d'~cA dLat4d d TECHNICAL EVALUATION REPORT MASONRY WALL DESIGN VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNITS 1 AND 2

-w w--

NRC DOCKET NO. 50-338 FRC PROJECT C5606 NRC TAC NO. 42895 FRC ASSIGNMENT 6 NRC CONTRACT NO. NRC43-81 130 FRC TASK 239 Prepared by Franklin Research Center Author:

A. K. Le, V. N. Con 20th and Race Street Philadelphia, PA 19103 FR~C Group Leader: V. N. Con Prepared for Nuclear Regulatory Commission Washington, D.C. 20555 Lead NRC Engineer: N. C. Chokshi March 22, 1985 This report was prepared as an account of work eponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, or any of their employees, makes any warranty, expressed or implied, or assumes any legal liabHity or responsibility for any third party's use, or the results of such use, of any Ir. formation, appa.

ratus, product or process disclosed in this report, or representa that Itt use by such third party would not infringe privately owned rights.

gs/32hW3 3O PP X&

FRANKUN RESEARCH CENTER OtYt90N OF ARVIN/CALSPAN 20tn & RACE STREITS,PHitADELMilA PA 19103

TECHNICAL EVALUATION REPORT MASONRY WALL DESIGN VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNITS 1 AND 2 NRC DOCKET NO. 50-338 FRC PROJECT C550C NRC TAC NO. 42895 FRC ASSIGNMt!NT6 NRC CONTR ACT NO. NRC-03-81 130 FRC TASK 239 Prepared by Franklin Research Center Author:

A. K. Le, V. N. Con 20th and Race Street Philadelphia, PA 19103 FRC Group Leader: V. N. Con Prepared for Nuclear Regulatory Commission Washington, D.C. 20555 Lead NRC Engineer: N. C. Chokshi l' arch 22, 1985 This report was prepared as an account of work sponsored by an agency of the United States Government.'Neither the United States Government nor any agency thereof, or any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibility for any third party's use, or the results of such use, of any information, appa-ratus, product or process disclosed in this report, or represents that its use by such third party would not Infringe privately owned rights.

Prepared by:

Reviewed by:

Approved by:

&Y Vs Ustt (1%

h Principal Author:

Group Leader D'epartment Di ectok Date: 3. 2 /- 85~

Date: 3 - 2. / - f[

Date:

3-2 9i FRANKLIN RESEARCH CENTER D(VISCN OF ARVIN/ CAL $ PAN 20th & RACE STREETS, PHILADELPHIA,PA 19103

\\

TER-C5506-239 CONTENTS Section Title Page 1

INTRODUCTION 1

1.1 Purpose and Scope

1 1.2 Generic Issue Background 1

1.3 Plant-Specific Background.

1 2

REVIEW CRITERIA 3

3 TECHNICAL EVALUATION 4

3.1 Evaluation of Licensee's Criteria.

4 3.2 Evaluation of Licensee's Approach to Wall Modifications.

13 4

CONCLUSIONS.

14 5

REFERENCES.

15 APPENDIX A - SGEB CRITERI A POR SAFETY-RELATED MASONRY WALL EVALUATION (DEVELOPED BY THE STRUCTURAL AND GEOTECHNICAL ENGINEERING BRANCH (SGES] OF THE NRC)

APPENDIX B - SKETCHES OF WALL MODIFICATIONS 1.,

iii

TE R-C 5 506-239 POREWORD This Technical Evaluation Report was prepared by Franklin Research Center under a contract with the U.S. Nuclear Regulatory Commission (Office of Nuclear Reactor Regulation, Division of Operating Reactors) for technical assistance in support of NRC operating reactor licensing actions. The technical evaluation was conducted in accordance with criteria established by the NRC.

v

i 9

e TE R-C 5506-239 1

1.

INTRODUCTION l

1.1 PURPOSE OF REVIEW The purpose'of this review is to provide a technical evaluation of the Licensee response to IE Bulletin 80-11 (1) with respect to compliance with the Nuclear Regulatory Conimission (NRC) masonry wall criteria.

In addition, if the Licensee plans repair work on masonry walls, the planned methods, and procedures are reviewed for acceptability.

1 1.2 GENERIC ISSUE BACKGROUND In the course of conducting inspections at the Trojan Nuclear Plant, Portland General Electric Company determined that some concrete masonry walls did not have adequate structural strength.

Further investigation indicated i

that the problem resulted from errors in engineering judgment, a lack of established procedures and procedural details, and inadequate design criteria. Because of the implication of similar deficiencies at other operating plants, the NRC issued IE Bulletin 80-11 on May 8, 1980.

