IR 07100113/2012015

From kanterella
(Redirected from ML20149M332)
Jump to navigation Jump to search
Notice of Deviation from Insp on 871113-1215.Deviation Noted:High Range Containment Area Radiation Monitor Does Not Have Recording Display in Control Room
ML20149M332
Person / Time
Site: Crystal River, 07100113 
Issue date: 02/19/1988
From: Wilson B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20149M319 List:
References
50-302-87-40, NUDOCS 8802250488
Download: ML20149M332 (1)


Text

'

.

\\

.

ENCLOSURE 2 NOTICE OF DEVIATION Florida Power Corporation Docket No. 50-302 Crystal River Unit 3 License No. DPR-72 The following deviation was identified during a Nuclear Regulatory Commission (NRC) inspection conducted on November 13 - December 15, 1987.

In a letter to the NRC from Florida Power Corporation (FPC) dated August 24, 1984, in response to a NRC Confirmatory Order dated February 21, 1984, FPC committed to comply with the requirements of Regulatory Guide (RG) 1.97.

This letter documented, in part, the installation of a high range containment area radiation monitor that has both an indicating and recording display in the control room.

Contrary to the above, as of November 23, 1987, the high range containment area radiation monitor does not have a recording display in the control room.

Please provide to the U.S. Nuclear Regulatory Comission, ATTN: Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, Region II, [IF APPLICABLE: and a copy to the NRC Resident Inspector, Crystal River 3,] in writing within 30 days of the date of this Notice, the reasons for the deviation, the corrective steps which will be taken to avoid further deviations, and the date when your corrective action will be completed. Where good cause is shown, consideration will be given to extending the response time.

FOR THE U.S. NUCLEAR REGULATORY COMMISSION b%

-

Bruce A. Wilson, Chief Reactor Projects Branch 2 Division of Reactor Projects Dated at Atlanta, Georgia this 19th day of February 1988 8802250488 080219 PDR ADOCK 05000302 O

PDR