2020 ILT NRC JPM i SRRS: 3D.105 (when utilized for operator initial or continuing training) 10BExelon Nuclear 11BJob Performance Measure 0BPlace the 1/2 RBCCW Pump in Operation on Unit 1 1BJPM Number: 2020 ILT NRC JPM i 2BRevision Number: 00 3BDate: 08/10/2019 4BDeveloped By:

5BInstructor Date 6BValidated By:

7BSME or Instructor Date 8BReviewed By:

9BOperations Representative Date

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.100; There are no retention requirements for this section JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.

Prior to JPM usage, revalidate JPM using steps 9 and 13 below.

1.

Task description and number, JPM description and number are identified.

2.

Knowledge and Abilities (K/A) references are included.

3.

Performance location specified. (in-plant, control room, simulator, or other)

4.

Initial setup conditions are identified.

5.

Initiating cue (and terminating cue if required) are properly identified.

6.

Task standards identified and verified by SME review.

7.

Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

8.

If an alternate path is used, the task standard contains criteria for successful completion.

9.

Verify the procedure(s) referenced by this JPM reflects the current revision:

Procedure QCOP 3700-02 Rev: 29 Procedure Rev:

Procedure Rev:

10. Verify cues both verbal and visual are free of conflict.
11. Verify performance time is accurate
12. If the JPM cannot be performed as written with proper responses, then revise the JPM.
13. When JPM is initially validated, sign and date JPM cover page. Subsequent validations, sign and date below:

SME / Instructor Date SME / Instructor Date SME / Instructor Date

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.100; There are no retention requirements for this section Revision Record (Summary)

Revision 00, This is a new JPM developed for the 2020 ILT NRC Exam.

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.100; There are no retention requirements for this section INITIAL CONDITIONS Unit 1 and 2 are operating at 100% power.

The Unit 1 RBCCW system is on line with the 1A and 1B RBCCW pumps running.

The 1/2 RBCCW pump is in standby.

The 1A RBCCW pump will be taken out of service next shift for planned maintenance.

INITIATING CUE Place the 1/2 RBCCW pump in operation IAW QCOP 3700-02 step F.4 Provide examinee with: A copy of QCOP 3700-02 marked up as follows:

Prerequisites C.1 thru C.3, C.6 thru C.8, are signed off C.4, C.5, and C.9 are N/Aed Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes critical steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section. The comment section should be used to document: the reason that a step is marked as unsatisfactory, marginal performance relating to management expectations, or problems the examinee had while performing the JPM.

Comments relating to procedural or equipment issues should be entered and tracked using the sites appropriate tracking system.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.105 (when utilized for operator initial or continuing training)

JPM Start Time:

STEP ELEMENT STANDARD SAT UNSAT Comment Number F.4.a Verify the 1/2 RBCCW Pump is not required for Unit 2 operation.

Contacts the control room to determine if 1/2 RBCCW pump is needed on Unit 2.

CUE:

As the Unit Supervisor or NSO state:

The 1/2 RBCCW pump is NOT required on Unit 2.

F.4.b.

(1)

Verify locked closed the 1/2 RBCCW Pump U-2 Suction Valve from Unit 2.

Verifies the 2-3799-68, 1/2 RBCCW PMP U-2 SUCT VLV FROM U-2 is locked and closed.

(Located east bottom of 1/2 RBCCW pump)

F.4.b.

(2)

Verify locked closed the 1/2 RBCCW Pump U-2 Discharge Valve to Unit 2.

Verifies the 2-3799-66, 1/2 RBCCW PMP U-2 DSCH VLV TO U-2 is locked and closed.

(Located above 1/2 RBCCW pump)

EVALUATOR NOTE/CUE: The 1/2 RBCCW Suction valve is elevated. If the examinee cannot see the valve tag, then after the valve is located, if necessary inform the examinee that the tag reads: 1-3799-68, 1/2 RBCCW PMP U-1 SUCT VLV FROM UNIT 1

  • F.4.c (1)

Open the 1/2 RBCCW Pump U1 Suction Valve from Unit 1.

