APPENDIX A NOTICE OF VIOLATION Vermont Yankee Nuclear Power Corporation Docket No. 50-271 Vermont Yankee Power Station License No. DPR-28 As a result of the 10 CFR 50 Appendix R inspection conducted on February 8-11, 1988, and in accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (Enforcement Policy 1987), the following violation was identified:

10 CFR 50, Appendix R, Section III.J. requires that emergency lighting units with at least an 8-hour battery power supply shall be provided in all areas needed for operation of safe shutdown equipment and in access and egress routes thereto.

Contrary to the above, as of February 8,1988, emergency lighting units with at leact an 8-hour battery power supply were not provided in the following safe shutdown areas and access and egress routes:

The Control Room The North East Section of the Torus Catwalk Fire Area RB-5 This is a Severity Level IV violation. (Supplement I)

Pursuant to the provisions of 10 CFR 2.201, Vermont Yankee Nuclear Power Corporation is hereby required to submit to this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and the results achieved; (2) the corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved.

Consideration may be given to extending the response time for good cause shown.

l 1

0FFICIAL RECORD COPY IR VY 88 0004.0.0

, 03/30/88 es04130140 880406 PDR ADOCK 05000271 Q DCD l l