ENCLOSURE 2 '
U.S. NUCLEAR REGULATORY COMMISSION
REGION IV
Docket Nos.:
50-445
50-446
License Nos.:
NPF-89
Report No.:
50-445/9,'-15
50-446/97-15
Licensee:
TU Electric
Facility:
Comanche Peak Steam Electric Station, Units 1 and 2
Location:
Glen Rose, Texas
Dates:
June 8 through July 19,1997
l
Inspectors:
G. E. Werner, Acting Senior Resident inspector
H. A. Freeman, Resident inspector
j
R. L. Nease, Technical Assistant, Division of Reactor Projects
Approved By:
J. l. Tapia, Chief, Projects Branch A
Division of Reactor Projects
,
ATTACHMENT:
Supplemental Information
l
1
"
9708000020 970005
ADOCK 05000445
g
.
.
-
.
.
_
_-.
- . ..
.. -
.
!
.
EXECUTIVE SUMMARY
Comanche Peak Steam Electric Station, Units 1 and 2
'
NRC Inspection Report 50-445/97-15; 50-446/97-15
Operations
I
The conduct of operations was professional and included safe practices
(Section 01.1).
,
The inspectors found that operators handled the loss of Reactor Coolant Pump 2-02
breaker indication well and that the licensee's plan to refurbish the breaker during
the upcoming outage was appropriate (Section 01.2).
The inspectors concluded that operations management used appropriate judgment in
performing the heater drain tank valve maintenance at 100 percent power. The use
"
of the simulator prior to the maintenance activity was a good practice
(Section 05.1).
.
A violation was identified as a result of the licensee operating Unit 2 above
102 percent thermal power on February 14,1996, for approximately 30 minutes
(Section 08.1).
Maintenance
The inverter troubleshooting plan was detailed and indicated a well prepared
strategy. The operators and technicians demonstrated excellent skills and carefully
performed each task of the troubleshooting plan (Section M1.2).
J
The technicians performed in an excellent manner during a very detailed
refurbishment .f Valve X-PV-3584-MO (Section M1.3).
,
Enaineerina
The inspector identified a violation where the licensee failed to update design
]
drawings and procedures for a design change which limited the travel of the Unit 2
~
containment pressure relief containment isolation valves (Section E2.1).
The inspectors determined that the surveillance procedures did not adequately
!
implement Technical Specification (TS) Surveillance 4.7.10, in that, a common
exhaust duct temperature detector provided temperature measurement for two
'
different safeguard building areas (main steam and feedwater penetration areas),
(Section E3.1).
Plant Sucoort
Overall, radiological housekeeping was very good; however, four examples of poor
radiological work practices were identified by the inspector (Section R1.1).
..
.
,
.
2-
The inspector concluded that access control was properly implemented and security
personnel demonstrated a good working knowledge of the requirements for
emergency access control (Section S1.1).
A computer software problem contributed to two individuals entering the protected
area when their key cards should have been deactivated. The failure to deactivate
the two key cards was identified as a noncited violation (Section S3.1).
The failure of the central alarm operator to reset the containment personnel airlock
,
alarm prior to releasing the compensatory officer is considered a noncited violation
j
(Section S4.1).
The inspectors identified three examples where the licensee failed to establish
compensatory measures prior to impairing a fire area assembly. These three
examples are considered to be a violation of TS 6.8.1.h (Section F3.1).
!
!
,
_
.
.
t
I
.
Report Details
,
i
Summary of Plant Status
,
Unit 1 and Unit 2 operated at approximately 100 percent power throughout the inspection
period.
l
t
l. Operations
l
01
Conduct of Operations
)
J
01.1 Plant Tours (71707)
l
a.
Inspection Scope
The inspectors conducted frequent plant tours to inspect general plant material and
housekeeping conditions. As part of the tours, the inspectors performed routine
control room observations.
b.
Observations and Findinas
Overall, the inspectors determined that plant housekeeping and material condition of
plant equipment was very good. Readily observed equipment discrepancies were
'
appropriately identified for repair. The inspectors did identify that Emergency Diesel
Generator Room 2-01 contained several areas that needed housekeeping attention.
A plastic bucket (approximately 1 gallon) used as an oil catch was completely full
and overflowing. In addition, the inspectors identified a large pool of oil beneath tne
generator end of the engine and numerous oil soaked pads. When the licensee was
informed of these observations, the areas were immediately cleaned up. The
inspectors identified other areas that needed minor housekeeping attention and
these areas were immediately addressed by the licensee.
The inspectors observed several shift turnovers and conducted numerous
observations of control room activities and determined that the conduct of
operations was professional and safe. Operators were aware of plant conditions
and ongoing riaintenance. Communications were generally good with consistent
use of three-ivay communication techniques (command, repeat back, and
acknowledgement).
01.2 Loss c,f Reactor Coolant Pumo 2-01 Breaker Closed Indication
a.
