

. lAEl109 HX Type: Fixed Heat Load HX Status: Off Mft: Dasco inc.

Model: 8A43A08048 Dwas: P1-342287 System Fluid:

Heat Load =

0.00 BTU /hr 1Ac111 HX Type: Fixed Hest Load HX Status: On/ Notin Flow Path Mfr: General Elect.

Model: 264A4803 Dwas: PM003-TR-18-5 System Fluid:

Heat Load -

515,000.00 BTU 4tr I AE!12 HX Type: Fixed Heat Lead HX Status: OniNotin Flow Path Mft: General Elect.

Model: 114D8270 Dwgs: PM003-G-1-7 System Fluid:

Heat Load =

42,300.00BTUAr e

N-NFr%TB P.OS 27 g/10/9814:16 PROTO-FLO 4.01 by Proto-Power Corporation - Serial CPFL 0000 Peso 4 of 26 Public Service Electric and Gas GAPSEG\\ll-385\\New 1.ES\\STACSUMS2.PDB - Revision 2.00 Hope Creek Generating Station - STACS Heat Exchanger Data Report Conmgewe:Preuuns=1 CE.5 Sum Q=:.0C.: Fricion-1 CE-6 FCV=1.CE4 PCV-1.0E-3 Temmaraturs=$ 0E.3 LOCA-Full Heat 1 and 1 SSWS SFP 1 AEl15 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfr: HL Porter Co.

Model: T 140963X45 Dwgs: PE005 0012 9 System Fluid:

Heat Load =

10,750.00 DTL*/hr 1 AEl16 HX Type: Fixed Hea: Load HX Status: On/ Not in Flow Path Mfr: General E!ect.

Model: 155B8243P001 Dwgs: PM003-T6-12 System Fluid:

Heat Load =

5,412.000.00 BTU /hr I AE117 HX Type: Fixed Heat Load HX Status: off Mfr: General Elect.

Modch MDE0924300 ogs: PM003 C-1-7 System Fluid:

Heat Load =

0.00 BTt.%r l

1AEl26 HX Type: Fixed Heat Load HX Status: Off Mft: American Sti Model: 5 046 17 168-3 Dwgs: N1-831-St-120 System Fluid:

Heat Load '

O.00 BTU /hr 1AE130 ILX Type Fixed Heat Lead HX Status: off Mfr AmetelvWinitlock Model: 4 Wl8HT-4-A-CD Dwgs: PM007-00313 System Fluid:

Mcar Load -

0.00 BTUhr 1 AE202 HX Type: Fixed Heat Load HX Status: Off Mft: Alfa LavalIr.c.

Modeh A-20-BXS Owgs: PM071Q-0010 Systsm Fluid: Fresh Water Hest Lead =

0 00 BTU /hr i

we oem CWT 4PJW~BY#%- YO 8608)3091216 P,06<27 1

i 8/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 pas. 5 of 26 Public Service Electric and Gas - G:\\PSEG\\11385\\New IJHS\\STACSUHS2.PDB Revision 2.00

~

Hope Creek Generating Station - STACS Heat Exchanger Data Report Cunvgmcc: Pressare-l.02 3 Sum @l.0E-2 Fnctior!.0E4 FCv=1.0E-4 PCV-l.0E.3 Tempers ure=$.cE-3 LOCA FullHeat 1 and 1 SSWS -SFP 1AE205 HX Type: ShcIl& Tube HX StattN On / in Mow Path Mfr: Deha Southern Model: 21 A9227AN Dwp: NO-El1-B001 5 Tube Fluid: Fresh Water ShellFluid: Fresh Water Shell Flow = 10,000.00 Shell Temperatures = 212.00*F - !86.09'F Tube Finw = 9,451.42 Tube Temperatures = 100.00*F - 126.61*F Construction Type; TEMA.E 1 Shells, O Shell Passes,2 Tube Passes Shell Min Area = 5.0880 fl^2, Design Shell Velocity = 4.200 ft/s Shell Diameter = 0.000 Baffle Info: Spacing = 0.000 in. Thickness = 0.000 in. Area = 0.000 ft^2, K

  • 0.000 Tubes: Din = 0.932 in, Dout = 1.000 in, Length = 33.94 ft, K = 9.40 Tube Pitch = 1.3750 in Tube Pitch Type = Triangular 430 of 430 Tubes Active UTubes a Yes E#ective Area = 3,740.00 ft^2 Area factor = 0.9789

-~

Fouling = 0.0005 (inside) 0.0005 (outside)

HotY= 0.7815 LMTD = 85.7356 LMID Corrections FF = 0.9842 Pb = 1.0000 Heat Load =

124,912.953.83 BITJ/hr UOverall = 395.81 BTU /br/ft^2/'F i

1 AE214 HX Type: Find Heat Load IIX Status: on / Notin Flow Path Mfr: CV1Inc.

Model: C735-9934 Dwas: PM048Q-0071-4 Systern Fluid:

Heat Load = -

19,500,000.00 BTU /hr lAE218 HX Type: Fixed Heat Load HX Stams: og Mfr:CVI1nc.

Model: C735 9934 Dwgs: PM048Q-0071-4 System Fluid:

Heat Load =

- 0.00 B'I11/hr IAE278 HX Type: Fixed Heat Load H X Status: og Mt'r: CV11ac.

Model:

Dwgs: PM048Q System Fluid:

Heat Load =

0.00 BTU /br l

l 1.

eNST.C v TL:RS S J 4 8 8 c. lfd F, @) 7 / 2 7 8/10/98 14:16 PROTO-FLO 4.01 by Proto. Power Corport in - Serial #PFL-0000 case 6 er 26 Public Service Electric and Gas - G:\\PSEGil1385\\New CHSWTACSUHS2.PDB Revision 2.00

~

Hope Creek Generating Station STACS Heat Exchanger DataReport Convergence: Wewurt-1.0E.$ Sum Qat.CE.2 Fnceon=t LE4 FCV-1.00-4 PCV-1.0E 3 Temperseve=5.oE-3 LOCA - Full Heat-1 and 1 SSWS - STP l AE328 HXType: Fixed Heat Load HX Status: On/ inflow Pa:h Mft: Parker.Hanison Model: HDTC-SS 6 2 Dwgs:

System Fluid:

Shell Flow = 5.03 Shell Temperatures = 100.00'F 122.00*F Heat Load =

55,000.00 BTU /hr 1 AE404 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mft:American Std.

Model: 17072 CPT Dwas: PM018Q System Fluid: Fresh Water Tube Flow = 1,080.46 Tube Temperatures = 115.95T - Il8.48aF Heat Load =

1,353,000 00 BTU /hr IAE405 HX Type: Jixed Heat Load HX Status; On / In Flow Path Mfr: Americans:d.

