Text
_
e recoq O
UNITED STATES g g y
{gg NUCLEAR REGULATORY COMMISSION 31
- l WASHINGTON, D. C. 20555 PORTLAND GENERAL ELECTRIC COMPANY THE CITY OF EUGENE, OREGON PACIFIC POWER AND LIGHT COMPANY DOCKET NO. 50-344 TROJAN NUCLEAR PLANT AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.139 License No. NPF-1 4
1.
The Nuclear Regulatory Comission (the Comission) has found that:
A.
The application for amendment by Portland General Electric Company, et al., (the licensee) dated November 13, 1987 complies with the staiidards and requirerents of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's regulations set forth in 10 CFR Chapter I; The facility will operate in conformity with the application, the provisions of the Act, and the regulations of the Comission; There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health c
and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
8804000197 000331 PDR ADOCK 05000344 P
, 2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachtrent to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-1 is hereby amended to read as follows:
(2) Technical Specifications The Technical Specifications contcined in Appendices A and B, as revis(d through Amendment No.139, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical S;,ecifica.
tions, except where othemise stated in specific license conditions.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEAR REGULATORY COMMISSION dd$/ $, fu
"'G e ge W nighton,,
rector Project Directora V
Division of Reactor Projects - III, IV, V and Special Projects Attachrrent:
Char.ges 'to the Technical Specifications Date of Issuance: fia rch 31, 1988
l l
March 31, 1988 l
l l
ATTACHMENT TO LICENSE AMENDMENT N0.139 TO FACILITY OPERATING LICENSE NO. NPF-1 DOCKET J. 50-344 Revise Append 1x A as follows:
R_emove Page3 Insert Pages 3/4 10-1 3/4 10-1 5
I I
1 4
l
1 I
3/4.10 SPECIAL TEST EXCEPTIONS SHUT 00WN,, MARGIN LIMITING CONDITION FOR OPERATION 3.10.1 The SHUT 00WN MARGIN requirement of Specification 3.1.1.1 may be suspended for measurement of control rod worth and shutdown margin provided:
a.
Reactivity equivalent to at least the highest estimated control rod worth is available for trip insertion f rom OPERABLE control rod (s).
APPLICABILITY: h00E 2.
ACTION:
a.
With the reactor critical (Kef f 11.0) and with less than the above reactivity equivalent available for trip insertion, immediately initiate ar.d cortinue boration at 130 gpm of 7000 ppm boron or its equivalent until the SHUTODWN MARGIN required by Specification 3.1.1.1 is restored, b.
With the reactor suberitical (Keff < 1.0) by less than the above reactivity equivalent, inwediately initiate and continue boration at
> 30 gpm of 7000 ppm boron or its equivalent until the SHUT 00WN MARGIN required by Specification 3.1.1.1 is restored.
OURVEILLANCE REOUIREMENTS 4.10.1.1 The post-sion of each full length rod either partially or fully withdrawn shall be.ietermined at least once per 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
4.10.1.2 Each full length rod not fully inserted shall be demonstrated OPERABLE by verifying its rod drop time to be < 2.2 seconds within 7 days l
pricr to reducing the SHUTQDWN MARGIN to less than the limits of Specification 3.1.1.1.
4.10.1.3 This Specification has been deleted due to the removal of part I
length rods from the reactor.
1 TROJAN-UHli 1 3/4 10-1 Amendment No. 70,139 March 31,1988 1