Duurs Powisn Go>mtNY 15.0. IlOX 331(ID CII AHLOTTE, N.C. 2(1242
,(
(7 k37
'll Nt1 LS- ' ' P OW.04TT104 August 5, 1988 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.
20555
Subject:
McGuire Nuclear Station Docket Nos. 50-369, -370 NRC/0IE Inspection Report Kos. 50-369,370/88-14 Reply to a Notice of Violation Centlemen:
Pursuant to 10CFR2.101, please find attached Duke Power Company's response to violation 370/88-14-02 that was reported in the subject inspection report.
h St.ould there be any questions uncerning this matter, contact S.E.
LeRoy at (704) 373-6233.
Ve.ry truly yours, q..g
/
Hal B. Tucker SEL/308/ bhp Attachment xc:
Dr. J. Nelson Grace Regional Administrator, Region II U.S. Nuclear Regulatory Cominission 101 M.rie
. Stc, NW, Suite 2900 Atlanta, GA 30323 Mr. Darl Hood 0;S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Wast.ington, D.C.
20555 Mr. W.T. Orders NRC Resident Inspector McGuire Nuclear Station 8808120124 880805 1
PDR ADOCK 05000369 O
t DUKE POWER COMPAN7 McGUIRE NUCLEAR STATION REPLY TO A NOTICE OF VIOLATION INSPECTION REPORT NOS. 50-369/88-14 and 50-370/88-14 Vlolatian 370/88-14-02 Technical Specification (TS) 6.8.1.a requires that written procedures be established, implemented, and maintained covering the activities delinaated in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978.
Regulatory Guide 1.33, Revision 2, February 1978, Appendix A, requires, in part, that general procedures for the control of maintenance should be prepared.
- Also, maintenance that can affect performance of safety-related equipmant should be performed in accordance with written procedures, documented instructions, or drawings appropriate to the circumstances.
Maintenance Management Procedure 1.0, Revision 13, dated April 21, 1988, covers control of maintenance at McGuire using the work request form and states that "Activities under categories I and II above shall require a work request". Category II work includes adjustment of equipment.
Contrary to the above, maintenance personnel adjusted the fuel racks on the 2A diesel generator on May 23, 1988, to increase the diesel generator output without a work request or a procedure.
This was done when operations found that the load on the 2A diesel could nat be raised to 4400 KW ns required by procedure PT/2/A/4200/36A, DG 2A 24 Hour Run.
This is a Severity Level IV (Supplement 1) violation and applien to Unit 2 only.
Response
1.
Admission of denial of violation:
The violation is admitted as stated.
2.
Reason for the violation if admitted:
When 'iesel Generator 2A could not be loaded to 4400 KW, Operations pers- _el requested Mechanical Maintenance personnal to adjust the diesel engine to previde the required ot.tput.
Maintenance personnel adjusted the fuel racks without a work request and without a procedure.
This cccurred as a result of an oversight by the individual involved and is considered a personnel error.
3.
Corrective steps which have been taken and results achieved:
The individual involved was counseled.
The incident was reviewed with all Mechanical Maintenance personnel.
Emphasis was placed on the correct method for performing adj ustments and completing the associated documentation. The u.a of procedures was reemphasized.
\\!
..e
,e I
2 4.
Corrective steps that will be taken to avoid further violations:
No additional corrective actions are planned.
5.
Date when full compliance will be achieved:
Full compliance was achieved on August 3,1938.-