Locates the 1-3799-68, 1/2 RBCCW PMP U-1 SUCT VLV FROM UNIT 1 and turns the handle counterclockwise until it will turn no further.

CUE:

The handwheel will turn no further EVALUATOR NOTE/CUE: The 1/2 RBCCW Discharge valve is elevated. If the examinee cannot see the valve tag, then after the valve is located, if necessary inform the examinee that the tag reads: 1-3799-66, 1/2 RBCCW PMP U-1 DSCH VLV TO UNIT 1

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.105 (when utilized for operator initial or continuing training)

STEP ELEMENT STANDARD SAT UNSAT Comment Number

  • F.4.c (2)

Open the 1/2 RBCCW Pump U1 Discharge Valve to Unit 1.

Locates the 1-3799-66, 1/2 RBCCW PMP U-1 DSCH VLV TO UNIT 1 and turns the handle counterclockwise until it will turn no further.

CUE:

The hand wheel will turn no further F.4.d.

Vent the 1/2 RBCCW pump Vents the 1/2 RBCCW pmp by:

Throttling open the 1/2-3799-150C, 1/2 RBCCW PMP VENT VLV When a continuous stream of water issues from valve, then closes the 1/2-3799-150C.

CUE:

After the 1/2-3799-150C is throttled open, state:

There is a continuous stream of water issuing from the valve.

F.4.e.

Start the 1/2 RBCCW Pump Contacts the NSO and requests a start of the 1/2 RBCCW pump per QCOP 3700-02 step F.4.e.

CUE:

As the U-1 ANSO, acknowledge the request, then state to the examine that you hear the 1/2 RBCCW pump start up with no abnormalities.

CUE:

As the U-1 ANSO, state:

RBCCW system pressure and temperature are in the normal band.

EVALUATOR: Inform the examinee that another operator will secure the 1A RBCCW pump per QCOP 3700-02 Attachment A.

EVALUATOR: The examinee should inform you that the task is complete.

JPM Stop Time:

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.105 (when utilized for operator initial or continuing training)

JPM

SUMMARY

Operators Name:

Emp. ID#: ____________

Job

Title:

EO RO SRO FS STA/IA SRO Cert JPM

Title:

Place the 1/2 RBCCW Pump in Operation on Unit 1 JPM Number: 2020 ILT NRC JPM i Revision Number: 00 Task Standard:

Using QCOP 3700-02, lineup the RBCCW system to place the 1/2 RBCCW pump in operation.

Task Number and

Title:

3700.035: Locally align RBCCW pump for start.

K/A Number and Importance: K/A: 400000 2.1.30 Rating: (4.4/4.0)

Suggested Testing Environment: Plant Alternate Path:

Yes No SRO Only:

Yes No Time Critical:

Yes No Reference(s): QCOP 3700-02 Rev. 29, RBCCW System Startup and Operation Actual Testing Environment:

Simulator Control Room In-Plant Other Testing Method:

Simulate Perform Estimated Time to Complete: 20 minutes Actual Time Used:

minutes EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes No The operators performance was evaluated against standards contained within this JPM and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name (Print):

Evaluators Signature:

Date:

2020 ILT NRC JPM i 2020 ILT NRC JPM i SRRS: 3D.100; There are no retention requirements for this section INITIAL CONDITIONS Unit 1 and 2 are operating at 100% power.

The Unit 1 RBCCW system is on line with the 1A and 1B RBCCW pumps running.

The 1/2 RBCCW pump is in standby.

The 1A RBCCW pump will be taken out of service next shift for planned maintenance.

INITIATING CUE Place the 1/2 RBCCW pump in operation IAW QCOP 3700-02 step F.4.

