SACRAMENTO MUNICIPAL UTILITY DISTRICT '. 6201 s Street. P.O. Box 15d;':. Cucramento CA 95852-1830,(916)452 3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA RJR 86-36 January 30, 1986 J B MARTIN REGIONAL ADMINISTRATOR REGION V 0FFICE OF INSPECTION AND ENFORCEMENT ATTENTION DOCUMENT CONTROL DESK U S NUCLEAR REGULATORY COMMISSION WASHINGTON D C 20555 DOCKET NO. 50-312 LICENSE NO. DPR-54 SPECIAL REPORT NUMBER 86-02, FIRE BARRIERS The Sacramento Municipal Utility District hereby submits Special Report 86-02 in accordance with Rancho Seco Nuclear Generating Station Technical Specifications, Section 3.14.6.2 and 6.9.5E.

This report provides an updated list (attached) of non-functional fire barriers reported in our December 26, 1985 Special Report 85-14, and identifies any non-functional fire barriers detected or created since that report which were not restored to functional status within seven (7) days.

The District has evaluated each non-functional fire barrier against the requirements of Technical Specification 3.14.6 and has verified that the proper fire watch has been established.

An updated status for each penetration program area is given h.the following:

1.

Electrical Penetrations - The first of thr. fire tests for conduit penetrations through cable trays resulted in a significant reduction in the number of remaining conduit breaches listed in previous reports. AJditional testing for the remaining conduit seals has oeen scheduled for February.

Breaches identified as surveillance items in the last report have been scheduled for a March 31, 1986, comple-tion date.

Work on the Bus Ducts remains scheduled for the next refueling outage.

New breaches are being made as a part of ongoing work.

A schedule for the closure of these breaches is being developed and will be provided in a future report.

,,3,/t'd 8602100209 G60130 7

D PDR ADOCK 05000312 S

PDR RANCHO SECO NUCLEAR GENERATING STATION O 14440 Twin Cities Road, Herald, CA 95638-9799;(209) 333-2935

~

I_-

J B MARTIN: Janaury 30, 1986 9

'2.

-Mechanical Penetrations - All mechanical penetrations-identified this summer as-part of Appendix R work have been completed.

The expansion joint, which has been-listed in the past with.the mechanical penetrations, will be provided with a completion date in a future report.

0ne new mechanical penetration breach has been identi-

-fied as a part of ongoing work. A schedule will be provided for sealing this breach in a future report.

3.

Doors - All-door work remains scheduled for completion by March 15, 1986.

4.

Fire Dampers - The damper work remains scheduled for completion by March 1, 1986.

If y u have any quest'ans concerning this report, please contact Mr. Ron W.

s lo bo t Rancho Seo; Nuclear Generating Station Unit'Nc. 1.

t y

R.-J.

ODRI EZ ASSISTANT GE RAL MANAGER, NUCLEAR Attachment cc: NRR

4 g.

LEGEND-C

. CONDUIT (Conduit through cable tray seals requiring additional fire tests.)

BD BUS DUCT (Inaccessible until next scheduled refueling outage.)

NB NEW. B REACHES S

SURVEILLANCE ITEMS SEALED SEALED PENETRATIONS (Reported per Tech Spec section 3.14.6.2)

G GROUTED MECHANICAL PENETRATION FOUR ELECTRICAL PENETRATIONS WERE RE-NAMED:

f 88-99/2 AA renamed 85/1-87 AA 88-90/2 AB renamed 85/1-87 AB 90/1-90/2 AA renamed 85/1-89 AA 99/1-90/2 AB renamed 85/1-89 AB 4

i

...,-.,_,.n

_n

,.---,.___..nn._

O e

4 -

e 01/13/86 ATTACHMENT TO NRC SPECIAL REPORT ELECTRICAL PENETRATIONS PENETRATION NOTES FIRE AREA DETECTOR ZONE NUMBER 01-17 AH NB 1-17 13-03 01-17 AH C

1-17 13-03 01-20 AA C

1-20 16-04 01-20 AA NB 1-20 16-04 01-20 AB C

1-20 16-04 01-20 AB NB 1-20 16-04 15-71/2 AA S

15-71/2.

