ML20151K502
| ML20151K502 | |
| Person / Time | |
|---|---|
| Site: | Framatome ANP Richland |
| Issue date: | 08/01/1997 |
| From: | Hardin K NRC OFFICE OF NUCLEAR MATERIAL SAFETY & SAFEGUARDS (NMSS) |
| To: | Maas L SIEMENS POWER CORP. (FORMERLY SIEMENS NUCLEAR POWER |
| References | |
| TAC-L30978, NUDOCS 9708060098 | |
| Download: ML20151K502 (3) | |
Text
_ _. ___ -
Mr. L..J.
Maas Manager. Regulatory Compliance
.r Siemens Power Cor) oration
~
2101 Horn Rapids Road
,_f P.O. Box 130-Richland. Washington 99352-0130
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION POWDER AND/0R PELLET SHIPPING PAILS (TAC NO. 30978)
Dear Mr. Maas:
This refers to your application dated May 22, 1997, and supplementary information submitted July 15, 1997, requesting the revision of License SNM-1227 to include loading and storing UO Powder and/or Peilets in NT-IX shipping container (Japanese certificate. 5/113/AF-85, revision 4) inner pails at your facility until the Jails are loaded into the NT-IX shipping container.
Our review of the revision las identified additional information that is needed in the area of criticality safety before final action can be taken on your amendment request. This additional information is described in the enclosure to this letter.
j The additional information should be provided in the form of res)onses to the individual comments within 30 days of tne date of this letter.
) lease i
reference the above TAC number in future correspondence related to this request.
If you-have any questions, please call me at 301-415-8119 or Harry Felsher at 301-415.5521.
Sincerely, f
Original signed by:
Kimberly J.
Hardin Licensing Section 2 Licensing Branch Division of Fuel Cycle Safety and Safeguards. NMSS Docket 70-1257 License SNM-1227
_t
{ FO D
/
i
Enclosure:
Re uest for Additional I formation-JISTRIBUTION: w/ encl. (Control No. 1F05) bcket 70-1257 PUBLIC NRC File Center Region IV FCLB R/F FCSS R/F NMSS R/F CHooker. RIV SChotoo
. G:\\PAILRAI.SPC]
[
0FC FCLB F.
FCLB 2E FCLB E
FCLB C
NAME HFelsher 6-/S PShea9Nrtr^
KHardin Y d MWeber N N DATE 8/ / /97 8/ l /97 8/ l /97 8/I/97 C = C NER E = COVER & ENCLOSURE N = NO COPY 0FFICIAL RECORD COPY ile ** %a d* Q (50 RLE CENTEg ggpy
c# "'C%
p*
.t UNITED STATES i
{
,j NUCLEAR REGULATORY COMMISSION
't WASHINGTON, D.C. 2056MJ01 o
August 1, 1997 Mr. L. J.
Maas Manager, Regulatory Compliance Siemens Power Cor) oration 2101 Horn Rapids Road P.O. Box 130 Richland Washington 99352-0130 1
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION POWDER AND/OR l
PELLET SHIPPING PAILS (TAC NO. 30978) i j
Dear Mr. Maas:
i This refers to your application dated May 22. 1997, and supplementary information submitted July 15, 1997, requesting the revision of License 4
i SNM-1227 to include loading and storing UO Powder and/or Pellets in NT-IX shipping container (Japanese certificate, b/113/AF-85, revision 4) inner pails j
2 at your facility until the Sails are loaded into the NT-IX shipping container.
Our review of the revision las identified additional information that is j
needed in the area of criticality safety before final action can be taken on your amendment request.
This additional information is described in the 1
enclosure to this letter.
i The additional information should be provided in the form of res)onses to the individual comments within 30 days of the date of this letter.
) lease reference the above TAC number in future correspondence related to this request.
If you have any questions, please call me at 301-415-8119 or Harry Felsher at 301-415-5521.
i Sincerely.
mberly ardin Licensing Section 2 Licensing Branch Division of Fuel Cycle Safety and Safeguards, NMSS Docket 70-1257 i
License SNM-1227
Enclosure:
Request for Additional i
Information i
4
t Request for Additional Information i
l Application Dated May 22, 1997 and Supplement Dated July 15, 1997 l
Siemens Power Corporation Docket 70 1257 o
Subject:
Siemens Power Corporation Request Dated May 22, 1997, with I
supplementary information submitted July 15. 1997, to amend License No. SNM-1227. Docket No. 70-1257.
1.
Because the activity has been analyzed for 3.5 gallon pails, modify your f
amendment request as follows: Add a new entry to Table I-4.1 for 3.5 gallons or less containers with the following criticality controls:
i VOL FNA CCM. MCU. ARA and SPA.
Delete the use of FNA for the 5 gallon containers in your request.
f 2.
Because the activity has been analyzed at 7.0 wt% H O and the U0 -H O i
2 2 2 becomes visibly wet at 7.0 wt% H 0 and thus administrative controls i
2 will be used to keep the H O wt% at or below 7.0 wt% modify your j
2 l
amendment.recuest as follows:
Add to the " Discussion of any special l
l controls usec/ additional explanation of control type" in Table I-4.1 for i
3.5 gallons or less containers the following condition:
Containers will I
never be visibly wet which means that the H O wt% will be less than or 2
equal to 7.0.
I i
3.
Describe the four steps in the activity: -(1) describe the normal filling process of the pails with UO powder / pellets including the
)
2 condition of storage at the filling site as a single tier array, (2) describe the normal on-site transportation of the pails as two pallets i
l (4 pails on each pallet C-to-C) on a forklift. (3) describe the normal I
storage of pails as in.a single tier array, and (4) describe the normal loading of pails into shipping casks as three stacks of 3 pails high j
l centered on 25"x25" steel pallets and must be attended until loaded into the overpack.
4.
Describe the process of loading the pails with the U0 powde' cr 2
pellets.
Provide details so that we can determine that the criticality safety basis for storage encompasses the loading activity from the point of filling the bags in the pail, to closing the lid of the
) ail, to l
placement of the pail on a pallet to storing the pail at tie filling site until transporting the pail to the storage area.
l 5.
Why did you use a UO density of 2.0 g/cc in your analysis instead of thestandard10.96gicc?
i 6.
Why did you use 7.0 wt% H O and a volume fraction H O of 0.15054 in your 2
2 analysis?
7.
Why did you use the density of regular-concrete to be 1.0 g/cc instead of the standard 2.3 g/cc?
l 8.
Why did you use the volume fraction of interspersed H 0 to be 1.0e-6 2
instead of 1.0?
i 9.
What were your results (k-effective and sigma values) for the four situations in this activity: baseline (single pail with reflectors).
L on-site transport (two 2x2-pail pallets with reflectors), storage 1
(infinite array with reflectors), loading into shipping casks (three 1x3-pail pallets with reflectors)?
' ENCLOSURE
~
-