Model: 19084 CFT _

Dwgs: PM018Q SystemFluid; Freshwater Tube Flow = 1,077.94 Tube Temperatures - 105.83'F. Il5.95'F i

Hast Load =

5,'412,000.00 BTU /hr lAE40s HX Type: Fixed Heat Los HX Status: On /in Flow Path Mft: Amencan Std.

Model: 19198 Dwgs: PM018Q

)

System Fluid: Fresh Water Tube Flow = 1.076.6i Tube Temperatures = 100.00*F - 105.63*F Heat Load -

3,118,000.00 BTU /hr 1AX111 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfr: Carrier Corp.

Model: 19FA553B5005932 Dwgs. PM623-0002-9 System Fluid:

Heat Load -

502,781.00 BTUilu i

l l

'-WN-N 12 3 S F.08/27 o

8/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation S2 rial #PFL-0000 Pase 7 or as Public Service Electric and Gas. O:\\PSEO\\t 1 385Wew UNS\\STACSUliS2.PDB - Revision 2.00

~~

Hope Creek Generating Station STACS Heat Exchanger Data Report Converaence 1%swl OE 3 Sam Q-105 2 Fnction=1.CE 6 FCv=1 CE-4 PCV=1.0E 3 Terriperature=5 00,-3 l

LOCA. Full Heat - I and 1 SSWS - SFP 1AK202 HX Type. Fixed Heat Load HX Status: On / in Flow Path Mft: CV1Inc.

Model: C735-9909 Dwas: PM048Q-0044-2 System Fluid: Fresh Water l

Tube Flow = 6.15 Tube Temperatures = 100.00*F - 116.38'F Heat Load =

50,000.00BBJ/hr 1AK400 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Carrier Corp.

Model: 19fA45$B122022 Dwgs: PM723Q SystemFluid: Fresh Water Tube Flow = 2.086.04 Tube Temperatures = 100.00 F - 107.27'F

. Heat Load =

7,530,700.00 BTU /hr l

lAK403 HX Type: Fixed Heat Load HX Staats: On /in Flow Pai Mft: Carrier Corp.

Model: 19FA44181142020 Dwgs: PM723Q System Fluid: Fresh Water Tube Flow = 568.41 nbe Ternperatures = 100.00*F - 108.91"F Heet Load =

2,515,340.00 BBJ/hr 1

t AP t 76 HX Type Fixed Heat Load HX Status: On/ Notin Flow Path Mft: Camer Corp.

Model: 19FA999100718 Dwgs: PM623-Il8 System Flutd.

l Heat Losd "

100,000.00 BBJihr l

1 AP2021 HX Type: Fixed Heat Lead HX Status: On iin Flow Path Mfr: Graham Mfg Co.

Model; 8X4C-12 Dwgs: N1 Ell-C002 51 System Fluid: Fresh Weter Tube Flow = 23.15 Tube Temperatures

  • 100.00*F 107.83aF Heat Load =

90.000.00 BTU /hr l

t e

g i.

e e

8/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation = Serial CPFL-0000 rase s of 26 Public Service Electrie and Oas G:\\PSEGill 385\\New UHS \\STACSL'HS2.PDB - Revnion 2.00

~~

Hope Creek Generating Station STACS Heat Exchanger Data Report Convt.gence:Prewe=t 02 5 Surn Q=LDE-2 Prkcon=1.X-6 FCV=1.eE4 PCV=l.02 3 Terryerstutt=$.0E 3 LOCA Full Heat-I and 1 SSWS - SFP 1AP202 2 HX Type: Fixed Heat Load IIX Status: On!in Flow Path Mfr: Orab6m Mfg. Co.

Model: 992C430BX Dwas: N1.El1 C002 6 System Fluid Fresh Water Tube Flow r 9.86 Tube Temperamtes = 100.00'F 103.05'F Heat Load =

10,000.00BTUAir LAVE 412 HX Type: Fixed Heat Load HX Stan:s: On / in Flow Path Mfr:Trane Co.

Model: MDE1291600 Dwgs: PM731Q System Flaid; Fresh Water Tube Flow - 450 25 Tube Temperstures = 100.00*F - 1%92*F Heat Lead =

1,100,000.00 BTU,tr 1 AVHil3 HX Type: Fixed Heat Lead HX Status: On / Not in Flow Path M.4: Amer AirFicr.

Model: H36MPACYA Dwas: PM611 A-0030-4 System Fluid:

Heat Load =

502,781.00 B'IUhr I AVH116 HX Type: Fixed Heat Load HX Status: On /Not in Flow Pai M&: Amer. Air Fltr.

Model: H36MPACYA Dwgs: PM61lA 0033 4 System Fluid:

Heat Load =

$30,000.00 BTU /br 1AVH208 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mfr: Amer. Air Fitt.

Model: MDE1572400 Dwgs: PM711Q SystemFluid Freshwater Tube Flow -' 32.11 Tube Temperatures = 99.75'F - 102.56'F Heat Load -

44,789 00 BTU,hr e

o

r. su.c.

8/10,98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation - Serial CPFL-0000 Page 9 of 26 l

Public Service Electne and Gas - G.\\PSEG\\11385'.New UHS'STACSUHS2.PDB - Revision 2 00 Hope Creek Ge:nerating Station - STACS Heat Exchanger Data Report Conwr;;erwe: Pressure =1 OE 3 Surn Q=1.0C-2 frictiurr-1.0E 4 FCV=1.0E-4 Ptv=1.0E-J Tamparatare-5.0C.)

LOCA - Full Heat 1 and 1 SSWS - SFP 1AVH209 HX Type: Fixed Heat trad HX Status: on / in Flow Path Mft: Amer. AirFitr.

Model: MDE1571400 DwEs: PM71LQ j

System Fluid: Fresh Water Tube Flow = 77.09 Tube Ter.iperatures - 100.00 4 - 102.80 9 i

Heat Load =

107,139 00 B7Uhr i

I AVH210 HX Type: Fixed Heat Load HX Status: On / iri Flow Path 1

Mh: Amer. A2 Fitt.

Modct: MDE1570300 Dwas. PM711Q I

SystemFluid: Fresh Water Tube Flow - 141.97 Tube Temperaturcs = 100.00*F - 103.004 i

Heat Load =

211,655.00 BTU /hr I AVH211 HX Type: Fixed Heat Load HX Satus: On / in Flow Path Mft: Amer. AirFitr.

Model. MDEl573500 Dwgs: PM71IQ I

SystemFluid: Freshwater Tube Flow - 11 L26 Tube Temperatures = 100.004 102.51'F Heat Load =

138,696.00 B7U4r 1AVH213 HX Type. Fixed Heat Lead HX Status: On / in Flow Path Mft: Amer. Air Fit:.