Insoection Scope (71707)
On June 27, a licensed operator identified that the closed breaker indication for
Reactor Coolant Pump 2-02 was not lit on the control board or on the breaker
cabinet. The licensee entered the action requirement for Technical Specification (TS) 3.8.4, " Containment Penetration Overcurrent Protective Devices." Pushin.~ an
the breaker housing restored the closed indication. The inspectors reviewed the
=.
.
.
=.
.
- - .
.
.
'
t
t
, .
'
.
-2-
.
effect that the loss of indication had on the operation of the reactor coolant pump
breaker and on reactor safety, and reviewed the licensee's immediate and long-term
corrective actions.
t
b.
Observations and Findinas
The breaker overcurrent and underfrequency trip functions were part of the same
circuit as the breaker closed indication. As a result, the loss of indication affected
the ability to trip the breaker both manually and automatically on overcurrent or
,
underfrequency. The licensee pushed on the breaker and reestablished the
j
secondary stab contacts on the breaker, which, in part, provided the previously
discussed protective functions. The breaker will be refurbished during the upcoming
refueling outage. The undervoltage-based and underfrequency-based reactor
coolant system low flow trip inputs to the reactor protection system were provided
by circuits separate from the breaker and were not affected by the loss of
indication.
Technical Specification 3.8.4 required that all containment penetration overcurrent
protective devices be operable. Final Safety Analysis Report Section 8.3.1.2
stated, in part, that the electric penetration assembly design is capable of
withstanding, without loss of mechanical integrity, the maximum current versus
time conditions permitted by backup protective devices. Since the primary
overcurrent protective device was inoperable, the licensee entered the action
statement and then restored the protective device prior to exceeding the allowed
outage time.
t
c.
Conclusions
The inspectors found that the licensee handled the loss of Reactor Coolant
Pump 2-02 breaker indication well and that the licensee's plan to refurbish the
breaker during the upcoming outage was appropriate.
04
Operator Knowledge and Performance
04.1 Operations Surveillance Observations (71707,61726)
The inspector used Inspection Procedures 71707 and 61726 to observe:
1
'
Unit 1 Slave Relay K601 actuation test
The reactor operator performing the slave relay actuation test conducted the
test using excellent self-verification and communication techniques. The
operator meticulously worked his way through the test procedure and
ensured that all equipment responded as required. During the review of the
surveillance work order (WO), the inspector determined that the TS impacted
by the testing, as noted in the WO, did not match the surveillance procedure
. .
.- .-
.
.
. - - -
- -
- - . -
.
-
.
.
-3-
TS listing. The inspector verified that the surveillance test procedure was
correct by ensuring that the Master Surveillance Test List corresponded with
the surveillance test procedure. A TS amendment changed numerous TS
requirements, however, the WO data base had not been revised to reflect the
changes. Operations personnel updated the WO data base for this test with
the correct TS surveillance references.
'
Unit 2 boric acid transfer pump operational test.
The inspector found that the test was properly conducted.
05
Operator Training and Qualification
O.5.1 Observation of Trainina for Abnormal Heater Drain System O_peration
a.
Inspection Scope (71707)
The inspectors observed meetings and training associated with the planned online
maintenance on the Unit 1 combined heater drain tank level control
Valve-HV-2592.
b.
Observations and Findinas
j
On June 17, Valve 1-HV-2592 failed to maintain control of the heater drain tank
levels for both tanks. Operators determined that the valve would only cycle
between 75 to 100 percent open. Subsequently, heater drain tank levels began to
i
i
decrease and operators took actions to throttle the heater drain pump discharge
manual isolation valves in order to maintain tank levels in the normal band.
On June 18, licensee management decided to repair the heater drain tank combined
outlet valve at power. Numerous discussions took place concerning the best plant
i
configuration in which to work the valve. The two options discussed were to
remain at 100 percent power or down power to approximately 70 percent and
remove the heater drain pumps from service. Both options involved some risks.
Initially, the operations supervisor decided that the preferred method would be to
reduce power in order to minimize any secondary plant transients. A draft
procedure was written to manually control heater drain tank levels while reducing
i
reactor power.
The inspectors observed operations personnel in the simulator performing the draft
procedure with various training and management personnel observing plant and
personnel recponse. The inspectors observed good discussions concerning the
proposed impact of power changes to the heater drain systems and actions to be
taken in case of unexpected loss of heater drain tank levels. The shift manager and
the operations supervisor stressed to the simulator crew that the downpower should
proceed slowly with good coordination between the reactor operator and the
.-
. . . _ . - .- .
...
__. __-
.-
-.
.
- .
- . - -
.
.
-4-
operator maintaining heater drain tank levels. Operators were able to easily control
heater drain tank level using the draft procedure.