IE Bulletin 80-11 required licensees to identify plant masonry walls and their intended functions.

Licensees were also required to present reevaluation criteria along with the analysis results of all safety-related walls.

If modifications were proposed, licensees were to state the methods and schedules

)

for the modifications.

1.3 PLANT-SPECIFIC BACKGROUND In response to IE Bulletin 80-11, Virginia Electric and Power Company

]

submitted to the NRC letters with attachments dated from July 7,1980 through September 14, 1981 (2-10) describing the status of masonry walls at North Anna Power Station Units 1 and 2.

The information in these letters was reviewed, and requests for additional information were sent to the Licensee. The Licensee responded to these requests on July 15, 1982 (11), November 16, 1982 (12), and October 26, 1984 (13).

The North Anna plant has approximately 398 single-or multi-wythe walls.

The Licensee identified 70 walls as safety-related according to IE Bulletin 80-11.

The working stress method was used to __

TE R-C 5 506-239 l

qualify tne walls, and 37 walls were found acceptable. Two walls were acceptable after equipment was removed from the wall, and 16 walls were modified. The remaining 15 walls in the fuel building were not acceptable j

under extreme loading cases; they have been removed and replaced with "blow-of f" metal siding attached to a steel girt system, which reduced the

]

total numbers of safety-related walls to 55.

The issues associated with these 15 walls have been resolved in the NRC staff Safety Evaluation Report which addressed the spent fuel pool expansion issue. All masonry walls are unreinforced except for horizontal joint reinforcement. Some walls are hollow, others are solid masonry blocks.

Masonry wall types and materials for North Anna Power Station Units 1 and 2 are given below:

Wall Types:

Total number of walls 398 Safety-related walls 55 Walls requiring modifications 16 Wall Functions:

partition, fire protection, shielding Construction Materials:

Hollow masonry units ASTM C90 and ASTM C129 Solid masonry units ASTM C145 Mortar Type S, M, or N i

~.

~. -.

e TER-C5506-239 2.

REVIEW CRITERIA The basic documents used for guidance in this review were the criteria developed by the Structural and Geotechnical Engineering Branch (SGEB) of the NRC (attached as Appendix A to this report), the Uniform Building Code (15),

and ACI-531-79 (16).

In general, the materials, testing, analysis design, construction, and inspection of safety-related concrete masonry walls should conform to the SGEB criteria (14].

For operating plants, the loads and load combinations for qualifying the masonry walls should conform to the appropriate specifications in the FSAR for the plant. Allowable stresses are specified in Reference 16, and the appropriate increase factors for abnormal and extreme environmental loads are given in the SGEB criteria ( Appendix A)..

l j

l TER-C5506-239 3.

TECHNICAL EVALUATION This evaluation is based on the Licensee's earlier respanses [2-10) and subsequent responses [11-13) to the requests for additional information. The 1

Licensee's criteria [4, 10] were evaluated with regard to the design and j

analysis method, loads and load combinations, allowable stresses, construction specifications, materials, and relevant test data.

The Licensee's response to j

the requests for additional information was also reviewed.

3.1 EVALUATION OF LICENSEE'S CRITERIA The Licensee reevaluated the masonry walls at the North Anna plant using 1

the following criteria:

Allowable stresses are based on the Uniform Building Code [15] and ACI o

531-79 [16) o Load combinations are according to the FSAR, which includes dead loads and seismic loads 1

o The working stress design method of analysis is used j

i Masonry walls are reevaluated for earthquake on the basis of i

o determining the effects of inertial loads, equipment loads, and l

interstory displacement effects. The spectral approach is used along with the following criteria l

2% damping is used for unreinforced walls for operating basis I

earthquake (OBE) i 4% damping is used for unreinforced walls for safe shutdown earthquake (SSE)

I To account for variations in material properties and assumed boundary conditions, the seismic response of masonry walls will be calculated using amplified response spectra for which the peak has been broadened.

Equipment loads are calculated based on a load distributed uniformly over part or all of the area of wall, depending on the arrangement of the supports.

The result may be applied as a single concentrated load or a line load, as appropriate Interstory displacements are imposed on the wall, where required, and its effects accounted for in the reevaluation analysis o The walls are modeled as beams or plates.,

l TER-C5506-239 o Independent laboratory testing was performed on masonry materials to assure compliance with the applicable ASTM specification for compressive strength and absorption.

Other than those areas identified in Section 4,.the Licensee's criteria have been reviewed and found to be technically adequate and in compliance with the SGEB criteria. The review of the Licensee's response to the request for additional information follows.