Model: MDE2478600 Dwgs: PM786Q System Flutd: Fresh Water Tube Flow - 417.33 Tube Temperatures 100.007 - 104.65'F Heat Load =

963,311.00 BTUar LBlEl18 HX Type: Fixed Heat Load HX Status: Ori/ Notin Flow Path Mfr:DeLaval/IMO Model: MDE1328000 Dwgs: PM012 0099 i

System Fluid:

Heat Load =

400,000,00 BTUlbr s

e. a v :.,

8/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation - Serial (lPFL-0000 Pes.10 or 26 Public Service Electric and Gas G:\\PSEGil1385\\New UHSWTACSUHS2.PDB. Revision 2.00 l

Hope Creek Gerarating Station - STACS l

Heat Exchanger Data Report Conve goce PNssureal oE-3 $un Q=L0E. 2 Fncnort.0E 6 FCV-1.cE 4 PCV-1.0E.3 Tempersture-3 0E.3 LOCA - Full Heat I and 1 SSWS - SFP 1BlE201 HXType: Shell & Tube HX Status: On / in Flow Path

- Mfr: Graham.\\ifg. Co.

Model: 92-6 504 CON Dwgs: PM069Q.0058 Tube Fluid: B:ackish Water-12 ppt ShellFluid: Fresh Water l

Shell Flow - 9,610.81 Sben Temperatures = 116.58'F 99.60*F Tube Flow = 8,932.00 Tube Temperatures = 91.02'F - 109.32*F Construction Type: TEMA G

[

t Shells, O Shc11 Passes,4 Tube Passes Shell Min Arca = 6.2330 ft^2, Design Shell Velocity = 3.900 ft/s, Shell Diameter = 92.000 Baffle info: Spacing = 62.000 in 'Ibickness e 0.000 in, Area = 0.000 ft^2, K = 0.000 Tubes: Din = 0 694 in, Dout = 0.750 in, Length = 42.00 ft, K = 9.50 Tube Pitch = 0.9375 in Tube Pitch Type = Triangular 5,700 of 5,700 Tubes Active UTubes = No Eff'ective Area -= 46,295.00 ft*2 Area Factor = 0.9849 Fouling = 0.0000 (inside) 0.0012 (outside)

Hoff = 0.4888 LMTD = 7.9065 LMTD Correctons FF = 0.7587 Pb = 1.0000 Heat Load =

80,782,613.63 BTU.tr UOverall e 290.88 BTU /hr/ft^2/*F IB2E118 HX Type: Fixed Heat Loud HX'Statos: On / Notin Flow Path Mir: DeLavst/IMO Model: MDE1328000 Dwgs: PM012 0099 l

System Fluid:

Hest Load =

400,000.00 BTU /hr l

l 4

e t

l l

weruwr wcyrnrs ie m :z!6 P,t2 27 8/10/98 14:16 PROTO FLO 4.01 by Proto Power Corporation - Serial #PFL-0000 Pm n or a Public Service Electne and Gas - GAPSEG111 385\\New LMS'STACSUMS2.PDB - Revision 2.00 Hope Creek Generating Station STACS Heat ExchangerData Report Caoserym.e:!wssurt-1.065 Sum Q=1.062 Fricton=1.0E4 FCV=1 CE 4 PCVeL.C3 ) Terrserature-5 OD3 i

1.OCA - Full Heat - 1 and 1 SSWS SFP I

1B2E201 HX Type: Shell& Tube HX Status: On / hi Flow Path l

Mir: Ornham Mfg. Co.

Model. 92-6-504 CON Dwgs: PM069Q 0058 Tube F uld. Brackish Water 12 ppt ShellFkid: Fresh Water Shell Flow = 9,952.43 Shell Temperatures = 116 58'F - 99.87'F Tube Flow = 9,007.00 Tabe Temperatures = 91.02'F-109.51*F Construction Type: TEMA-G 1 Shella, O ShcIl Passes,4 Tube Passes Shc11 Min Area = 6.2530 fl^2, Design Shell velocity = 3.900 ft/s, Shell Diameter = 92.000 l

i Baffle Info: Spacing = 62.000 in Thickness = 0.000 in. Area = 0.000 ft^2, K = 0.000 I

Tubes: Din e 0.694 in, Deut = 0.750 in, Length = 42.00 ft, K = 9.50 l

Tube Pitch - 0.9375 in Tube Pitch Type = Triangular 5,700 cIS,700 Tubes Active UTubes = No I

Effective Area = 46,295.00 ft^2 Area Factor = 0.9849

~~

j Fouling = 0.0000 (inside) 0.0012 (outside)

Hoff = 0.4888 LMTD = 7.9304 LMTD Correctfons W = 0.7638 Fo=1.0000 I

Heat toad -

82,3:0,602.19 B1U/hr UOverall = 293.58 BTU /hr/ft^2MF i

18E1M9 HXType: Fhed Heat Load HX Status: On/ Notin Flow Path I

Mft: Basco ln:.

Model: 8A44A08048 Dwgs: P1-342287 System Fluid.

Heat Load =

481,650.00 BTU /hr 1Bb!!1 HX Type: Fixed Heat Load IIX Stams: On / Notin Flow Path Mfr: General Elect.

Model: 264A4808 Dwgs! PM003-TR 18 5 System Fluid:

Heat Load =

9,360,000.00 BTUtr LBEll2 WX Tsc: Fixed Heat Load HX Status: on / Not in Flow Path Mfr. General Elect.

Model: 114DS270 Dwgs: PM003 0-1-7 System Fluid:

Heat Load =

5,487,500.00 B'lTJ/hr l

l.

1 l

m my I

l 8/10ms 14:16 PROTO FLO 4.01 by Prot > Power Corporati:n - Seri:1 CPFL-0000 n ec12 or u i

Public Service Electric and Osa G.\\PSEG\\11 385\\New UHS \\STACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station - STACS

=

Heat Exchanger Data Report Coescrgence. Pressurc=1.0E-5 Sum Q=1.0h-2 FrwtwI.0E 6 FCV=1.0E4 PCV=1 OE4 Termeraturc=3 DE-3 LOCA - Full Heat. I and 1 SSWS. SFP i

1 IBEl15 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path l

Mfr: H.K. Porter Co.

Model: T.140963X45 Dwgs: PE005-0012 9 System Fluid; Heat Load =

515,000.00 BTU.

1 bet 16 HX T>pe: Ftxed Heat Load HX Status: On / Notin Flow Path l

l Mft: General Elect.

Model: 155B8243P001 Dwgs: PM003 T61-2 l

System Fluid:

Heat Load -

42,500.00 BW/hr IDEl17 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mft: General Elect, Model: MDE0924300 Dwgs: PM003-0-1-7 System Fluid.