,
Work on Valve 1-HV-2592 was scheduled for later that evening based on the arrival
of parts. - Prior to commencing the work, the inspectors were informed that the
i
decision was made to work on the valve at 100 percent power. The operations
supervisor stated that this decision was reached after determining that the heater
drain tank level could be controlled at 100 percent power. The operations
supervisor indicated that performing the evolution at 100 percent could cause a
more severe secondary transient if one were to occur, however, he did not want to
unduly challenge the operators by intentionally varying mass flow inputs to the
heater drain tanks and possibly inducing a secondary transient.
The valve work was completed at approximately 11 p.m. without any operational
,
problems. The inspectors reviewed the temporary modification used to gag open
i
Valve 1-HV-2592 and the procedure used to control heater drain tank levels. Tank
,
levels were maintained by throttling the manual discharge valves and controlling
tank recirculation flow. The inspectors determined that the modification and
4
procedure change were appropriate.
1
'
c.
Conclusions
The inspectors concluded that operations management used appropriate judgment in
,
performing the heater drain tank valve maintenance at 100 percent power. The use
'
of the simulator prior to the maintenance activity was a good practice.
08
Miscellaneous Operations issues (92901)
1
08.1 (Closed) Unresolved item 50-446/9601-01: operation of Unit 2 at greater than
100 percent power. After further review, the staff concluded that operating Unit 2
at greater than 102 percent was a violation of TSs. TS 6.8.1 requires the licensee
to establish, implement, and maintain procedures covering the activities referenced
in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978. Appendix A
requires general plant operating procedures for power operation, startup and
shutdown of safety-related systems, and conducting maintenance. Integrated Plant
Operating Procedure Number IPO-0038, " Power Operations," Revision 2,
Section 5.5, stated, in part, that thermal power shall not exceed 102 percent.
Contrary to this requirement, the licensee operated Unit 2 above 102 percent
thermal power on February 14,1996, from approximately 10:10 a.m. to 10:40 a.m.
(50-446/9715-01).
The inspectors also concluded that Instrument and Control Manual Instruction
ICl-4126B, " Calibration Condensate Pumps Discharge Header Pressure
Channel 2240 [ sic)," was inadequately written in that the procedure allowed
calibration of Channel 2240 while in Mode 1 and did not take provisions to prevent
or mitigate the effects of a loss of feedwater heaters. Performing the instruction in
.
.
-5-
Mode 1 caused a loss of feedwater heaters and contribugt -' to operating Unit 2
above 102 percent.
W
The inspectors reviewed the corrective actions listed in NRC Inspection Report
Numbers 50-445(446)/9601 and 50-445(446)/9604, and in TU Electric Letter
TXX-96075 dated March 25,1996. The inspectors found the corrective actions
reasonable and complete.
II. Maintenance
M1
Conduct of Maintenance
M 1.1 General Comments
a.
Inspection Scope (62707)
The inspectors observed all or portions of the following work activities:
Unit 1 inverters IV1C2 and IV1C3 troubleshooting
Unit 2 Floor Drain Tank 2 cleaning
Unit 2 containment preoutage modifications
Unit 2 Train B emergency diesel generator governor design modification
installation
Unit 2 N16/Tave (Protection Sat IV) analog channel operational test
Control room air conditioning condenser component cooling water return
valve motor operator rebuild
Laundry holdup and monitor tank cleaning
b.
Observations and Findinas
The inspectors found the work performed under these activities professional and
thorough. Specific details are listed below.
M1.2 Troubleshootina on Inverters IV1C2 and IV1C3
a.
Inspection Scope (62707)
The inspectors reviewed the troubleshooting plan and observed portions of the
troubleshooting activities performed on the two inverters.
b.
Observations and Findinas
Troubleshooting was conducted in an attempt to determine the cause of the
inadvertent transfer of the inverters to their bypass power source during battery
. _ .
.
- .-
. - -
~
-.
.-
_ - _ - - -
.
1
.
-6-
charger swapping. On several occasions, the inverters transferred to bypass power
without any indication of abnormal conditions.
,
,
The inspectors reviewed the troubleshooting plan and found that the plan was very
l
detailed and gave detailed instructions regarding actual troubleshooting. The plan
also specified precise equipment lineups and configuration changes.
'
,
Prior to performing the troubleshooting, the shift manager briefed operations and
maintenance personnel on the overall scope of the work activity. Precautions and
limitations were discussed and an emphasis was placed on ensuring a safe and
2
controlled evolution.
i
Both operations and maintenance personnel used excellent self-checking and peer-
checking techniques prior to component manipulation. Operations and mairitenance
supervisors were present and provided appropriate oversight.
.
As a result of information obtained during the troubleshooting, the licensee planned
to change battery charger operating procedures and to replace the battery charger
capacitors.
4
c.
Conclusions
The inverter troubleshooting plan was detailed and was indicative of a well prepared
strategy. The operators and technicians demonstrated excellent skills and carefully
performed each task of the troubleshooting plan.
