- i Repon No. 75-33
(-
SIR.1ECT:
Violation of the Technical Specifications, paragraph 3.1. A.3,
%e high flow setpoints on the ster:: sad condensste lines of the Tsolation.Condensen were fotad to trip at AP values in excess of those as stated in Technical Specification Table 3.1.1.H (<20 psid - stcai,d27.inchos 6F H2O - Condensate).
'Ihis event is considered to be an abnor al occurrenco as de-fined in the Technical Specifications, paragraph 1,153..
1:uti-fication of this ovent; as required by the Technical Specifi-cations, paragraph 6.6.2.a, was n:5dc to AEC Region I, Directorate of Reguistory operations, by telephone on Fridsy, Decer.her 21, 1973, at 1635, and by teleccpier on k'ednesday, December 26, 1973, e
at 0955.
SITU.GIC : On F'iday, Dccerber 21, 1973, whilc performing survoi'11ance
, testing-on tho Isolation Condenser liigh Flow sensors (two each por condensate and Aten line per cond ser), four of the sensors were found to trip.at setpoints in exces'. of their respective l
lir.dts.
Specificelly, the sensors of concern and their corres-
'ponding "as found" setpoints are as follows; l
Condssate "A"ContkenserIE11A1'.29"ofWAter f
l ID]) A2 - 31" of water IB11B2 - 20" of water 5
Stcan l
J1 "S" Cendenser 2005a1 - 22 psid f/0399D729
~
MI*
.m, w
.w.
.a...
~
Abnomal Occurrenct.
P.cpor't No. 73-33, Decer.ber 21, 1973 caul $
. The cause of this ' event is yet to be dotcr=ined.
p.95pj AL Action:
Upon discovery of the condition, the instrumnt tecnicina per-forming-the surveillance test reset the affected d/p, sensors to their raquired vsIves (5,27 inches H2O on condensate and <20 psid on the stcan).
s
. T 3
SAFEiY SIGNIFJC/JiCTir The safaty irplication of this event is minicAl sincethaesen-i sors were operabIe and would have perfomed their.ftmction.
Fast: data has shDWn that. Upon initinting ~ the c'ondensers, the condensate line senses d/p in excess of 60. inches of water; therefore, althou;;h th'e setpoint had drifted, the new value was well,within the range of the egerted signal and 'the sensor was -
capP.ble of perfoming' its protectivo action.
+
+