Heat Load =

8,050,000.00 BW/hr 1BE126 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfr: Arnetican Std.

Model: 5 0046-17-168-3 Dwgs: N1.B31 St-120 System Fluid:

Heat Load -

5,630,000.00 DW/hr 1BE130 HX Type: Fixed Heat Load HX 5tatus: On / Not m flow Path Mft: Ametek/Whitlock Model: 4-Wl8HT.4 A-CB Dwgs: PM007 0031-3 System Fluid:

Heat Load =

42,300.00 BTU,br IBC202 HX Type: Fixed Heat Load 11X Status: off Mir. Alfa-Lavallac.

Model: A-20 BXS Dwgs. PM071Q-0310 System Fluid; Fresh Water Heat Lead -

0.00 BWehr I

I i

j N t N N OTEYE p,Iae27 l

3/10,98 14:16 PROTO FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 c:sc 13 of 26 l

Public Service Electric and Gas 0:\\PSEGit 1-385;New tHIS\\STACSUHS2.PDB Revision 2.00 l

Hope Crcck Generating Station STACS Heat Exchanger Data Report

(*onvergence. tiwure=1.0R-5 Sum Q-1.CE.2 FdetW=1.0E4 FCV=l CE-t (Wal CE 1 Terrperature=$.0E.1 LOCA - Fu!1 Heat I and 1 SSWS - SFP l

IBE205 HX Type: Shell& Tube HX Status: Ou / m Flow Path Mfr: Delta Southern Model: 21 A9227AN Dwgs: NO Ell-8001-5 Tube Fluid: Fresh Water ShellFluil Fresh Water

- Shell Flow w 10,000.00 Shell Temperatures = 212.00'F - I 86.20*F Tube Flow = 9.186.44 Tube Temperatures = 99.7S'F - 127.0 l'F Construction Twc: TEMA E I Shells, O Shell Passes. 2 Tube Passes ShellMin Area = 5.0850 8^2, Design Steli velocity = 4.200 n's, Shell Diameter = 0.000 Baffe Lafo: Spacing = 0.000 m, Thickness = 0.000 irt, Area = 0.000 A^2, K = 0.000 Tubes: Din = 0.902 in Dout = 1.000 in, Length = 33.94 8 K = 9.40 Tube Pitch = 1.3750 in

'nibe Pitch Type -Triangular 430 of 430 Tubes Active UTubes = Yes Effective Area = 3,740.00 ft'2 Area Factor = 0.9789 Fouling = 0.0003 (Inside) 0.0005 (outside)

Hoff= 0.7815 LMTD = 83.7194 LMTD Corrections FF = 0.9839 Fb = 1.0000 Heat Load =

124,395,430.67 DTU/hr UOverall = 394.35 BTU /hr/R^2/*F IBE214 HX Type: Fixed Heat Load IlX Sta:us: On / Notin Flow Puh Mh CVIinc.

Model: C735 9934 Dwas: PM048Q 00714 System Fluid.

Heat Load =

9,565 00 B'IU/hr IBE215 HX Type: FixedHeat Load HX Sta:us: On / Notis Flow Path Mfr CVIlac.

Model: C735 9934 Dwgs: PM048Q-00714 System Fluid:

Heat Load =

10,750.00 B1U/br IBE278 HX Type: Fixed Heat Load HX Status: On / b*ot in Flow Path M&iCVI Inc.

Model:

Dwgs: PV045Q System Fluid:

Heat Load =

6,000.00 BTU /hr t

(

--vt.

p,ig,27 l

l" s/lo/9814::6 PROTO-FLO 4.01 by Proto Power Corporation - Serial #PFL-0000

&se i4 or 26 Public Service Electric and Oss - OAPSEGill 385\\New UHS \\STACSUHS2 PDB = Revision 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report Convergec,ee Pmsve=1.0E 3 hrn Q-l.0E.2 Fnctional.0E4 FCv=1.0E 4 PCV-10E4 Tc'npertane=5.0E-3 LOCA-Full Heat 1 and 1 SSWS. SFP IBE328 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr Parker-Hanison Model: HDTC-SS-6 2 Dwgs:

System Fluid:

ShellFlow 5.86 Shell Tempersturcs = 100.00*F - 118.90*F

~l Heat Load -

55,000.00 BTU /hr l

1BE404 HX T)pe: Fixed Heat Load HX Status: On/in Flow Path Mft: American 5td.

Model: 17072 CPT Dw5s: PM018Q System Fluid: Fresh Water Tube Flow = 1,074.72 Tube Temperatures = 115.78'F 118.33'F Heat Load -

1.333,000.00 BTU /hr 18E405 HXType: Fixed Heat Load EX Status: On / in Flow Path Mfr: American Std.

Model: 19064 CPT Dwgs: PM018Q System Fluid. Fresh Watu Tube Flow = 1,072 20 Tube Ternperatures = 105.61*F - 115.78'F Heat Load =

5,412,000.00 BTU /hr IBE408 HX Type: Fixed Heat Toad HX Status: On /in Flow Path Mft: American S!d.

Modd: 19198 Dwas: PM018Q System Flutd: fresh Water Tube Fiow = 1,070.87 Tube Temperatures = 99.75'F.105.61'F Heat Load -

3,i18.000.00 BTU /hr IBKi11 HX Type: Fixed Heat Load HX Statos: On / Not in Flow Path Mfr Carrier Corp Model. 19FA353B5005932 Dwas: PM623-0002-9 Sys:em Fluid:

Heat Load

19,500,000.00 BTU /hr i

- - - - - - - ^

-.w@vsf3TrTe P Is zy s/10/98 14:16 PROTO FLO 4.01 by Proto Power Ccrporation - Seri:1 t!PFL-0000 rup is or a Public Service Electric and Gas - GAPSEG\\11 385\\New UHS \\STACSUHS2.PDB. Revision 2.00 Hope Creek Generanng Station STACS Heat Exchanger Data Report Conserpet: Pressel.CE-$ sum Q=1.0E 2 Frictional.0E4 FCY=1 CE.4 PCV=1.0P 3 Tegera: urea $.0E 3 LOCA-FullHeat 1 and 1 SSWS SFP 1BK202 HX Type: Fixed lleatload HX Status: On / in Flow Path Mfr:CVllac.

Model: C735-9909 Dwas: PM048Q 0044-2 Systern Fluid: Fresh Water Tube Flow a 5.92 Tube Tensperatures - 99.75'F - 116.75'F Heat Load =

50,000 00 BTtJ/hr 1BK400 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mft: Carrier Corp.