Request 1 Provide and justify the boundary conditions and modeling techniques used for the reevaluation of masonry walls at the North Anna plant and, using sample calculations, indicate how the potential for block pullout was considered at equipment attachments.

Response 1 In response to this request, the Licensee provided sketches to illustrate typical boundary conditions used for the reevaluation of masonry walls at North Anna Power Station Units 1 and 2.

The Licensee also provided types of boundary conditions and their justifications, modeling techniques, and sample calculations for block pullout.

a.

Boundary Conditions l

The boundary conditions were taken as free, fixed, simple, or elastic j

supports. The fol. lowing are the criteria used by the Licensee to determine the boundary conditions:

l 1

o Seismic loads are reversible; therefore, supports had to provide restraint in both directions, o Consideration was given to the relative stiffness of the block wall and its supports.

If a rigid boundary could not be justified for a specific wall, then the analysis included the effect of the support's i

elasticity.

o Shear load transfer mechanisms were only considered at block-to-block and block-to-concrete interf aces.

No shear transfer was considered for block-to-steel interf aces or across expansion joints or compressible materials (free boundary conditions were assumed). '

.o TE R-C 5506-239 o Fixity was considered in the following cases:- ( a) Fixity was used at the base of a block wall built on a concrete slab if a cantilevered wall would exist (i.e., three sides of wall f ree).

(b) At the perpendicular intersection of two block walls, fixity was taken at those corner joints constructed of alternating courses of running bond.

If fixity was taken, then the relative stiffness of the walls had to be accounted for and the reaction was carried into the supporting wall.

For the cantilevered walls, the mortar bed joints at the base cannot be relied upon to prevent rotations of the walls at the base. Some modifications need to be done to assure the moment transfer mechanism takes place at the base. The review of other plants indicated that for a similar situation, some clamping devices are provided at the base to assure the load is transferred properly at the base. See the additional discussion in Response 10.

b.

Modeling Techniques All walls were analyzed based on grid models.

Effects of out-of-plane loads at penetrations from pipe, conduit, or ducts were considered.

c.

Block Pullout The potential for block pullout was considered by development of local block loading criteria including shell face pullout and core pullout. As stated in the sample calculation, an on-site testing program was performed at Surry Power Station on May 8,13,15, and 20,1981.

The test indicated that failure loads for'the 3/8-in & Hilti sleeve anchor failed as a result of excessive slippage of the anchor system; however, the f ailure loads were well above the 350-lb allowable for C-90 block.

Several 1/2-in $ Hilti sleeve anchors had a spall cone failure mechanism.

The smallest load which involved a spall cone failure was 1871 lb, which is well above the 350-lb all,owable load for C-90 block. As a result, the Licensee confirmed that t^e allowable values for block pullout are higher than those calculated.

The Licensee's response is technically adequate and in compliance with the SGEB criteria. -

TER-C 5506-239 Request 2 Using sample calculations, indicate how the ef fects of higher modes of vibration are included in the analysis.

Response 2 The Licensee indicated that walls having high fundamental frequencies away f rom resonance were analyzed using the envelopes of the amplified response spectra (ARS).

For walls having natural' frequencies in the resonant range, a dyriamic analysis was carried out, and the responses due to at least the first ten modes were obtained by the square root of the sum of the squares (SRSS).

A sample calculation for walls having high fundamental frequencies away from resonance was provided. The wall analyzed is 4 ft 6 in wide and 7 ft 4 in high and is constructed by solid blocks 12 in x 8 in x 16 in.

The maximum tensile stresa normal to bed joint due to inertial and equipment load is 4 psi, which is less than the allowable of 40 psi.

In addition, a STRUDL computer program input file was provided which indicated that the Licensee has employed dynamic analysis for walls having natural frequencies in the resonant range. Also, it indicated that the responses of the wall were obtained by the SRSS of at least the first ten modes.

The Licensee's response is adequate and in compliance with the SGEB criteria.

Request 3 Provide sample calculations to show the analytical approach used for obtaining the stresses in single-wythe and multiple-wythe walls.

Response 3 In response to this request, the Licensee indicated that single-wythe walls were analyzed based on conventional beam or plate equations with the boundary conditions and modeling techniques stated in Response 1.

Multiple- _ ___

TE R-C 5 506-239 wythe walls were analyzed in a similar manner except that in-plane shear stresses and out-of-plane tension stresses were censidered to be transfered across the collar joint.