11-10 15-71/3 AA BD 15-71/3 11-10 15-71/3 AB S

15-71/3 11-10 15-71/3 AC BD 15-71/3 11-10 15-71/3 AD S

15-71/3 11-10 16-17 AA C

16-17 12-13 16-29 AA C

16-29 12 16-29 AA NB RM1-16 19-12 16-31 AA C

16-31 12-37 17-18 AA NB 17-18 13-14 17-18 AB C

17-18 13-14 17-20 AC C

17-20 13-16 17-29 AA C

17-RM1 13-19 17-29 AA NB RM1-17 13-19 17-29 AB NB RM1-17 13-19 17-29 AE C

17-29 13-20 17-31 AA BD 17-31 13-3" 17-31 AB BD 17-31 13-37 18-19 AC C

18-19 14-15 18-19 AC NB 18-19 14-15 18-31 AH NB 18-31 14-37 18-47 AA C

18-47 14-46 19-32 AD NB 19-32 15-38 19-46 AA C

19-46 15-46 19-81 AB S

19-81 15-81 20-29 NB 20-RM1 20-16 20-29 NB 20-RM1 20-16 20-29 AB NB RM1-20 20-16 20-29 AC C

20-RM1 16-20 20-29 AC NB RM1-20 20-16 20-29 AD NB RM1-20 20-16 20-29 AE NB RM1-20 20-16 20-29 AF C

20-RM1 16-20 20-32 AA C

20-32 16-38 20-32 AB BD 20-32 16-38 20-32 AC BD 20-32 16-38

01/13/86

-ATTACHMENT TO NRC SPECIAL REPORT ELECTRICAL PENETRATIONS PENETRATION NOTES FIRE AREA DETECTOR ZONE NUMBER 20-32 AD NB 20-32 16-38 27-29 AC C

27-RM1 20 27-29 AC NB 27-RM1 20 28-29 AA NB RM1-28 20 29-71 AA C

RM1-71 19-10 29-71/2 AA NB RM1-71 19-10 29-71/2 AB NB RM1-71 19-10 30-31 AA C

30-31 36-37 30-31 AC BD 30-31 36-37 30-31 AE SD 30-31 36-37 30-71/1 AF BD 30-71 36-34 30-7tJ1 AG C

30-71 34-36 31-32 AA BD 31-32 36-37 31-32 AC PER ECN 31-32 36-37 31-36 AA C

31-36 37-42 31-36 AE NB 31-36 37-42 32-36 AA C

32-36 38-42 34-36 AB C

RG1-36 43 34-36 AB NB RG1-36 43 34-36 AJ NB RG1-36 42 34-64 AA NB RG1-64 42 34-64 AB NB RG1-64 42 34-OUTSIDE AA NB RG1-69 42 36-64 AA NB 36-64 42 36-71/1 AA NB 36-71/1 34-42 36-71/1 AB NB 36-71/1 42-34 39-50 AA C

RG1-RB1 47-43 39-50 AA NB RG1-RB1 47-43 47-56 AA C

47-56 46-48 703277 NB OUT-18 14 75/1-81 AA S

75/1-81 75-81 75/1-81 AB S

75/1-81 75-81 76/1-82 AA G

76/1-82 76-82 76/1-82 AB S

76/1-82 76-82 78/2-82 AB S

78/2-82 78-82 781699 NB 84/1-83/1 84-83 781699 NB 85/1-84/1 85-84 85/1-85/2 AA S

85/1-85/2 85 85/1-85/2 AA NB 85/1-85/2 85 85/1-85/2 AA NB 85/1-85/2 85 85/1-85/3 AA S

85/1-85/3 85 85/1-85/3 AA NB 85/1-85/3 85 85/1-85/4 AA S

85/1-85/4 85 85/1-85/4 AA NB 85/1-85/4 85

31/13/86 ATTACHMENT TO NRC SPECIAL REPORT ELECTRICAL PENETRATIONS PENETRATION NOTES FIRE AREA DETECTOR ZONE NUMBER 85/1-85/4 AB S

