ML20150E048

From kanterella
Jump to navigation Jump to search
RO 78-124 on 781116 Design Deficiency Indicates That post- LOCA Conditions Could Overstress Piping & Pipe Supports
ML20150E048
Person / Time
Site: North Anna Dominion icon.png
Issue date: 11/20/1978
From:
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
References
NUDOCS 7812110090
Download: ML20150E048 (1)


Text

--

TERA esw

iGjQ,} ,, , I. P. Or ,W AYLAliTA, GECiRGI A 0 J,$.y P. D. C 'i Ti. B. '
i
. ucV20 A 8: 38 p[

Virginia Electric and Puwer Ccmpany North Anna Power Station, Unit No.1 t g j,5 kj Docket No. 50-338 g g ,.)

Report No. LER 78-124 Event Date 11-16-78 Report Dete 11-17-78 The Service Water System piping and support requirements teove been analyzed for trwr nal plus seisanic produced stresses assts11r.g c tr.oe it' u i fervice Water tewerature of 96*F. The piping was also anoljzed for o down tronac The tent Tecn-to 45"F. Tre supperts have been analyzed for up transients to 95"F.If the sp.te nical Specifications limit the Service Water ter:perature to 95*F is at il5"F, prelininary analysis indicates tnat post LOCA conditions could ove<

stress tre piping and pipe supports.

A prelininary analysis has been accc<rplished by randocily sar,plir.9 7.33 o tne larse bore supports. Eight-five (85Six 5) percent of these supports st% no supports may require addttional problesns in a down transient to 45'F.

analysis but five (5) of these do not exceed the op transient loading et 654 and or,e (1) at 66*F. 'Ibe design temperature is 70*f for stress analysis.

Our analysis indicates that with one unit operating post LC{ A tur.ditions will not cause the tersperature to rise above 95"F with service water teciper atur.

r,c.< being experienced. This is based on prelininary data .fitch shows a IP-t rise 3 units in in tee:perature frco 9d*F with one unit in post LOCA conditions and cooldown.

Service water conditions are being set to mintain terceratures at approximately the design conditions where practical. Design mrgins for tr.e supports ir.clude the following:

1) No design yield straigths exceed 62.57. of material design yield stre%ths.
2) Design margins always exceed one.
3) Support hilti allowables are based on scoe per cent of capability.

There is no immediate effect upon the safe operation of the plant and power operation.will continue.

l 7812110070

-