~

With regard to single-wythe walls, sample calculations were provided for an 8-in, hollow, lightweight block wall with the following conditions:

o Two-way slab, a = 8.17 f t, b = 10.27 ft o The wall fundamental frequency is 87.8 cps o Firewall, four sides simply supported o Total attached load on wall is 1483 lb o Accelerations due to earthquake are:

Horizontal SSE = 0.43g Vertical SSE = 0.55g Horizontal OBE = 0.30g Vertical OBE = 0.379 j

o Wall is unreinforced.

The results of the single-wythe sample calculation are listed below.

Type of Stress Calculated Stress Licensee Allowable *

(SSE) 1 Maximum tensile stress 30.81 psi 66.7 psi (parallel to bed joint)

Maximum tensile stress 24.12 psi 35.42 pai (normal to bed joint)

Maximum compressive stress 38.62 psi 298 psi Maximum shear strest 4.82 psi 40.4 psi i

The sample calculations indicated that the computed stresses for the combined loading of inertia, interstory relative displacement, and equipment attached load were found to meet the intent of the SGEB allowables.

With regard to multi-wythe walls, sample calculations were provided for a j

18-in, solid, normal-weight block wall.

The 18-in wall has three layers of 6-in x 8-in x 16-in blocks.

  • The Licensee allowable meets the intent of the SGEB allowable as discussed in Response 4., -

TE R-C 5506-239 The wall was analyzed under the following conditions:

o Vertical beam strip, L = 8.06 ft The wall fundamental frequency is 25.4 cps (using plate formula) o o

Shielding wall, cantilevered from floor f

o Total attached load on wall is 970.75 lb o

Accelerations due to earthquake are:

Horizontal DBE = 0.48g Vertical DBE = 0.30g Horizontal OBE = 0.359 Vertical OBE = 0.21g The results of the multi-wytne wall sample calculation are listed below.

l Type of Stress Calculated Stress Licensee Allowable (SSE) a Maximum tensile stress 61.3 pai 66.7 psi (normal to bed joint)

M&ximum compressive stress 76.7 psi 298 psi Maximum shear stress 4.2 psi 40.4 psi Combined collar joint 5.6 psi 12 psi stress The sample calculations indicated that the computed stresses for the combined loading of inertia and equipment attached loads were found to be within the EGEB allowables except for the case of tension normal to bed joint.

Response 4 provides justifications and sources of conservatisms for accepting t

the Licensee's increased f actor. Therefore, it is concluded that the Licensee's response is adequate and meets the intent of the SGEB criteria.

Request 4 Justify the increase factor of 1.67 used in the criteria for allowable stresses.

The allowable working stresses for load conditions which represent abnormal / severe and abnormal / extreme environmental conditions such as design basis earthquake (DBE) may be multiplied by factors shown in the table in the SGEB criteria (10) which are given below:

4 -

,__, - - _ ~. _ - _ - - -. -.. _.... _ _

TER-C5506-239 Types of Stress Factor Shear re,inforcement and/or bolts 1.5 Masonry tension parallel to bed joint 1.5 Shear carried by masonry 1.3 Masonry tension perpendicular to bed Joint for reinforcement masonry 0.0 for unreinforcement masonry 1.3 Response 4 In this response, the Licensee stated that all allowable stress levels given in the SGEB criteria are met except for masonry tension perpendicular to the bed joint.

With reference to National Concrete Masonry Association (NCMA) test data for masonry tension perpendicular to the bed joint, the Licensee indicated that the factor of 1.67 provides a minimum average factor of safety of 2.3 with respect to the NCMA test results for masonry tension perpendicular to bed joint.

Moreover, in order to determine the extent to which this increased allowable stress was used to establish that the walls were acceptable, the calculated tension perpendicular and parallel to the bed joint stress values were reviewed for all walls.

The results of this review indicated that all but 20 walls meet the SGEB criteria. For these 20 walls, the only stress not meeting the SGEB criteria is the tension perpendicular to the bed joint and,the calculated stresses show an increase of 1.31 to 1.56 over the allowable working stress. These values are greater than the SGEB f actor of 1.3 but less than the 1.67 increase allowed in the Licensee's criteria. However, the 1.67 increase factor is felt to be reasonable in light oC the conservative values used for damping:

24 for OBE and 4% for SSE as opposed to 4% and 7% allowed by the SGEB.

Therefore, the Licensee's response is considered adequate and meets the intent of the SGEB criteria.

Request 5 Provide sketches of the proposed wall modifications and indicate how these modifications will correct the wall deficiencies. - -_._ ---

j TER-C5506-239 Response 5 In response to this request, the Licensee provided sample sketches of the wall modifications. One set of sketches is an example of a wall which was i

modified by changing its boundary conditions and adding steel plates on both sides of an existing structural member to provide a pinned boundary. Another set of sketches is an example of a wall modification which reduced the unsupported span of the wall by adding vertical and horizontal members.