Model: 19FA455B122022 Dwgs: PM723Q System Fluid, fresh Water Tube Flow a 1.839.79 Tube Temperanirea = 99.75'F 107.99'F Heat Load =

7,$30,700 00 BTL'/hr IBK403 HX Type: Fixed Heat Load HX Status: On/in flow Path Mfr. Carrier Corp.

Model. 19FA44tBil42020 Dwgs: PM723Q System Fluid: Fresh Water Tube Flow = $79.77 Tube Temperatures = 99.75'F - 108.48"F Heat Load =

2,515,340.00 BTU /hr lBPl76 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfr. Carrier Corp.

Model: 19FA999100718 Dwas: PM623-118 System Fluid:

Heat Load =

100,000 00Bn!/hr iBP2021 HX Type: Fixed Heat Load HX Status: 00 !in Flow Path M& Graham Mfg. Co.

Model. 8X4C 12 Dwgs: NL-El1-C002 51 System Fluid: Fresh Water Tube Flow = 23 31 Tube Temperatures = 99.75'F 106.15*F Heat Load =

90,000.00 BRJ.t.r I

rarr7n

?

l

\\

8/10/98 14:16 PROTO-FLO 4.01 by Prao-Power Corporatian - Scrial CPFL-0000 Pasa u or u l

Public Service Electric and Gas. G:\\PSEOt t 1 385\\New UHSsSTACSUHS2.PDB - Revision 2.00 Hope Creek Generating Statior.. STACS Heat Exchanger Data Report Cwe Sence: Preuure-I%5 Sum Q=1 CE4 Frictional.oE4 FCV-1.0E 4 PCV=1.uti.3 'rernperaturc=iOF.-1 LOCA - Full Heat-I and 1 SSWS. Sff IBP202-2 HX Type: Fixed Heat Load liX Staras: On/in Flow Path Mft: Graham Mfg. Co Modch 992C430BX Dwas: N1. Ell.C002-6 System Fluid: Fresh Water Tube Flow = 10.14 Tube Temperatures = 99.75'F - 101.73*F l

Heat Load =

10,000.00 BTU /hr IBVE4:2 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mft:Trane Co Model: MDE1291600 Dwgs: PM731Q System Fluid: Fresh Water Tube Flow - 524.07 Tube Temperatures = 99.75'F - 103.97'F Heatload =

1,100,000.00 BTU /hr IBYHil3 HX Type: Fixed Hea: Load HX Status: Ofr

~

Mfr: Amer. Air Fitt.

Model: H36MPACYA Dwgs: PM611A-0030-4 Synem Fluid:

Heat Load =

0.00 BTUhr 1BVH116 HX Type: Fixed Heat Load HX Status: On / No in Flow Path Mft: Amer. Art Fitr.

Model: H36MPACYA Dwgs: PM611A-0033 4 System Fluid:

Heat Load =

530,000.00B'IUhr IBVH208 HX Type: Fixed Heat Load HX Status: On Iin Flow Path Mft: Arner. Air Fitt.

Model: MDE1572400 Dwgs: PM711Q System Fluid. Fresh Water Tube Flow = 31.63 Tube Temperatures = 99.75'F - 102.60'F Heat Load =

44,789.00 BTUihr r

m 8/10c9814:16 PROTO4FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 p1ge 17 of 26 l

l Public Service Electric and Oas. G:\\PSEGT11-385\\New UNS\\STACSUHS2.PDB - Revision 2.00 Hope Creek Ocnerating Station. STACS

~

l Heat Exchanger Data Report l

Comer 1p: rec: Prence-1.CE-3 Sum Q-1.0D2 Fricten=1.0E-6 FCV-1.0E-4 PCV=t OC.) Temperanae=5 08 3 LOCA = Full Heat. I and 1 SSWS - SFP IDVH209 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Amer. Air Fict.

Model: MDE1571400 Dwgs: PM71IQ System Fluid: Fresh Water l

Tube Flow - 105.06 Tube Temperatures = 100.00*F - 102 06'F Heat Load -

107,139 00 BE/hr 1BV!;110 HXType Fixed Heat Load HX Status: Oo /in Flow Path Mfr: Amer. Air Fitr.

Model: MDE1570300 Dwgs: PM711Q System Fluid: Fr: sh Water Tube Flow - 148.25 Tube Tempe:a:ures = 99.75'F - 102.62*F Heat Load -

211,655.00 BTU /hr 1BVH211 HX Type: Fixed Heat Load HX Status: Ou /in Flow Path Mft: Amer. Air fler.

Modeh MDE1573500 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow 111.56 Tube Temperatures e 99.75'F.102.25*F Heat Load =

138,696.00 DTU/hr 1BYH213 RX Type: Fixed Heat Load HX Status: On / in Flow Pada Mft: Amer. Air F1tr.

Model: MDE2478600 Dwas: PM780Q System Fluid: Fresh Water Tube Flow - 423.00 Tube Temperatures - 99.75'F - 104.33'F Heat Load =

963,311.00 BTUtlar ICIE118 HX Type. Ftxed Heat Load HX Status: On / Notin Flow Path Mft: DeLaval/IMO Model: MDE1328000 Dwgs: PMO12-0099 System Fluid:

Heat Load =

400,000.00 BW/hr

{

l

mcc 8/10/98 14:1e PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 P sils or 26 Public Service Electric and Gas - G:\\PSEGill-385'New U11S'STACSUHS2.PDD - Revision 2.00 Hope Creek Generating Station - STACS Heat Exchanger Data Report Convwgerics: Preswre=1 CE 3 Sum Q=1.0E 2 Fricton=1.0C-4 FCV-1 A4 PCVel.0E 3 Temperature =5 OE 3 LOCA FullHeat-1 and 1 SSWS - SFP 1C2El18 IIX Type: Fixed Heatload HX Status: On / Notin Flow Path l

l Mfr DeLaval/IMO Model: MDE1328000 Dwgs: PM012-0099 l

System F'uid:

Heat Load =

400,000.00 BTutt tCEII2 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mft: General Elect.

Model: 114D8270 Dwgs: PM003-0 1-7 System Fluid.

Heat Load =

5,487,500.00 BW/hr

!CE130 HX Type. Fixad Heat Load HX Status: On / Notin Flow Path M &:Ametek/Whitlock Model; 4-W18HT-4-A-CB Dwas: PM007-0031-3 i

System Fluid:

Heat Load =

42,300.00 BTU /hr i

1CE404 HXType: Fixed Heat Load HX Status: On / in &w Path Mft: American Std.

Model: 17072 CPT Dwas: PM018Q System Fluid: Fresh Water Tube Flow = 1,089.46 Tube Temperaaares = 115.82'F - 118.33'F Heat Load =

1,353,000.00BW/hr 1CE405 HX Type: Fixed Heat Load HX Status. On /in Flow Path Mft: Arnetican Std.