85/1-85/4 85 85/1-87 AA

-S, 85/1-87 88-98

- 85/1-87 AB S,

85/1-87 88-90 85/1-89 AA S,

85/1-89 99 85/1-89 AB S,

85/1-89 90 85/2-89 AA NB 85/2-89 85-89 85/2-89 AB NB 85/2-89 85-89 85/3-87 AA NB 85/3-87 85-87 85/3-88 AA S

85/3-88 85-88 85/3-88 AB S

85/3-88 85-88 FB 69-1 NB 69 FB 69-2 NB 69 Xe3267 NB OUT-18 14 X44111 NB 32-36 38-42 X41195 NB 20-92 16-104 X41185 NB 19-29 15-16 X42250 NB 2-85/4 104-85 4

X43BE3 NB 31-36 37-42 X81514 NB 84/1-84/2 84 X81514 NB 85/1-87 85-87 4

l 4

4

. e _,.

01/13/86 ATTACHMENT TO NRC SPECIAL REPORT FIRE DAMPERS DAMPER NUMBER FIRE AREA DETECTOR ZONE-NOTES FD-Gel 01-02 04-104 FD-902 01-02 04-104 FD-903 01-02 04-104 FD-904 01-02 04-104 FD-905 01-02 04-104 FD-906 01-02 04-104 FD-907 01-02 04-104 FD-808 01-02 04-104 FD-018-15-RM1 11-19 FD-025 47-48 46-47 FD-826A 20-21 16-17 FD-027A 21-20 16-17

- FD-028 RB1-RB2 47 FD-028A 21-20 46 FD-029A 16-17 12-13 FD-030A 16-17 12-13 FD-031A 16-17 12-13 FD-042 RT1-RG1 05-109 FD-046 RT1-RG1 05-109 FD-047 RT1-RG1 05-109 FD-048 RT1-RG1 05-109 FD-101 30-36 36-42 FD-102 33-36 39-42 MISSING DAMPER 92-74 104 MISSING DAMPER 92-74 104

!)

X ATTACHMENT TO NRC SPECIAL REPORT FIRE DOORS FIRE DOOR FIRE AREA DETECTOR ZONE

~9 ACCESS HATCH RM1-38 1

AU102 36-RG1 43 AU199 R61-72 42 AU129 RG3-69 42 AU132 38-71 34-41 AU136 47-64 42-YARD Ad137 RB2 46-43 AU139 RG1 42 AU201 67-RM1 18 AU215 17-RM1 13-19 AU218 71-RM1 10-19 AU221 71-RM1 10-19 AU225 RM1-27 20 AU319 72-RT1 07 AU334 1-RT1 03-109 AU338 1

02-03 AUR401 74 06 NS063 82-81 82-81 NS153 83/2-83/1 83 NS154 76/3-76/1 76 NS155 76/2-76/1 76 NS156 75/2-75/1 75 NS157 75/3-75/1 75 NS160 82-83/1 82-83 NS161 81-83/1 81-83 NS232 82-84/1 82-84 NS233 81-84/1 81-84 N9242 84/1-83/2 84-83 NS355 85/2-85/1 85 NS356 85/1-83/2 85-83 NS358 79-85/3 79-85 NS359 80-85/2 80-85 L

q.

'J 01/13/86 ATTACHMENT TO NRC SPECIAL REPORT MECHANICAL PENETRATIONS PENETRATION NUMBER FIRE AREA DETECTOR ZONE NOTES 3131 31-36 37-42 NB EXDANSION JOINT (UNSEALED) 27-28 20