Appendix B of this report presents the sketch of the typical wall modifications.

The Licensee's recponse is satisf actory and in compliance with the SGEB criteria.

1 l

Request 6 Provide the status of the proposed wall modifications.

Response 6 The Licensee confirmed that 16 walls that required modifications had been installed as indicated in Reference 10.

The remaining 15 walls in the fuel building were not acceptable under extreme loading cases and they have been removed and replaced with "blow-off" metal siding attached to a steel girt system.

See Section 1.? for additional information.

Request 7 Provide the results of the analysis of masonry walls which do not satisfy working stress criteria in terms of actual stresses versus allowable stresses.

Response 7 The Licensee confirmed in this response that all walls except those 15 walls in the fuel building are within the allowable stress limits.

Discussions about the allowable stresses are given in detail in Response 4. )

l 1

1 l

TER-C5506-239 i

Request 8 The Licensee indicated that arching theory and other inelastic analyses are used to qualify some masonry walls. The NRC, at present, does not accept the application of these analytical techniques to masonry walls in nuclear powe'r plants in the absence of conclusive evidence to justify the application.

Indicate the number of walls which have been analyzed using these techniques.

Response 8 In response to this request, the Licensee confirmed that no arching or other inelastic analyses were used to qualify the masonry walls.

The Licensee's response has resolved this concern.

Request 9 Justify the allowable stresses used for collar joints.

Response 9 In this response, the Licensee stated that the allowable tension and shear stresses in collar joints are taken to be 8 psi and 12 psi for OBE and DbE loads, respectively. The Licensee referred to tests conducted at the Trojan plant which indicated an average twnsile bond strength of 194 psi. The SSE allowable stress of 12 psi at North Anna Station Units 1 and 2 is only 6%

of the ultimate test value for tensile bond strength. Shear bond and tensile bond strengths are taken to be the same.

The Licensee's response is adequate and in compliance with the SGEB criteria.

Request 10 (Reference 13)

With respect to the boundary conditions used in the analysis, the Licensee indicated in Reference 11 that fixity was assumed at the base of a block wall built on a concrete slab. The Licensee is requested to provide the technical basis for assuming fixed-end conditions for these walls.

It is believed that without some clamping devices to prevent rotation at the wall boundary, the assumed boundary conditions may not be valid. 1

TER-C5506-239 Response 10 The Licensee restated its assumption that the mortar bed joint at the base of the cantilevered wall can be relied upon to transfer the induced moment. For the cantilevered walls, it is questionable whether the mortar bed

~

joint could perform this intended function. The review of other plants indicated that for a similar situation, some clamping devices are installed to assure the load is transferred properly at the base.

It is recommended that one of the following options be implemented for these walls:

Clamping devices should be installed at the base of the tall to o

provide positive means for load transfer.

Structural steel supports should be provided to change the boundary o

conditions at the free edges.

3.2 EVALUATION OF LICENSEE'S APPROACH TO WALL MODIFICATIONS In the response to Question 5 (Section 3.1), the Licensee indicated that modifications were performed to change the boundary conditions and/or reduce the unsupporteo span.

The Licensee also provided a sample modification with illustrative drawings.

The Licensee's approach to wall modifications has been reviewed and is considered satisfactory.

(Appendix B provides sample f

mod if ications. )

4 1,

TER-C5506-239 4.

CONCLUSIONS A detailed study was performed to provide a technical evaluation of the masonry walls at. North Anna Power Station Units 1 and 2.

A revient of the Licensee's criteria and the additional information provided by the Licencee led to the conclusions below.

Except for two items listed below, the criteria used for reevaluation of the masonry walls, along with the additional information provided by the Licensee, satisfy the intent of the SGEB criteria [14] and are found adequate.

o A total of 20 walls exceeded the SGEB stress allowable for tension normal to bed joint. As indicated in Response 4, the increase f actors are greater than 1.3 (SGEB allowable) but less than 1.67 (Lic6nsee allowable). However, because of conservative values used for damping (2% for OBE and 4% for SSE as opposed to 4% and 7%

allowed by the SGEB), it is judged that the allowable used by the Licensee is considered to meet the intent of the SGEB criteria.

o For the cantilevered walls, the Licensee is requested to provide positive means to assure the load transfer mechanisms taking place at the base of the walls. See Response 10 for more details.