,
j
M1.3 Rebuild of Control Room Air Conditioner Motor Operated Valve
a.
Inspection Scope (62707)
The inspector observed partial performance of the refurbishment of
Valve X-PV 3584-MO, control room air conditioning Unit X-02 refrigerant condenser
component cooling water return pressure control valve.
'
b.
Observations and Findinas
On June 8, the inspector observed two technicians overhaul the motor operator
j
'
ectuator and gearhead assembly for Valve X-PV-3584-MO. The technicians
performed a detailed inspection of allinternal components and either replaced or
!
repaired damaged components. Slightly damaged components (burrs, scratches,
J
etc.) were reworked using excellent work practices.
. A quality control inspector inspected new and reused components associated with
the motor operator actuator. The inspection was cursory and not as meticulous as
the inspection performed by the technicians, however, the inspector determined
,
that the quality control inspector did an adequate inspection of the parts.
i
_ . _ _ _
_
_ _ _ _ _ _ .
.
.
l
7
-
The inspector reviewed Technical Manual 661-76268-003, "Limitorque Operation
and Maintenance Manual and Bulletins," and determined that appropriate
maintenance guidance had been incorporated into Procedure MSE-CO-8805.
<
c.
Conclusions
4
'
The technicians performed in an excellent manner during a very detailed
refurbishment of Valve X-PV-3584-MO.
i
M4
Maintenance * Staff Knowledge and Performance
"
M4.1 Containment Entry (71707 and 92902)
On June 25, the inspector observed ongoing preoutage modification work inside the
Unit 2 Containment. This included observing the logging of materialin and out of
.
containment using Form STA-625-1, " Material / Accountability Log," and the
!
containment closeout process per Procedure STA-620, " Containment Entry,"
'
Revision 11. The inspector also observed radiation protection personnel monitoring
radiation levels in the work areas, and logging stay times for recording neutron
doses as required per Procedure RPI 515, " Neutron Dose Measurement and
Recording," Revision 8. In interviewing several workers, the inspector found all
workers were aware of the recent revision to STA-620 and knowledgeable of the
changes made in response to a violation of containment entry procedures identified
in NRC Inspection Report 50-445(446)/97-14.
Ill. Enaineerina
E2
Engineering Support of Facilities and Equipment
'
E2.1
Containment Pressure Relief System
.
l
a.
Inspection Scone (37551)
The inspector reviewed the TS and design basis for the containment pressure relief
system. In addition, the inspector interviewed various licensee personnel
concerning the operation and maintenance of the system.
4
b.
Observations ano Findinas
While reviewing operating logs, the inspector determined that both Units 1 and 2
containments were being vented every 3 to 4 days for periods lasting approximately
-
6 to 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />. On average, this would equate to approximately 600 hours0.00694 days <br />0.167 hours <br />9.920635e-4 weeks <br />2.283e-4 months <br /> per year.
The inspector reviewed TS 3.6.1.7 and determined that the licensee appropriately
4
implemented the TS. NUREG-0797, " Safety Evaluation Report related to the
4
4
.
_
. _ _
___
_ ._
_
.
__.
.
__ __ _ _.
.
L
.
.
-8-
operation of Comanche Peak Steam Electric Station, Units 1 and 2," Section 6.2.3,
determined that the use of the containment pressure relief system was limited to 90
!
hours of operation per year. Followup conversations with engineering personnel
identified that this was changed during licensing as a result of standard TS 3.6.1.8
which allowed containment purge valves with diameters of 3 inches or less to be
.
open continuously. The licensee installed an orifice plate that effectively limited the
pipe diameter to 3 inches. Based on this change, the approved TS allows the
'
containment pressure relief valves to be open continuously.
NUREG 0797, Supplement 23, Section ll.E.4.2, ensured that the valves could shut
j
against containment design pressure without damaging the pressure relief
,
containment isolation valves by limiting travel to 65 degrees open. Design Basis
'
Document DBD-ME-301, " Containment Air Cleanup Systems," Revision 7, also
stated that the valves were limited in travel to 65 degrees open.
!
,
Maintenance personnel reviewed Procedures MSM-CO-6500, " Matrix Actuator
Maintenance with Master Operator", Rev.1 and MSM-CO-8600, "Posi-Seal
Trunnion Valve Maintenance", Rev.1, both associated with the maintenance for
these valves, and could not find any reference to a mechanical stop which limited
disc travel. The inspector reviewed the technical manual and Valve Drawings
14758-2 (1-HV- 5548 and 5549) and 14759-2 (2-HV-5548 and 5549) and did not
i
identify any reference to the mechanical stop. On June 16, the system engineer
identified that DCN 906 was implemented for Unit 1 to limit valve travel to 65
degrees open, however, the modification was not referenced on Unit 2 Valve
Drawing 14759-2.
!
