ML20151V577
| ML20151V577 | |
| Person / Time | |
|---|---|
| Site: | Waterford |
| Issue date: | 01/27/1986 |
| From: | Knighton G Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML20151V581 | List: |
| References | |
| NUDOCS 8602110348 | |
| Download: ML20151V577 (7) | |
Text
~~
en are,,
+
o UNITED STATES 8
~,j NUCLEAR REGULATORY COMMISSION 7,
E WASHINGTON, D. C. 20555
~s., +... /
LOUISIANA POWER AND LIGHT COMPANY DOCKET NO. 50-382 WATERFORD STEAM ELECTRIC STATION, UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 3 License No. NPF-38 1.
The Nuclear Regulatory Commission (the Coninission) has found that:
A.
The application for amendment, dated June 6,1985, by Louisiana Power and Light Company ~(licensee), complies with standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangerino the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the coninon defense and security or to the health and safety of the public; E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paracraph 2.C(2) of Facility Operating License No. NPF-38 is hereby amended to read-as follows:
8602110348 860127 DR p
ADOCg 0500o39, PDR i
L' 2
(2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 3, anc the Environmental Prntection Plan contained in Appendix B, are hereby incorporated in this license.
LP&L shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
3.
The license amendment is effective as of the date of issuance.
FOR THE NUCLEAR REGULATORY COPHISSION 4
f4 George nicht Director PWR Proiect Directorate No. 7 Division of PWR Licensing-B
Attachment:
Changes to the Technical Specifications Date of Issuance: JAN 2 71986 4
{}'
N 2pfgg6
. ATTACHMENT TO LICENSE AMENDMENT NO. 3 TO FACILITY OPERATING LICENSE NO. NPF-38 DOCKET NO. 50-382 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages. The revised pages are identified b.y Amendment number and contain vertical lines indicating the area of change. Also to be replaced are the following overleaf pages to the amended pages.
Amendment Pages Overleaf Paoes 3/4 3-52 3/4 3-51 3/4 6-29 3/4 6-30 l
[
o a
I 4
l f
l l
L
- ~.
TABLE 3.3-11 FIRE DETECTION' INSTRUMENTS TOTAL NUMBER OF INSTRUMENTS
- ELEVATION HEAT FLAME SM0KE ZONE ROOM NAME/ NUMBER (ft)
(x/y) (x/y) (x/y) 1.
REACTOR AUXILIARY BUILDING RAB 1A Control Room Proper /304
+46 20/0 RAB 18 Emergency Equip. H&V Room /314
+46 0/12 RA8 ID Computer Room (above raised floor)/306 +46 5/0 Computer Room (below raised floor)/306 +46 0/7 RA8 2 Ventilation Equip. Room /299
+46 0/36 RAS 3 RA8 Corridor to Relay Room /261
+35 0/1(3) 4/0 RAB HVAC Switchgear Equip. Room /323
+46 0/10 RA8 3A RAB Battery Exhaust Fan Room /406
+69 0/2 RAB 4 Cable Vault /260
+35 0/27 RA8 5 Electrical Penetration Area "A"/263
+35 0/13 RAB 6 Electrical Penetration Area "B"/263A
+35 0/14 RAB 7 Relay Room /262
+35 (3) 12/0 Isolation Panels (9 Compartments
+35 2/0
- 2 per comp.)
RAB 8A High Voltage Switchgear. Room "A"/212A
+21 0/1(1) 18/0 RAB 8B Electrical Equip. Room /2258 and High
+21 0/1(2) 28/0 Voltage Switchgear Room "B"/212
'480V Switchgear 3A32 Room
+21 (2) 2/0 RAB 8C High Voltage Switchgear Room
+21 (1) 8/0 "A-B"/2128 RAB 8E CEA M/G Set Room /216
+21 2/0 RAB 9 Remote Shutdown Panel Room /217
+21 1/0 RA8 11 Battery Room "B"/213
+21 2/0 RA8 12 Battery Room "AB"/214A
+21 2/0 RAB 13 Battery Room "A"/214
+21 2/0 RAB 15 Emergency Diesel Gen. "B" Room /222
+21 0/1 RAB 15A Emergency Diesel Gen. "B" Feed TK
+46 0/1 Room /328A RAB 16 Emergency Diesel Gen. "A" Room /221
+21 0/1 RAB 16A Emergency Diesel Gen. "A" Feed Tk.
+46 0/1 Room 328A RAB 17 CCW Heat Exchanger "B"/236
+21 0/4 RAB 18 CCW Heat Exchanger "A"/220
+21 0/4 RAB 19 CCW Pump "A"/235
+21 2/0 RAB 20 CCW Pump "AB"/234
+21 0/2 RAB 21 CCW Pump "B"/233
+21 1/0 RAB 23 Corridor to CCW Pumps /218, Corridor
+21 0/39 to CCW Heat Exchangers/219 and Corridor to Emergency Dieser Gen./225A (1) Common Resistor Wire (2) Common Resistor Wire (3) Common Resistor Wire WATERFORD - UNIT 3 3/4 3-51
. ~ ~
TABLE 3.3-11 (Continued)
FIRE DETECTION INSTRUMENTS TOTAL NUMBER OF INSTRUMENTS
- ELEVATION HEAT FLAME SMOKE ZONE ROOM NAME/ NUMBER (ft)
Bfy), @ h/y),
1.