2020 ILT NRC JPM j SRRS: 3D.105 (when utilized for operator initial or continuing training)

Exelon Nuclear Job Performance Measure RPV Injection Using Condensate System Crosstie JPM Number: 2020 NRC ILT JPM j Revision Number: 11 Date: 08/09/2019 Developed By:

Instructor Date Validated By:

SME or Instructor Date Reviewed By:

Operations Representative Date

2020 ILT NRC JPM j SRRS: 3D.105 (when utilized for operator initial or continuing training)

JOB PERFORMANCE MEASURE VALIDATION CHECKLIST

1.

Task description and number, JPM description and number are identified.

2.

Knowledge and Abilities (K/A) references are included.

3.

Performance location specified. (in-plant, control room, simulator, or other)

4.

Initial setup conditions are identified.

5.

Initiating cue (and terminating cue if required) are properly identified.

6.

Task standards identified and verified by SME review.

7.

Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

8.

If an alternate path is used, the task standard contains criteria for successful completion.

9.

Verify the procedure(s) referenced by this JPM reflects the current revision:

Procedure QCOP 3300-12 Rev: 13 Procedure Rev:

Procedure Rev:

10. Verify cues both verbal and visual are free of conflict.
11. Verify performance time is accurate
12. If the JPM cannot be performed as written with proper responses, then revise the JPM.
13. When JPM is initially validated, sign and date JPM cover page. Subsequent validations, sign and date below:

SME / Instructor Date SME / Instructor Date SME / Instructor Date NOTE: All steps of this checklist should be performed upon initial validation.

Prior to JPM usage, revalidate JPM using steps 9 through 13 below.

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j Revision Record (Summary)

Revision 00, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates. JPM revised to match procedure changes.

Revision 01, JPM revised to match procedure changes.

Revision 02, JPM revised to update estimated times.

Revision 03, JPM revised to match procedure changes.

Revision 04, JPM revised to update estimated times.

Revision 10, 9/18/2018, JPM revised to reflect current procedure revisions and add new template. Revisions 05 through 09 are of the old template and previous procedure revisions. All updates are now included on revision 10.

Revision 11, JPM cues revised.

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j INITIAL CONDITIONS Transient has occurred on Unit 2(1) which requires Alternate Injection Systems to restore RPV water level.

Unit Supervisor has entered QGA 100 and has directed Operator to inject water from Unit 1(2) Condensate system into Unit 2(1) RPV using Condensate system crosstie in accordance with QCOP 3300-12.

The Unit 1(2) Condensate pumps are operating satisfactory.

The Unit 1 and Unit 2 NSOs have been briefed and are standing by to monitor parameters in the Control Room.

There are no Condensate Demin backwashes in progress on either Unit.

You have obtained an S-key from the WEC.

INITIATING CUE Line up Condensate System Crosstie and restore Unit 2(1) RPV water level in accordance with QCOP 3300-12.

EVALUATOR: Provide examinee with a copy of QCOP 3300-12.

Fill in the JPM Start Time when the examinee acknowledges the Initiating Cue.

Information for Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes critical steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section. The comment section should be used to document: the reason that a step is marked as unsatisfactory, marginal performance relating to management expectations, or problems the examinee had while performing the JPM.

Comments relating to procedural or equipment issues should be entered and tracked using the sites appropriate tracking system.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the examinee to direct the local Operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the examinee acknowledges the initiating cue.

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j JPM Start Time:

STEP ELEMENT STANDARD SAT UNSAT Comment Number EVALUATOR NOTE: If examinee elects to manually close the outlet valves, the breakers should be opened first. If this is done, provide cues for each breaker c/s position as they are manipulated.

  • F.2.a.

(1)

OR

  • F.2.a.

(2)

Remotely close all Unit 2(1)

Cond Demin Outlet valves.

OR Manually close all Unit 2(1)

Cond Demin Vessel Discharge Valves.

At Cond Demin panel 2252(1)-

11:

Depresses A through G DEMIN OUTLET E VALVE close pushbuttons and verifies green light lit for each valve.