Model: 19084 CFF Dwgs: PM018Q

~,.

SystemFluid: Freshwater Tube Flow - 1,086.96 Tube Temperatures - 105.787. I15.82'F Heat Load -

5,412,000.00 BW/hr l

uw.=se a gizy 8/10,vs 14;16 PROTO FLO 4.01 by Proto-Power Corporation - Serial (IPFL-0000 r:s> to or 26 I

Fublic Service Electne and Gas - G:\\PSEG\\11 385\\New UHS \\STACSUHS2.PDB - Revision 2.00 1

Hope Creek Generarms Station-STACS l

Heat Exchanger Data Report i

Convergence: Prmsure al.0E-5 sum Q=LCS2 Frienen=1.oS6 FCVal.0E.4 Pcv=1.024 Terrpcare-tow 1.OCA Full Heat - I and i SSWS - SFP I

l 1CE408 HX Type: Fixed Heat Load HX Sta:us: On /In Flow Path Mh: American Std Model: 19198 Dwgs: PM018Q l

SystemFluid: Fresh Water l

Tube Flow - 1,055.63 Tube Temperatures - 100.00'F - 105.78T Heat Load =

. 3,i18.000.00 BTU /hr 1CK!1L MX Type: Fixed Heat Load HX Status: On/ Not in Flow Path Mfr: Carrier Corp.

Modeh 19FA553B5005932 Dwgs: PM623-0002-9 System Fluid:

Heat Load >

19,500,000.00 BTU /nr ICP!76 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path

~

Mft: Carrier Corp.

Model: 19FA999-1001-18 Dwgs: PM623118 j

System Fluid:

Heatload -

100,000.00 BTU!hr I

1CP2021 HX Type: Flxed Heat Load HX'5tatus: Oc /in Flow Path Mh: Graham Mfg. Co.

Model: 8X4C-12 Dwgs: N1. Ell-C002 Sl System Fluid:

Shell Flow 4 28.29 Shell Tempemtures = 100.00*F.106.41'F Heat Load =

90,000.00 BIU/hr I

1CP202 2 HXType: Fixed Heat Load '

HX Status: On /in Flow Path Mft: Graham Mfg. Co.

Mcdel: 992C430BX Dwgs: N1.El1 C002-6 SystemFluid: Fresh Water i

Tube Flow - 10.32 Tube Temperaturea = 100.00T - 101.95*F Heat Lead =

10,000.00 BTU /hr 1

L 1

5

N'2'arr YTTbv6 p'. 21 / 2 7 j

8/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation - Scrist (!PFL 0000 Pase 20 of 26 Public Service Electric and Gas - 0:\\PSEG\\11 385\\New UHSiSTACSUHS2.PDB - Revision 2.00 l

Hope Creek Generating Station STACS Heat ExchangerData Report Cnmergence' Preamel.05 3 $wn Q=1DE.2 Frtetunal.0E 6 FCV=1.08-4 PCV=l.0F-3 rempera utee$.0E-3 LOCA - Full Heat - 1 and 1 SSWS - SFP 1CVE412 HX Type: Fixed Heat Lead HX Status: On / in Flow Path l

Mft:Trane Co.

Model. MDE1291600 Dwgs: PM73IQ System Fluid: Fresh Water Tube Flow = 453.99 Tube Ternperatures = 100.00'F 104,88'F Heat Load =

1,100,000.00 BTU /hr ICVH113 HX Type: Fixed Heat Load HX Status: On / Not in Flow Path Mfn Amer. Air Fitr.

Model: H36MPACYA Dwgs: PM611A-0030-4 System Fluid:

- HeatLoad =

502,781.00 BTU /hr ICVH210 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mft: Amer. Air Fltr.

Modet MDE1570300 Dwas: PM711Q System Fluid: Fresh Water Tube Flow = 125.44 Tube Temperatures = 100.00'F.103.23*F HeatLoad-200,957.00 BTU,hr ICVH211 HX Type: Fixed Heat Load HX Star.as: On / in Flow Path Mft: Amer. Air Fitr.

Model: MDE1573500 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow = 111.78 Tr.be Temperatures - LOO.00*F - 102.50*F Heat Load =

138,696.00 BTU /hr ICVH213 HX Type: FixedHeat Load HX Statur On / in Flow Pa*1 Mfr. Amer. Ai Fl!r.

Modeh MDE2478600 Dwgs: PM786Q System Fluid. Fresh Water Tube Flow - 412.00 Tube Temperatures = 100.00'F - 104.71*F Heat Lead =

963,311.00 BTU /br t

e

.-a ma..a,

- 8/10/9814:t6 PROTO FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 resc 21 or 26 Public Sers ice Elec ric and Oss. 0;\\PSEGil 1 385\\New UHS'STACSUllS2.PDB. Revision 2.00 Hope Creek Generating Station STACS

~

Heat Exchanger Data Report Comergewe. Prenae=10E4 km Q=1.0E 2 FncJen=1.00 6 FCV*l.CFA PCV-1.0E4 Tentperstm=$.CE 3 LOCA - Fu!! Heer-1 and 1 SSWS SFP 1DE!!2 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mft: General Elect.

Model; 114D8270 Dwas: Pv003.G 1-7 System Flaid:

HeatLoad=

5,487,500.00 BTU /hr 1DE404 HXType: Fixed Hea: Tend HX S*atus: On /in Flow Path Mfr: American Std.

Model: 17072 CPT Dwas: PM018Q j

System Fluid: Fresh Water Tube flow - 1.068.36 Tube Temperamres = 115.88'F - 118.44'F HostLosd=

1,353,000.00 BTU /hr 1DE405 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: American Std.

Model; 19084 CPT Dwgs: PM018Q System Flaid: Fresh Water l

l Tube Flow = 1,065.34 Tube Temperatures = 105.64'F - 115.8S'F Heat Load =

5,412,000.00 B1U/hr IDE408 HX Type: Fixed Heat Load HX Status: On /in Flow Path Mfr:American Std.

Model: 19198 Dwgs: PM018Q System Fluid: Fresh Water Tube Flow = 1,064.51 Tube Temperatures = 99.75'F.105.64'F lleat Load =

3,1I8,000.00 BTUehr IDK111 HX Type: Fixed Heat load HX Status: On / Not in Flow Path Mfr: Carrier Corp.

Model: 19FA553B5005932 0wgs: PM623-0002-9 Sys:em Fluid:

Heat Load -

19,500,000.00 B1U/hr l

1 I

r,c m 8/10/98 14:16 PROTO-FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 pose 22 or 26 Public Service Electric and Gas GAPSEGul-385\\New 1;HSiSTACSUHS2.PDB - Revision 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report Cnmerpra:e' Preum=1.CC.$ Sum Qal.0E-2 Frict;on=l OH FCV=1.054 PCv=1054 Tcmperature=5.0E4 LOCA FullHeat 1 and 1 SSWS SFP 1DP176 HX Type: Fixed Heat Load HX Status: On / Notin Flow Path Mfr: Carrier Corp.