The inspector reviewed DCN 906 and preoperational test data and determined that
the mechanical stops had been installed on both units for the pressure relief
'
containment isolation Valves 1-HV-5548,1-HV-5549, 2-HV-5548, and 2-HV-5549.
The test data verified that valve travel was limited to 65 degrees open. The
inspector was concerned that the valves may have been reworked or replaced since
initial installation and possibly that the mechanical stop was not installed. Licensee
personnel searched the maintenance history data base and determined that the air
i
actuators for the valves had not been replaced or reworked.
Subsequent to this finding, licensee personnel initiated DCN 11370, Revision 0, to
document that Unit 2 Valves 2-HV-5548 and 5549 were limited to 65 degrees open
,
by a mechanical stop. In addition, Procedures MSM-CO-6500 and MSM-CO-8600
,
l
were revised to reflect that valve travel was limited to a meximum of 65 degrees
'
open. The corrective actions were determined to be appropriate and complete.
10 CFR Part 50, Appendix B, Criterion lil, states in part that measures shall be
)
established to assure that the design basis, as defined in Part 50.2 and as specified
1
,
i
in the license application, is correctly translated into specifications, drawings,
procedures, and instructions. Design changes, including field changes, shall be
subject to design-control measures commensurate with those applied to the original
[
.
f
.
.
I
9
design and approved by the organization that performed the original design. The
failure to update Valve Drawing 14759-2 or to have procedures in place describing
the mechanical stop is a violation of 10 CFR Part 50, Appendix B, Criterion ill
(50-446/9715-02).
c.
Conclusions
The inspector identified a violation wherein the licensee failed to update design
drawings and procedures for a design change which limited the travel of the Unit 2
containment pressere relief containment isolation valves.
E3
Engineering Procedures and Documentation (92903)
E3.1
Main Steam Penetration Area Temoeratures
a.
Inspection Scope (37551)
)
The inspectors reviewed selected areas of routine shift tog taking for compliance
with TS 3/4.7.10, " Area Temperature Monitors." The inspectors measured selected
component temperatures and air temperatures in the Unit 1 main steam penetration
areas.
b.
Observations and Findinas
TS Surveillance Requirement 4.7.10 requires that the temperature in each of the
areas shown in Table 3.7-3 be determined to be within its limit at least once per 12
hours. Table 3.7-3 lists the maximum temperature limit of normal safeguards
buildings areas under normai conditions to be 104*F. The main steam penetration
areas and the feedwater penetration areas are in normal safeguards buildings areas
and are therefore subject to the 104 *F maximum temperature limitation.
Operations Testing Manual Procedures OPT-102A, Revision 8, (Unit 1) and
OPT-1028, Revision 2, (Unit 2), " Operations Shiftly Routine Tests," implemented
i
Surveillance Requirement 4.7.10. Procedure OPT-102 required that Temperature
Indicators 1-TI-5624 (Unit 1) and 2-TI-5624 (Unit 2) be recorded to determine that
the main steam penetration area temperatures were within their limit.
The inspectors found that Temperature Indicators 1-TI-5624 and 2-TI-5624
measured the bulk room air temperatures of the main steam penetration area and
the feedwater penetration areas after the air had been mixed in a common exhaust
duct and were located approximately 20 feet in adjoining rooms. The air
temperature in the Unit 1 adjoining room was measured to be approximately 20 F
cooler than the measured temperature. The inspectors concluded that the location
l
of the indicators may not be representative of the actual conditions in each of the
areas.
i
i
,
. _ .
-
.
l
,
.
-10-
The inspectors measured the ambient air temperatures and selected component
temperatures in the Unit 1 main steam penetration areas. While most of the air
temperatures were less than the limit, the air temperatures of equipment associated
with Steam Generator 1-01 were approximately 5 to 6 F above the normal
conditions limit of 104 F. Measured locations were selected to be away from hot
steam piping and out of the direct path of ventilation. An exhaust plenum contact
j
temperature of 110 F from this area validated the measurements from the selected
l
locations. During this time, Temperature Indicator 1-TI-5624 indicated that the bu!k
air temperature from the main steam penetration areas and feedwater penetration
areas was approximately 102 F.
During meetings with engineering personnel, they stated that the environmental
4
'
qualification temperature and component life were based on the conservative
assumption that the components experienced the temperatum 'imit continuously.
They also explained that temperatures of the measured areas and components
fluctuated with environmental conditions and typically approached TS limits only
I
during the late af ternoon of the summer months. Based on this conservative
assumption, the licensee concluded that operability was not affected. However, the
licensee did initiate an Operations Notification and Evaluation (ONE) form to review
the environmental qualification program measurement techniques and assumptions.
