PNO-77-071:on 770427,turbine Generator Tripped & Reactor Scrammed as Result of Electrical Phase Differential Across Generator & Main Transformer & Ground on Main Generator. Caused by Leak in Water Hose
ML20151U917
Person / Time
Site: Brunswick 
Issue date: 04/29/1977
From: Gower G, Roy G, Thompson D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-77-071, PNO-77-71, NUDOCS 9809110230
Download: ML20151U917 (1)


Text

{p p cjl g e Q Ch hl

..n PRELIMINARY NOTIFICATION

~

.-.-..._.__.._....................-s--mm.n,..m,__u.____.._._

April 29, 1977 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-77-71 This preliminary notification constitutes EARLY notice of an event of

, POSSIBLE safety or public interest significance. The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

Facility:

Carolina Power and Light Company (CP&L)

Brunswick Unit No.1 (DN 50-324)

Subject:

TURBINE GENERATOR FAILURE At 11:41 a.m. on April 27, 1977, with reactor operating at 100% power, the turbine generator tripped and the reactor scrammed as a result of an electrical phase differential across the generator and the main trans-former, and a ground on the main generator. Preliminary investigation indicated that a water hose that supplies water for cooling the stator windings may have developed a leak that shorted one or more conductors; however, the cause and extent of damage to the generator is still unknown.

The turbine generator is expected to be out of service for at least three weeks.

-si CP&L is considering making a press release.

Region II received notification of'this occurrence from the plant manager via telephone at 0830 hours0.00961 days <br />0.231 hours <br />0.00137 weeks <br />3.15815e-4 months <br /> on April 28, 1977.

Contact:

GCGover, IE x27261 GWRoy, IE x 27261 DThompson, IE x27541 Distribution:

TransmittedHSt/.Y Chairman Rowden C. C. Kammerer, CA G. F. Murphy, JCAE Commissioner Kennedy S. J. Chilk, SECY H. H. Whiteside, SCNR Commissioner Gilinsky H. R. Myers, HCEE MNBB [ % :

PBldg((YI; SS Bldg /! Y $ ;

Transmitted:

L. V. Gossick, EDO E. G. Case, NRR C. V. Smith, NMSS

{

S. H. Hanauer, EDO H. K. Shapar, ELD J. A. Harris, PA.

W.'G. Mcdonald, MIPC Luge (mail);

E. Vol IE R. G. Ryan, OSP T. J. McTiernan, OIA Region nau, / M ;

PRELIMINARY NOTIFICATION c

pi' 9809110230 770429 PDR I&E PNO-77-071, PDR

-..