With regard to 15 walls in the fuol building, the Licensee indicated that they have been removed and replaced with "blow-off" metal siding attached to a steel girt system. Concerns associated with these walls have been resolvec and addressed in the NRC Safety Evaluation Report which addressed the spent fuel pool expansion issue.

l <

~

--,.,,--_,.,-,--,-_r

,---v-p

-w,.

-,--v-m.v e

1 TER-C 5506-239 j

5.

REFERENCES 1.

Masonry Wall Design NRC, 08-Mey-80 IE Bulletin 80-11 i

2.

B. R. Sylvia Letter to J. P. O'Reilly, NRC

Subject:

Response to IE Bulletin 80-11; Item 4, for North Anna and i

Surry Power Stations Virginia Electric & Power Co., 07-Jul-80 Serial No. 434/05 3.

B. R. Sylvia Letter to J. P. O'Reilly, NRC

Subject:

Extension of IE Bulletin 80-11 Deadline for Surry Power Station Units 1 and 2 and North Anna Power Station Units 1 and 2 Virginia Electric & Power Co., 24-Oct-80 Serial No. 868 4.

B. R. Sylvia Letter to J. P. O'Reilly, NRC

Subject:

IE Bulletin 80-11 Interim Report for Surry Power Station

]

Units 1 and 2 and North Anna Power Station Units 1 and 2 Virginia Electric & Power Co., 03-Nov-80 Serial No. 878 l

5.

B. R. Sylvia Letter to J. P. O'Reilly, NRC Sub3ect:

IE Bulletin 80-11 Estimated Schedule for Surry Power Station Units 1 and 2 and North Anna Units 1 and 2 Virginia Electric & Power Co., 26-Dec-80 Serial No. 1005 6.

B. R. Sylvia Letter to J. P. O'Reilly, NRC

Subject:

IE Bulletin 80-11, Interim Progress Report for Surry Power Station Units 1 and 2 and North Anna Power Station Units 1 and 2 Virginia Electric & Power Co., 15-Apr-81 Serial No. 245 7.

B. R. Sylvia Letter to J. P. O'Reilly, NRC

Subject:

IE Bulletin 80-11, Interim Progress Report for Surry Power Station Units 1 and 2 and North Anna Power Station Units 1 and 2 Virginia Electric & Power Co., 15-Jun-81 Serial No. 372._.

TE R-C 5506-239 8.

B. R. Sylvia Letter to J. P. O'Reilly, NRC

Subject:

IE Bulletin 80-11, Masonry Wall Design - Surry Power Station Units 1 and 2, North Anna Power Station Units 1 and 2 Virginia Electric & Power Co., 19-Jun-81 Serial'No. 372A 9.

W. R. Cartwright Letter to J. P. O'ReilP!, NRC

Subject:

Submittal of Licensee Event Report No. LER 81-062/03L-0 for North Anna Unit i Virginia Electric & Power Co., 20-Aug-81 Serial N-81-142 10.

R. H. Leasburg Letter to J. P. O'Reilly, NRC

Subject:

IE Bulletin 80-11, Masonry Wall Design North Anna Power Station Units 1 and 2 Virginia Electric & Power Co.

14-Sept-81 Serial No. 465 11.

R. H. Leasburg Letter to H. R. Denton, NRC Subject Submittal of Additional Information, IE Bulletin 80-11, Masonry Wall Design, North Anna Power Station Units 1 and 2 Virginia Electric & Power Co.

15-July-82 Serial No. 372 12.

R. H. Leasburg Letter to H. R. Denton (NRC)

Subject:

Fuel Building Block Wall Virginia Electric and Power Company (Received draft copy on October 13, 1982) 13.

W. L. Stewart Letter to H. R. Denton (NRC)

Subject:

Submittal of Additional Information NRC IE Bulletin 80-11 (Masonry Wall Design) 26 October-84 14.

Criteria for Safety-Related Masonry Wall Evaluation NRC Standard Review Plan, Section 3.8.4, Appendix A 15.

Uniform Building Code International Conference of Building Officials, 1973..

TE R-C 5506-239 1

16.

Building Code Requirements for Concrete Masonry Structures Detroit: American Concrete Institute, 1979 ACI S31-79 and ACI S31-R-79 i

i I

l i

APPENDIX A SGEB CRITERIA FOR SAFETY-RELATED MASONRY WALL EVALUATION (DEVELOPED BY THE STRUCTURAL AND GEOTECHNICAL ENGINEERING BRANCH (5GEB) OF THE NRC)

July 1981 I

FRANKLIN RESEARCH CENTER DWITCN CF ARVlti/CALSPAN 20tn A RACE STREETS,PHILADELPHJA,pA :gjo3

TER-C5506-239 CONTENTS Section Title Page 1

GENERAL REQUIREMENTS A-1 2

LOADS AND LOf.D COMBINATIONS.