The inspectors concluded that Procedures OPT-102A and OPT-102B did not
I
adequately implement the surveil!ance requirement in that the location of the
l
temperature indicators in common exhaust ducts prevented the licensee from
j
determining that the temperature of each area was within the limit. Area
!
temperatures in excess of the limit would not be identified if the exhaust air flows
I
from other areas were sufficiently greater than or cooler than that from the affecei
area. The failure to adequately implement the requirements of Surveillance
Requirement 4.7.10 in Procedures OPT-102A and OPT-102B is a violation of 10
j
CFR Part 50, Appendix B, Criterion V (50-445(446)/9715-03).
I
c.
Conclusions
The inspectors determined that the surveillance procedures did not adequately
implement TS Surveillance 4.7.10, in that, a common exhaust duct temperature
detector provided temperature measurement for two different safeguard building
areas (main steam and feedwater penetration areas).
]
l
l
E6
Engineering Organization and Administration
E6.1
Operational Review Subcommittee Meetina
!
l
The inspectors attended a presentation on the axial offset anomaly given to
members of the maintenance and engineering Operational Review Subcommittee.
The presentation focused on measures to reduce the anomaly during the current
operating cycle and on redesign of the Unit 2 Cycle 4 core (October 1997 refueling
_
-
.
-
..
-.
.
.
,.
-11 -
.
outage) to minimize axial offset. The presentation was informational and the
subcommittee members openly participated.
IV. Plant Support
3
R1
Radiological Protection and Chemistry Controls
R 1.1 Tour of Auxiliary Buildina
l
a.
Inspection Scope (71707 and 71750)
4
The inspectors performed a tour of the radiation controlled area (RCA) to verify that
areas were properly posted for given radiological conditions and to observe
radiological practices.
,
i
.
I
b.
Observations and Findinas
The inspectors found that areas were properly posted and that overall radiological
housekeeping was very good, however, during the walkdown of Room X-213, a
radioactive material storage area, the inspector identified a pump hose with a
contact dose rate of 4.5 mrem / hour. The hose did not have a radioactive material
tag attached. Procedure STA-652, " Radioactive Material Control," Revision 7,
Section 6.6 specified that a radioactive material tag should (management
expectation) be attached to equipment with a contact dose rate greater than
2 mrem / hour. In addition, the hose ends were not taped closed or capped which
i
was also contrary to a management expectation as stated in Procedure STA-653,
" Contamination Control Program," Revision 6, Section 6.5.
A radiation protection technician immediately attached a radioactive material tag
and tapped the hose ends. ONE Form 97-693 was initiated to document these
discrepancies.
On July 2, while exiting the RCA, the inspectors observed a small article monitor
(SAM) alarming with low activity indicated. A radiation protection technician
opened the monitor and picked up the flashlight without wearing protective gloves.
Subsequent frisking of the flashlight indicated no contamination. The inspectors
discussed the practice of not using gloves to pick up potentially contaminated items
with the technician and a radiation protection supervisor both of whom indicated
that this was a poor practice.
On July 16, while exiting the RCA, the inspectors observed another poor
radiological work practice associated with the use of the SAM. The SAM alarmed
on low activity and the individual removed his design modification package with a
gloved hand; however, he opened the package and removed severalitems with his
ungioved hand and placed the items back in the SAM. Allitems were determined to
_.
.
-
.
4
.
-12-
,
-
be clean. The inspectors discussed this poor work practice with the individual and
a radiation protection technician.
c.
Conclusions
Overall, radiological housekeeping was very good; however, four examples of poor
radiological work practices were identified by the inspector.
S1
Conduct of Security and Safeguards Activities (71750)
S 1.1
Physical Security
a.
Insnection Scope (71750)
Using Inspection Procedure 71750 during routine tours in the protected and vital
areas, the inspector observed various aspects of physical security.
b.
Observations and Findinas
On June 16, the inspector observed security officers performing normal access
control to the protected area. Security officers were found to be knowledgeable of
the requirements for access control to the protected area during emergencies for
NRC employees, emergency response personnel, and emergency vehicles. The
inspector independently verified that licensee designated vehicle numbers of several
licensee designated vehicles in the protected area were on the authorized vehicle
access list. No keys were found in unattended vehicles in the protected area,
c.
Conclusions
The inspector concluded that access control was properly implemented and security
personnel demonstrated a good working knowledge of the requirements for
emergency access control.
S3
Security and Safeguards Procedures and Documentation
S3.1
Access Authorization
a.
Inspection Scope (71707 and 71750)
During a routine review of ONE Forms, the inspector identified a concern with
access authorization.
b.
Observations and Findinas
ONE Form 97-650 identified that on June 20, the licensee discovered that a key
card was not deactivated per the request of the fitness for duty coordinator.
u
-- .
- _ .
--
.
-
~ _ . - .
. - . -
-
_ - . - . . - -
. - .
.
.
.
-13-
-
1
Security manual records indicated that the badge was deactivated on May 19,
i
however, the individual entered the protected area three times after May 19. ONE
j
Form 97-676 identified that on June 27, another instance was discovered where a
j
key card was not deactivated per the request of the fitness for duty coordinator.