REACTOR AUXILIARY BUILDING (Continued)
RA8 25 Equip. Access Area /226 (wing area)
+21 15/0 RA8 27A H&V Room /124
+7 0/6 RA8 278 Electrical Area and Health Physics
+7 0/35 Offices /122 l
RA8 27C I&C Room /120
+7 0/6 l
l RA8 270 Communications Equip. Room /123
+7 1/0 RA8 31 Corridors and Passageways
-4 0/24 Corridors on eastside
-4 0/21 RA8 32 Wing Area westside - Auxiliary Com-
-35 32/0 ponent Cooling Water Pump "A"/853 and Pipe Penetration Area /8100
-4 Wing Area Center /853 and 8100
-35 &
28/0
-4 i
Wing Area eastside-Component Cooling
-35 31/0 Water Pump "B"/853 and Pipe l
Penetration Area /8100
-4 RA8 33 S/D Cooling Heat Exchangers A&B/820
-35 0/18
& 848 RA8 34 Valve Operating Enclosure Bay Room
-15.5 2/0 "A"/854 l
Valve Operating Enclosure Bay Room
-15.5 4/0 "8" 855A RA8 35 Safety Injection Pump Room 8/816
-35 10/0 RA8 36 Safety Injection Pump Room A/815
-15 10/0 RA8 37 Motor-Driven Emergency Feedpump
-35 0/1 "A"/849A RA8 38 Motor-Driven Emergency Feedpump
-35 1/0 "B"/8498 RA8 39 General Equipment Area /85, 12, 13,
-35 0/10
~
& 49 Corridors & General Equip. Areas /85,
-35 0/28 1, 2, 3, 4, 39, 40, 41, 42, 44 & 46 East Corridor & General Equip. Areas /
-35 0/15 817, 23 & 25 BA Make-up Tank "A"/838
-35 4/0 BA Make-up Tank "B"/853A
-35 4/0 RAB 40 Diesel Storage Tank "A"/850
-35 3/0 RA8 41 Diesel Storage Tank "B"/852
-35 3/0 WATERFORD - UNIT 3 3/4 3-52 Amendment No. 3 t
t
- il g
TABLE 3.6-2 (Continued)
M ig CONTAINMENT ISOLATION VALVES **
E o
PENETRATION VALVE MAXIMUM NUpBER NUBBER FUNCTION ISOLATION TIME (Seconds)
Eg 6.
Manual / Remote Manual (Continued) 48 2HV-8190A (CAR 202A)*
CARS Exhaust N.A.
51 2FS-V145A/8 (FS405)*
Refueling Cavity Purification Inlet N.A.
51 2FS-V144A/8 (FS406)*
Refueling Cavity Purification Inlet N.A.
Instrument H&V N.A.
55 2SI-V1550A1 (SI 225A)*
m1 55 2SI-V154581 (SI 2258)*
U 56 2SI-V1546A2 (SI 226A)*
56 2SI-V154082 (SI 2268)*
57 2SI-V1542A3 (SI 227A)*
57 2SI-V154783 (SI 2278)*
58 2SI-V1548A4 (SI 228A)*
58 2SI-V154484 (SI 2288)*
59 2SI-V1570 (5I344)*
SIT Drain to RWSP N.A.
E 62 2FS-V165A/8 (FS416)
Refueling Cavity Drain M.A.
5 m
9
t TA8LE 3.6-2 (Continued)
CONTAINMENT ISOLATION VALVES **
5 PENETRATION VALVE MAXIMUM e
NUMBER NUMBER FUNCTION ISOLATION TIME (Seconds) 6.
Manual / Remote Manual (Continued) 62 2FS-V164A/B (FS415)
Refueling Cavity Drain N.A.
63 25A-V114 (LRT109)
ILRT Connection M.A.
63 2SA-V604 (LRT110)
ILRT Connection N.A.
65 2SA-V609 (LRT202)
ILRT Test Connection M.A.
65 2SA-V611 (LRT204)
ILRT Test Connection N.A.
65 25A-V610 (LRT201)
ILRT Test Connection N.A.
8 65 2SA-V612 (LRT203)
ILRT Test Connection M.A.
65 25A-V620 (LRT2011)
ILRT Test Connection N.A.
65 2SA-V621 (LRT 2031)
ILRT Test Connection N.A.
Instrument H&V N.A.
SI Hot Leg Injection N.A.
SI Hot Leg Injection N.A.
E g
71 20W-V642 (CMU244)*
Demineralized Water N.A.
s an U
S
.