A-1 a.

Service Load Combinations A-1 b.

Extreme Environmental, Abnormal, Abnormal / Severe Environmental, and Abnormal / Extreme Environmental Conditions.

A-2 3

ALLOWABLE STRESSES.

A-2 l

4 DESIGN AND ANALYSIS CCNSIDERATIONS.

A-3 5

REFERENCES.

A-4 l

l l

i 1

l 1

i iii

TER-C5506-239 1.

General Requirements The materials, testing, analysis, design, construction, and inspection related to the design and construction of safety-related concrete masonry walls should conform to the a7plicable requirements contained in Uniform Buf1 ding Code'- 1979, unless specified otherwise, by the provisions in this criteria.

The use of other standards ci codes, such as ACI-531, ATC-3, or NCMA, is also acceptable. Howevar, when the provisions of these codes are less conservative than the corresponding provisions of the criteria, their use should be justified on a case-by-case basis.

In new construction, no unreinforced masonry walls will be permitted. For operating plants, existing unreinforced walls will be evaluated by the provisions of these criteria.

Plants which are applying for an operating license and which have already built unieinforced masonry walls will be i

evaluated on a case-by-case basis.

2.

Loady 7,1 Lesd fumbinations 1

T.ie leads and load combinations shall include consideration of nornal loeds, severe environmental loads extreme environmental loads, and abnorra1 loads.

Specifically, for operating plants, the load combinations provided in the plant'e FSAR shall govern. For opetating license applications, the follouing load combinations shall apply (for definition ef losd teras, see SRP Section 3.8.4I2-3).

(a)

Secvice, Load Conditions (1) D+L I

(2) D4 L* E (3) 3*L+W If thermal strasses due to T and Ro are g>esent, they should be o

includ d in the above combinations as folim2=:

(la) 3

  • L + Te + Ro (2a) D+L+To + Ro + E (3a) D + L + To + Ro + W Check load combina*Lan for controlling condition for maximum

'L' and for no

'L'.

A-1

,a

I TER-C5506-239 (b)

Extreme Environmental, Abnormal, Abnormal / Severe Environmental, and i

Abnormal / Extreme Environmental Conditions (4) D + L + To + do + E (5) D + L + To + Ro + Wt (6) D + L + Ta + Ra + 1.5 Pa (7) D + L + Ta + Ra + 1.25 Pa + 1.0 (Yr + Yj + Ym) + 1.25 E (8) D + L + Ta + Ra + 1.0 Pa + 1.0 (Yr + Yj + Ym) + 1.0 E' In combinations (6), (7), and (8) the maximum values of P, T

  • a a

at Yje Yr, and Ym, including an appropriate dynamic load R

factor, shocid be used unless a time-history analysis is performed to j

justify otherwise. Combinations (5), (7), and (8) and the corresponding structural acceptance criteria should be satisfied first without the tornado missile load in (5) and without Yr* Yj' and Ya in (7) and (8). When considering these loads, local section strength capacities may be exceeded under these concentrated loads, provided there will be no loss of function of any safety-related system.

Both cases of L having its full value or being completely absent 2

should be checked.

3.

Allowable Stresses Allowable stresses provided in ACI-531-79, ac supplemented by the following modifications / exceptions, shall apply.

(a)

When wind or seismic loads (OBE) are considered in the loading combinations, no increase in the allowable stresses is permitted.

J' (b)

Use of allowable stresses corresponding to special inspection category shall be substantiated by demonstration of compliance with 4

the inspection requirements of the SEB criteria.

(c) When tension perpendicular to bed joints is used in qualifying the unreinforced masonry walls, the allowable value will be justified by test program or other means pertinent to the plant and loading conditions. For reinforced masonry walls, all the tensile stresses will be resisted by reinforcement.

t 1

(d)

For load conditions which represent extreme environmentti, abnormal, abnormal / severe environmental, and abnormal / extreme environmental conditions, the allowable working stress may be multiplied by the I

factors shown in the following tables a

A-2

- I l;

4 TER-C5506-239 Type of Stress

? actor Axial or Flexural Compression 2.5 Bearing 2.5 Reinforcement stress except shear 2.0 but not to exceed 0.9 fy Shear reinforcement and/or bolts 1.5 Masonry tension parallel to bed joint 1.5 Shear carried by masonry 1.3 Masonry tension perpendicular to bed joint for reintorced masonry 0

for unreinforced masonry 2 1.3 Notes (1)

When anchor bolts are used, design should prevent facial spalling of masonry unit.