Security logs indicated that the badge was deactivated on June 25, however, the
individual entered the protected area on June 27.
.
The key cards were deactivated because the individuals were infrequcntly onsite
'
and not available for their scheduled fitness for duty test. Procedure STA-910,
" Fitness for Duty Program," Revision 2, Section 6.8.4.7, required that if an
,
individual is unavailable for random testing because he or she is only onsite
occasionally, their access shall be deactivated until a urine specimen is provided.
The security manager indicated that a computer software problem allowed these
events to occur. If data was entered and not updated within approximately 90
seconds, then the computer data base was not updated. Followup conversations
,
I
with the security manager identified that the software was modified to prevent this
from recurring and that positive verifications of data base information was required
j
'
for all key card deactivations. The inspector reviewed Security instruction 3.13,
'
" Key Card Control," Revision 7, and determined that the changes, as described by
the security manager, were incorporated into the procedure. The inspector
determined that the corrective actions taken by the licensee were prompt and
should prevent recurrence.
In addition, the manager stated that no other examples were identified where fitness
I
for duty testing access authorization were not properly deactivated. When
!
questioned about reviewing deactivation of access authorization for other issues,
j
the security manager stated that they had not looked generically at the issue;
however, after reviewing all of the key card deactivations for the prior 12 months,
no other instances were identified.
1
Technical Specification 6.8.1 requires that written procedures be established,
implemented, and maintained covering the activities recommended in Regulatory
Guide 1.33, Revision 2, Appendix A. Regulatory Guide 1.33, Appendix A, Section
1.a, recommends that procedures be written covering security and visitor control.
This licensee-identified and corrected violation is being treated as a Noncited
Violation, consistent with Section Vll.B.1 of the NRC Enforcement Policy
(NCV 50-445(446)/9715-04)
J
c.
Conclusions
'
.
A computer software problem contributed to two individuals entering the protected
'
area when their key cards should have been deactivated. The failure to deactivate
the two key cards was identified as a noncited violation.
i
,
- .
. - _ - - . - - . . - . -
-
.
.
-14-
S4
Security and Safeguards Staff Knowledge and Performance
S4.1
Failure to Reset Security Alarm (71750 and 92904)
At approximately 5:17 p.m. on June 25, the licensee identified that the security
alarm on the Unit 2 personnel containment hatch had not been reset, as required by
Security instruction 3.10, " Alarm Stations," Rev. 9, prior to releasing the security _
compensatory officer after containment closecut, at 4:25 p.m. Upon discovery, the
central alarm station operator immediately reset the alarm and the licensee reported
a 1-hour Reportable Safeguards Event to_the NRC per 10 CFR 73.31(a)(1). Security
j
personnel verified that both the Security and Radiation Protection containment hatch
i
padlocks were in place, and walked down the RCA and found no unauthorized
personnel or activity. A review of control room alarms, security access logs, and
sector reports revealed no unauthorized entries. The licensee determined that there
was no opportunity for unauthorized or undetected access, and no such access had,
in fact, occurred because (1) both containment hatch padlocks were verified to be
iocked and in place and (2) no door alarms (independent of the security alarm) were
received in the control room. Based on this the licensee determined that this event
was only required to be logged, and retracted the 1-hour report. Security
management issued immediate instruction to emphasize the requirement for alarm
station operators to reset alarms prior to releasing compensatory officers.
The failure of the central alarm operator to reset the alarm prior to releasing the
,
compensatory officer is considered to be a violation of procedure of minor
significance and is being treated as a Noncited Violation, consistent with Section IV
of the NRC Enforcement Policy (NCV 50-445(446)/9715-05).
F4
Fire Protection Staff Knowledge and Performance
j
F3.1
Inadeauate Imolementation of Fire Protection Proaram Reauirements
a.
Insoection Scope (71707. 71750)
,
4
The inspectors observed work associated with the cleaning of Unit 2 Floor Drain
Tank 2 conducted in accordance with WO 3-97-318184-01. The inspectors
reviewed the work package for adherence to procedures, and held discussions with
licensee personnel. The inspector reviewed the Fire Protection Report to
independently determine the effect of the work on Unit 2 fire protection barriers.
b.
Observations and Findinas
i
On June 19, the inspector observed the removal of liquid waste and associated
drain tank cleaning equipment from Room 2-061, elevation 773, to Room 2-070,
elevation 790, in the Unit 2 safeguards building. The work required the removal of
a floor plug on elevation 790. The inspector noted that the STA-738, Form 2, " Fire
Protection System / Equipment impairment Form," in the work package had been.
L
-
. __
__
.__
. _ _ _ .
_ _ _ . _ _ _ .
_
_ . -
_
.
.
!