Model: 19FA999-100718 Dwgs: PM623-118 System Flu;d.

Heat Load -

100.000.00 BTU /hr 1DP202-1 HX Type: Fixed Heat Load HX Sta:us: On / in Flow Path Mfr Graham Mfg. Co.

Model: 8X4C12 Dwgs N1-E11 C002 5i System Fluid Fresh Water Tube Flow - 25.51 Tube Tent;~,oues - 99.75'F.106.85'F Heat Load =

90,000 00 BTU,tr IDP202 2 HX Type: Fixed Hear Load HX Status: On / in Flow Path Mfr. Graham Mfg Co.

Model: 992C430BX Dwgs: N1 Ell C002 6 System Flu:d. Fissh Water Tube Flow w 9.97 Tube Temperatures = 99.75'F - 101.77'F Heat Load -

10.000.00 BTUehr 1DVB412 HX Type: Fixed Heat Load

!!X Status: On / m Flow Pa:h Mfh Trane Co.

Model; MDE1291600 Dwgs: PM131Q System Fluid Fresh Water Tube Flow e 520.11 Tube Tenperantres - 99.75'F - 104.00*F Heat Load =

1,100,000.00 Bluhr lDVHI13 HX Type; Fixed Heat Load HX Status: On / Not in Flow Path Mft: Amer. AirF1tr.

Model: H36MPACYA Dwgs: PM611 A-0004 7 System Fluid:

Heat load =

502,781.00 BTUihr

~u

~-.a un ss,a.assun;su y, z.., y 8/10/93 14:16 PROTO-FLO 4.01 by Proto Power Corporation Serial #PFL 0000 Pagt 23 of 26 Public Service lilectric and Gas 0:\\PSEG\\l1-385\\New UHS \\STACSLilS2.PDB. Revision 2.00 Hope Creek Occeratin5 tation STACS S

Heat Exchanger Data Report Ccwevnts:Pressurcal.0E.5 $ urn Q-1.0E 2 Fricton-l.0E4 FCV=l.0E-4 PCV-L CE-J Terrpermac=5.0E 3 LOCA FullHeat-I and 1 SSWS SFP IDVH210 HX Type: Fixed Heat Load HX Status: On / in Flow Path Mfr: Amer. Air Fitr.

Model. NDE1570300 Dwgs: PM711Q System Flufi Fresh Water Tube Flow = 144.13 Tube Temperatures a 99.755F - 102.55'F Heat Load =

200,957.00 DTU/hr IDVH211 HX Type: Fued Heat Load HX Status: Oa / in Flow Path Mft: Amer. As Fitr.

Modeh MDE1573500 Dwss: PADIIQ System Fluid: Fresh Water Tube Flow - 111.59 Tube Temperatures - 99.75'F - 102.25'F Heat Load =

138,696.00 BTU /hr IDVH213 HX Type: Fixed Heat Load IIX Status: On / in flow Path Mft: Amer. Air Fitr.

Model: MDE2478600 Dwas: PM786Q System Fluid. Fresh Water Tube Ftow = 414.86 Tube Temperatures - 99.75'F - 104.42Y Heat Load -

963,311.00 BTU /hr 1 EVE 412 HX Type: Fixed Heat Load HX Sta'us: On /in Flow Path Mft:Trane Co.

Modeh MDE1291600 Dwgs: PM731Q System Fluil Fresh Water Tube Flow = 327.57 Tube Temperatures = 100.00 F - 104.20*F Heat Load =

1,100,000 00 BTU /hr IEvilll3 HX Type: Fhed Heat Load HX Status: On /Not tn Flow Path Mir: Amer. Air F1tr.

Model: H36MPACYA Dwgs: PM611 A 0004-7 System Thud:

Heat Load =

502,181.00 BTU /hr e

--m < - m c. i e r. a.:.,

8!!W9814:16 PROTO-FLO 4,01 by Proto-Power Corporntion - Serial #PFL 0000 Pagi24 nr a Pubhc Service Electric and Gas. GAPSEGill 385\\New UHSiSTACSL'HS2.PDB - Revision 2.00 Hope Creek Generating Station STACS Heat Exchanger Data Report Cetraence: Presurrel.Uli-3 Sum Q=1 OE 2 Fricten=l.0E 0 FCV=1 OE4 PCV-1.05-) Tem;wraam-$.00 3 LOCA FullHeat - 1 and 1 SSWS - SFP l

lEVH210 HX Type: FixedHest Load HX Status: On / in Flow Path Mfr. Amer. Air Fitt.

Model: MDE1570300 Dwgs: PM71IQ l

System Fluid: Fresh Water l

Tube Flow

  • 142.71 Tube Temperatures = 100.00*F - 102.99'F Heat Lead =

211,655.00 BTU /hr l

1EVH211 HX Type: Fixed Heat load HX Status: On/ in Flow Path Mft: Amer. Air FI:r.

Model: MDE1573500 Dwgs: PM711Q System Fluid: Fresh Water Tube Flow a 111.23 Tube Temperstates = 100.00*F.102.5l'F Heat Load =

138,696.00 BTU /hr l

IEVH213 HX Type: Fixed Heat Load HX Status: On / in Flow Path MA; Amer. Air Fitr.

Model: MDE2478600 Dwas: PM786Q System Fluid. Fr:ah Water 4

Tube Flow - 408.16 Tube Tempetiturea - 100.00*F - 104.75'F

]

Heat Load =

963,311.00 BTU /hr IFVE412 IlX Type: Fixed Heat Load HX Status: On / m Flow Path Mft: Trar.e Co.

Model: MDE1291600 Dwgs: PM731Q System Fluid Fresh Water Tube Flow = $24.07 Tube Temperatures = 99.75'F - 103 97'F Heat Losd =

1.100,000.00 BTU /hr I

IFVHI13 HX Type: Fixed Heat Load HX Statum: On / Notin Flow Path j

Mft: Amer. Air F1 r.

Model: H36MPACYA CWgs: PM61lA 0004-7 Systr.m F' aid; Heat Load -

502,781.00 DTU/hr h

1 s

i

~

an'me~px'am vorTsysmYsnr4Tle P.26>27 s/10/9s 14:16 PROTO.FLO 4.01 by Proto-Power Corporation - Serial #PFL-0000 Paveas er ao Public Service Electric and Gas GAPSECT11385Wew UHSTSTACSUHS2.PDB Revision 2.00 l

Hope Creek Generating Station STACS

~

Heat Exchanger Data Report Cancrgence. Pressure =t.02 3.%m Q-1 OE4 Frict'onal.0PA FCV-l.0E 4 PCVal 064 Towerature-$.oEd LOCA. Full Heat - I and 1 SSWS SFP 1FVH210 HX Type: Fixed Heat Load HX Status: On! in Flow Path Mir: Amer. Air Fitr.