(2)

See 3 (c).

4.

Design and Analysis Considerations (a)

The analysis should follow established principles of engineering mechanics and take into account sound engineering practices.

(b)

Assumptions and modeling techniques used shall give proper considerations to boundary cor.ditions, cracking of sections, if any, and the dynamic behavior of masonry walls.

(c)

Damping values to be used for dynamic analysis shall be those for reinforced concrete given in Regulatory Guide 1.61.

(d)

In general, for operating plants, the seismic analysis and Category I structural requirements of FSAR shall apply.

For other plants, corresponding SRP require' ents shall apply. The seismic analysis a

shall account for the variations and uncertainties in mass, materials, and other pertinent parameters used.

(e)

The analysis should consider both in-plane and out-of-plane loads.

(f)

Interstory drift effects should be considered.

A-3

TER-C5506-239 (g)

In new construction, grout in concrete masonry walls, whenever used, shall be compacted by vibration.

(h)

For masonry snear walls, the minimum reinforcement requirements of ACI-531 shall apply.

(i)

Special constructions (e.g., multiwythe, composite) or other items not covered by the code shall be reviewed on a case-by-case basis for their acceptance.

l (j)

Licensees or applicants shall submit QA/QC information, if available, i

for staff's review.

l In the event QA/QC information is not available, a field survey and a test program reviewed and approved by the staff shall be implemented i

to ascertain the conformance of masonry construction to design l

drawings and specifications (e.g., rebar and grouting).

(k)

For masonry walls requiring protection from spalling and scabbing due to accident pipe reaction (Yr), jet impingement (Y ), and missile 3

impact (Ym), the requirements similar tc those of SRP 3.5.3 shall apply.

However, actual review will be conducted on a case-by-case basis.

5.

References (a)

Uniform Building Code - 1979 Edition, i

(b)

Building Code Requirements for Concrete Masonry Structures ACI-531-79 and Commsntary ACI-531R-79.

(c)

Tentative Provisions for the Development of Seismic Regulations for Buildings - Applied Technology Council ATC 3-06.

(d)

Specification for the Design and Construction of Load-Bearing Concrete Masonry - NCMA August, 1979.

(e)

Trojan Nucleir Plant Concrete Masonry Design Criteria Safety Evaluation Report Supplement - November, 1980.

A-4

1 APPENDIX B SKETCHES OF WALL MODIFICATIONS FRANKLIN RESEARCH CENTER i

DIVISON OF ARVIN/CALSPP.N 20tn & RACE STREET 1,PHil.ADELPHIA,PA 19103

r 4

4 f a 8 e t ?g t4 tee 04 g

.~

,r

. _.. _=

l_R 7 7 9 f.'

.1g...

I-_' f L t Pi s' t

,.I,13'

)

.r j r;ym-

)

-l' i

T 1

J

_. L_

e.

l

  • {

j,

  • (m.

.,,.1 MtP p*

O 14J.8.b W f U.,

y g.

[]

Q 24J,8 ll

.\\-.

-J u

4

(....

u.

. w m,,,,...,

p p

. ~, s., e, c,.v e.

=

_l_T i--

g n

. _L,, L t.

a':1 '. nL----

r-

^ du c %- Jl..

T prrce v

t j

-H.

1 - 1 o t' m y.<.

e l

4 b,

'4 4IC 11

,pg L

CC1 O sts 24w. t >>

eren i)Ae

,ag m w m as=ruam

.1, r

.._._a

~3 r-t:_

r.f - ]Q.=s-f..a non we.,io.e a o r i n. i.e 4 +4t a e.)y fi

.. o-Typical Wall Modification - Boundary Conditions B-1

0 *.

o cc.t. t. tc cct/

-<*I j

1.c r.3f__.

g.

I l

r

__---l 1 ti m,

~,a,, -

C# M,4 f t g d e 4-IY i

%y

.m 24 o l-

- 6

.- -f l W

1-n

_...<,.m....,

coo uw,* ',u u os.L 1

.1 = [.htL.CLf;Y 2 <s..o..,,

2r L.

,:..:,,..... +.

T-a,

< M

.I. g..

e Lt we 6 * *

/

j' 1

\\

n.!

...../

I

,LL JI II.13l Y

eu t i e ri

/

i

~

?

?

n,8,/

. sr e oc e s.4,n.u.n o.E w

A a

u eurn s sies.r

~

J rra Mee4LC foe to TAL'.