-15-
l
crossed out and marked as not applicable. In questioning fire protection personnel,
l
the inspectors were informed that Form STA-738-2 was not necessary because
Rooms 2-061 and 2-070 were in the same fire area. The inspectors independently
reviewed fire area boundaries shown on Figures FPR-25 sheets 1 and 2 of the Fire
i
Protection Report and found that Rooms 2-061 and 2-070 were in different fire
l
areas and, therefore, the removal of the floor plug breached a fire barrier. Upon
identification by the inspectors, the licensee established the required compensatory
I
'
measures and initiated a ONE form. The licensee's investigation found that
Form STA-738-2 was incorrectly processed due to human error when a fire
protection technician reviewed fire protection drawings for Unit 1 rather than
Unit 2.
in reviewing ONE forms, the inspectors noted two ONE forms having recently been
,
(
written on fire impairment issues. The inspectors requested a listing of all ONE
forms written on fire impairrnents in the last 6 months and found similar errors. On
March 15, the licensee failed to initiate the required compensatory measures prior to
impairing a fire assembly when a concrete floor plug was removed from the 810
elevation of the Fuel Building. On' July 16, the licensee again f ailed to establish
compensatory measures prior to impairing a fire area assembly when a concrete
,
!
floor plug was removed from the 810 elevation of the Unit 1 Safeguards Building.
The inspectors found that the licensee failed to follow procedure on three separate
occasions when fire assemblies were impaired prior to implementing compensatory
measures as required by procedure S. A-738. In addition, the inspectors found that
corrective actions for a previous failure to be very limited in scope and ineffective to
(
prevent recurrence.
TS 6.8.1.h states, in part, that written procedures covering fire protection program
implementation be established and implemented. Procedure STA-738, " Fire
l
Protection Systems / Equipment impairments," Revision 5 required that any fire
l
protection systern/ equipment needing to be impaired to support work activities shall
have a Fire Protection impairment Form STA-738-2 initiated and the necessary
compensatory measures put in place prior to the item being impaired. The failure to
'
,
establish compensatory measures prior to impairing fire area assemblies is a
l
violation of TS 6.8.1.h (50-445(446)/9715-06).
i
c.
Conclusions
The f ailure to establish compensatory measures prior to impairing a fire area
assemblies as required by procedure on three occasions is a violation of TS 6.8.1.h.
,
l
V
r-'
.
9
.
I
i
16-
!
!
V. Manaaement Meetinas
i
X1
Exit Meeting Summary
The inspector presented the results of the inspection to members of licensee management
,
at the conclusion of the inspection on July 25,1997. The licensee acknowledgad the
findir'gs presented. No proprietary information was identified.
l
l
'
!
!
!
'
I
,
i
)
>
l
[
l
i
!
!
l
f
I
.
.
ATTACHMENT
SUPPLEMENTAL INFORMATION
PARTIAL LIST OF PERSONS CONTACTED
Licensee
Curtis, J. R., Radiation Protection Manager
Davis, D. L., Nuclear Overview Manager
Killgore, M. R., Nuclear Enginee ing Manager
Lancaster, B. T., Plant Support Manager
Moore,.D. R., Operations Manager
,
Terry, C. L Group Vice Presidcot, Nuclear Production
Walker, R. D., Regulatory Affairs Manager
INSPECTION PROCEDURES USED
37551
Onsite Engineering
61726
Surveillance Observations
62707
Maintenance Observations
71707
Plant Operations
71750
Plant Support Activities
92901
Followup - Operations
j
92902
Followup - Maintenance
92904
Followup - Plant Support
ITEMS OPENED. CLOSED. AND DISCUSSED
Opened
50-446/9715-01
Operation in excess of 102 percent thermal power
(Section 08.1)
50-446/9715-02
Failute to update valve drawing or to have procedures
in place describing the mechanical stop (Section E2.1)
50-445(446)/9715-03
Inadequate surveillance procedure (Section E3.1)
50-445(446)/9715-04
Failure to deactivate key cards (Section S3.1)
J
e
.
C'
,
s
.
.
2-
50-445(446)/9715-05
Failure of the central alarm operator to reset the
containment personnel airlock alarm prior to releasing
the compensatory officer (Section S4.1)
50-445(446)/9715-06
Failure to establish compensatory measures prior to
impairing a fire protection assembly (Section F3.1)
Closed
50-446/9601-01
Operation of Unit 2 at greater than 100 percent power
(Section 08.1)
50-445(446)/9715-04
NCV Failure to deactivate key cards (Section S3.1)
50-445(446)/9715-06
NCV Failure to establish compensatory measures prior to
impairing a fire protection assembly (Section F3.1)
LIST OF ACRONYMS USED
IFl
inspection followup item
noncited violation
ONE
Operations Notification and Evaluation
'
Public Document Room
radiation controlled area
small article monitor
TS
Technical Specification
unresolved item
violation
Work Order