Forwards Safety Evaluation Granting Util 870812 Request for Relief from Requirements of ASME Section XI Due to Inaccessible Welds in Feedwater Sys
ML20151E028
Person / Time
Site: Fort Calhoun 
Issue date: 04/07/1988
From: Calvo J
Office of Nuclear Reactor Regulation
To: Andrews R
OMAHA PUBLIC POWER DISTRICT
Shared Package
ML20151E030 List:
References
TAC-65998, NUDOCS 8804150021
Download: ML20151E028 (6)


Text

_ _ _ _ _ _ _

/ o.:e.,k\\

UNITED STATES b

NUOLEAR REGULATORY COMMISSION j

. f.

e a

W ASHINGTON, 0. C. 20555 k

April 7,1988 I

Docket No. 50.?85 I

Mr. R. l.. Andrews Division Manager - Nuclear Production Onaha Public Power District 1623 Harney Street Omaha, Nebraska 68102

Dear Mr. Andrews:

SUBJECT:

PELIEF FROM RE0VIREMEtlTS OF ASME SFCTION XI FORT CALHOUN STATION (TAC NO. 65998)

By letter dated Jure 10, 1986, OmahaPublicPowerDistrict(OPPD) identified i

specific ASME Code requirements that OPPD detemined to be impractical to be perfomed and provided supporting technical infomation. The staff completed its review with a conditional Safety Evaluation, dated November 10, 1986. The conditional requirement was that OPPD would select additional accessible welds l

to maintain the sample size.

l By letter dated August 12, 1987, OPPD informed the staff that the inaccessible welds in the feedwater system were subject to examination because the detection of recordable surfree indications required expansion of the sample to include 100 percent of the weld locatiens.

In addition. OPPD infomed the staff that some of the inaccessible welds were not subject to examination.

The staff has completed its review of the August 12, 1987 and has concluded l

that the November 10, 1986 Safety Evaluation is still correct in concept end represents an accurate evaluation of the infomation provided. The enclosed Safety Evaluation supplements that infomation and relief has been granted for certain examination recuirements with certain conditions described in the Safety Evaluation.

~

Accordingly, relief from certain requirements of Section XI of the ASME Code is hereby granted, as described in the November 10, 19R6 and enclosed Safety Evaluation.

I 6804150021 000407 l

PDR ADOCK 05000205 i

P PDH t

i i

Mr. R. L. Andrews We have determined that this action is authorized by law and will not endanger life or property or the cone.on defense and security and is otherwise in the public interest.

Sincerely,

/s/

Jose A. Calvo. Director Project Directorate - IV Division of Reactor Projects - III, IV, Y and Special Pro.iects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page DISTRIBUTION Docket File NPC PDR Local PDR PD4 Reading DR4A/J. Collins J. Calvo P. Noonan A. Bournia OGC-Rockville E. Jordan J. Partlow ACRS(10)

PDA Pltnt File T.Barnhart(t)

  • See previous concurrences:

PO4/LA*

PD4/FM*

OGC-Vf*

PD4/D /2I0 PNoonan ABournia:sr 0Calvo 03/23/88 03/24/88 03/31/88 04/ / /88

Mr. R. L. Andrews We have determined that this action i2 authorized by law and will not endanger life or property or the cons ? detense and security and is otherwise in the public interest, civing due consideratior to the burden upon the licensee that could result if the code inquirements were imposed en the faci',ity.

Sincerely, Jose A. Calvo. Director Project Directorate - IV Division of Reactor Proiects - 111 IV, Y and Special Proiects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page 1

r I

DISTRIBUTION Docket File NRC PDR Local PDR PD4 Reading DR4A/J. Collins J. Calvo P. Noonan A. Bournia OGC-Rockville E. Jordan J. Partlow ACPS (10)

PD4 Plant File T. Barnhart (4)

'\\,

OD 1l/h PD4/LA p j fx~~

PD4/FM OGC-VF PD4/0

'.sieesc.

JCalvo PNoonan.

ABournia:sr 03/,'3/88 03/Jy/88 03/4t./88' 03/ /08

Mr. R. L. Andrews -

We have determined'that this action is authorized by law and will not endanger life or property or the common defense and security and is otherwise in the public interest.

-Sincerely,

/s/

Jose A. Calvo, Director Project Directorate - IV Division of Reactor Projects - III, IV, Y and Special Pro,iects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page i

l DISTRIBUTION l

Docket File NRC PDR Local PDR PD4 Reading DR4A/J. Collins J. Calvo P. Noonan A. Bournia OGC-Rockville E. Jordan J. Partlow ACRS (10)

PDA Plant File T. Barnhart (d) l

  • See previous concurrences:

PD4/LA*

PD4/FM*

OGC-WF*

PD4/D /?!0 PNoonan ABournia:sr JCalvo 03/23/88 03/24/88 03/31/88 04/ / /88 l

l

Mr. R. L. Ardrews We have determined that this action is authorized by law and will not endanger life or property or the comon defense and security and is otherwise in the public interest.

Sincerely, p

6(, [a$G" Jose A. Calvo, Director Project Directorate - IV Division of Reactor Pro.iects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page t

l l

l I

i

i Mr. R. L. Andrews Fort Calhoun Station

.0maha Public Power District Unit No. I cc:

Harry H. Voigt Esq.

LeBoeuf, Lamb, Leiby & MacRae 1333 New Hampshire Averue, NW Washington, D.C.

20036 Mr. Jack Jensen, Chairman Washington County Board of Supervisors Blair, Nebraska 68008 Mr. Phillip Harrell, Resident Inspector U.S. Nuclear Regulatory Commission P. O. Box 309 Fort Calhoun, Nebraska 68023 Mr. Charles B. Brinkman, Marager Washington Nuclear Operations C-E Power Systems 7910 Woodmont Avenue Bethesda, Maryland 20814 Regional Administrator, Regicn IV U.S. t'uclear Regulatory Commission Office of Executive Director for Operations 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 Harold Borchert, Director Division of Radiological Htalth Department of Health 301 Centennial Mall, South P.O. Box 95007 Lincoln, Nebraska 68509 W. G. Gates, Manager Fort Calhoun Station P. O. Box 399 Fort Calhoun, Nebraska 68023 l