Model: MDE1570300 Dwas PM711Q j

SystemFluid: Fresh Water

'Ibbe Flow = 147.99 Tube Temperatures = 99.73'F - 102.63'F Heat Lead -

211,655.00 DTU/hr 1FVH211 HX Type: Fixed Heat toad HX Status: Ou/in Flow Path Mft: Amer. Air F1tr.

Model: MDE1573500 Dwgs: PM7t!Q System Fluid: Fresh Water Tube Flow = 111.44 Tube Temperatures - 99.75'F - 102.25'F Heat Load =

138,696.00 BTU,6 IFVH213 HX Type: Fixed Heat Load MX Status: On / in Flow Path Mft: Amer. Air Fitr.

Model: MDE2478600 Dwgs: PM786Q System Fluid: Fresh Water Tube Flow = 419.39 Tube Temperatures = 99.75'F 104.37'F Heat Load ='

963,311.00 DTUAr 1GVE412 HX T>pe: Fixed Heat Load HX Status' On /in Flow Path Mfr: Tran: Co.

Model: MDE1291600 Dwgs: PM731Q System Fluid: Fresh Wa:et Tube F.ow = $31.9$

Tabe Temperatures - 100.00*F-104.17'F Heat toad =

1,100,000.00 BTular 10VH210 HX Type: Fixed Heat Load HX Statua: On /in Flow Path Mf'r: Aroer. AirF1:r.

Model: MDE1570300 Dwgs: PM711Q System Fluid. Fresh Water l

Tube Flow = 130.96 Tube Temperamtes = 100.00'F 103.09'F Heat Load =

200,957.00 BTU /hr t

I' i

l

mmm mm, 8/10/98 14:16 PROTO FLO 4.01 by Prcts-Power Corporttion - S: rial tPFL 0000 pag 3 26 or 26 Public Service Electric and Gas. G:\\PSEOst 1355%w UHSiSTACSUHS2 FDD Revision 2.00 Hope Creek Generadng Station. STACS Heat Exchanger Data Repon emvmpnce: rm.m-1 m3 sm 4 1.ct.2 rnaiun-1.ct4 tcv-t oca rev-1.ct.) Imrwarm 2.ot.3 l

LOCA Full Heat. I and 1 SSWS. SFP l

1GVH211 WX Typet Frxed Heat Load HX Status. Ou/in Flow Path Mft: Amer. a:r Fitr.

Model: MDE1573500 Dwas: PM71IQ System Fluid Fresh Wates l

Tube Flow = 112.31 Tube Tcznperetttres = 100.00 F 102.49'F Heat Load -

138,696 00 BTU <br l

IHVE412 HXType: Fixed Heat Load IIX Status: On / in Flow Pat l

Mir:Tranc Co.

Model: MDE1291600 Dwgs: PM731Q SystemFluid: Fresh Water Tube Flow = 606.52 Tube Temperatures = 99 75'F - 103.40'F Heat Load =

1,100,000.00 BTU,tr IHVR210 MX Type: Fixed Heat 1.oad HX Status: On / in Flow Path Mfr: Azr.cr. Air Fl:r.

Model: MDE1570300 Dwas: PM71IQ Systeta Fluid: Fresh Water Tube Flow - 144.00 Tube Tcznperatures - 99.75*F - 102.56*F Heat Load -

200,957.00 Bilhhr lHVH211 HX Type: Fixed Heat Load MX Status: On /In Flow Path Mft: Amer. Air Fitr.

Modeh MDE1573500 Dwas: FM71IQ System Flutd: Fresh Water Tube Flow = 112.14 Tube Te:tiperatures - 99.75'F 102 24*F Heat Load =

138,696,00 BTU /hr

<
  • TOTAL PME. 027 **

.. - ~....

9-i i

i i

]

= -

i

~

l g

GE Nuclear Energy M

Gene *al Eectnc Cyrcany 2CS Great varley Parsway rfaNent Pa 1935$ 1337 HCGS-Ie96-039 September 20,1996 Mr. Chris Brennan Nuclear Fuels Public Service Electric ac Gas Hancocks Bridge, NJ 08038

SUBJECT:

TRANSMITTAL OF GE-NUCLEAR ENERGY INFORMAT REGARDING THE USE OF SHEX AND THE GE-NE VERSION OF THE ANS 5.1 - 1979 DECAY HEAT CURVE IN CONTAINMENT CALCULATIONS

REFERENCE:

1) GE-Nuclear Energy Letter EGT96:054, dated 9/17/96

Dear Chris,

GE Nuclear Energy engineering personnel have transmitted the subject information per your request as Attachments 2 and 3 to the above referenced letter. Both the letter and Attachments 2 and 3 are attached for your use.

If further information is required, please call me.

7m.J. h&"

M. G. Farschon GE Site Service Manager Hope Creek Site l

t i

i e

1

~

i l

l GENuclearEnugy i

TECHNICALSERVICES SanJose, California EGT96:054 cc:

P. C. Ray September 17,1996 Mr. M. G. Farschon GE-Nuclear Energy Hope Creek Generating Station End of Buttonwood Road Hancocks Bridge, NJ 08038 i

Transmittal of Information Requested by PSE&G

Subject:

This letter transmits information requested by Mr. Fuhrmeister and Mr. Brennan PSE&G. Attachment 1 provides design verified information for Mr. Fuhrmeiste resolving an USNRC inquiry regarding f:ed water addition in containment c provides additionalinformation regarding the use of the SHEX engineering computer program (ECP) for Hope Creek containment calcula included in the plant UFSAR. Attachment 3 is the USNRC letter to GE-Nucle specifically accepting the SHEX ECP and GE-NE's version of the ANS heat curve for use in containment calculations and other background information Please call me if you have any questions.

s t

I I.

E. G. Thacker

- Principal Engineer Phone:

408 9254154-408 322 3569 pager

/att.

,o.

Hope Creek Generating Station Computer Program Used for Containment Analyses Which containment analysis code was used for Hope Creek G Question:

Station FSAR analysis?

The GE proprietary code SHEX 03 was used for the FSAR a hich current version used for these types of calculations is SHEX-04, w Answer:

replaced SHEX 03 with the following improvements (reference:

User's Manual, August 1985);

Improve computational speed a)

Expand the analytical modeling capabilityIncrease the t b) c)

GE Note that ECPs such as SHEX are unde program identifies the domain of application.

e e