At Cond Demin panel 2252(1)-

116:

Places c/s for 2(1) H DEMIN OUTLET MO 2(1)-3302H to close and verifies green light lit.

OR At MCC 27-1(17-1):

Places c/s to OFF for A thru H Demin Outlet Valve breakers.

and Locally closes MO 2(1)-3302A through H COND DEMIN VESSEL DSCH VLVS, by depressing declutch lever and rotating handwheel clockwise for each valve.

CUE:

As appropriate point to lights and state, Demin outlet valve green lights are lit. Or if manually closed state, Demin vessel discharge valve handwheels will not rotate any further.

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j STEP ELEMENT STANDARD SAT UNSAT Comment Number F.2.b.

Verify closed Cond Demin Bypass Valve.

At Cond Demin panel 2252(1)-

11 verifies MO 2(1)-3303, COND DEMIN BYPASS VALVE green light lit OR Locally at the Cond Demin bypass valve, verifies green light lit, near MO 2(1)-3303.

OR Contacts CR to verify MO 2(1)-

3303 closed.

CUE:

As appropriate point to light on 2252(1)-11 panel or at light on the Cond Demin Bypass valve and state, Green light is lit.

OR As appropriate report from the Control Room and state, Unit 2(1) Cond Demin Bypass valve indicates closed.

  • F.2.c.

Open the 1-5599-68 valve.

Opens 1-5599-68, U-1 COND HDR TO 1/2 BACKWASH HDR SV by rotating handwheel counterclockwise.

Located south of Unit 1 Cond Demin Precoat Tank.

CUE:

The Handwheel will not rotate any further.

F.2.d.

Verify open Unit 2(1) A and B RX Feedwater Inlet valves.

Contacts Control Room to verify open MO 2(1)-3205A and B, RX FW INLT VLVs, on Panel 902(1)-6.

CUE:

Report from the Control Room and state, Unit 2(1) Reactor Feedwater Inlet valves MO 2(1)-3205A and MO 2(1)-3205B are open.

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j STEP ELEMENT STANDARD SAT UNSAT Comment Number F.2.e.

Verify open a Reactor Feedpump Discharge valve.

Contacts Control Room to verify open MO 2(1)-3201A, B, or C, RFP DISCH VLVs, on Panel 902(1)-6.

CUE:

Report from the Control Room and state, Unit 2(1) RFP discharge valves MO 2(1)-3201A and MO 2(1) 3201B are open.

F.2.f.

Verify the Main and Low Flow Feed Reg valves are in manual and closed.

Contacts Control Room to verify the following feedwater regulating valves are closed and in manual:

2(1)-640-19A, 2(1)A FEEDWATER MAN/AUTO CONT STA.

2(1)-640-19B, 2(1)B FEEDWATER MAN/AUTO CONT STA.

2(1)-640-20, FEEDWATER LO FLOW CONTLR.

CUE:

Report from the Control Room and state, A and B FWRV and the Low Flow FWRV are all in manual and closed.

  • F.2.g.

Unlock the 2-5599-68 valve Unlocks 2-5599-68, U-2 COND HDR TO 1/2 BACKWASH HDR SV.

Located 20 feet east of Unit 1 Cond Demin panel.

  • F.2.h.

Throttle open the 2-5599-68 valve.

Slowly rotates the 2-5599-68, U-2 COND HDR TO 1/2 BACKWASH HDR SV handwheel counterclockwise.

CUE:

The Handwheel will not rotate any further.

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j STEP ELEMENT STANDARD SAT UNSAT Comment Number Report status to Control Room Contacts the U2(1) NSO and reports steps F.2.g and F.2.h are complete.

CUE:

As the NSO acknowledge the report, then state:

The Low Flow FWRV is opening and RPV water level is slowly rising.

EVALUATOR NOTE: Examinee should inform you that the task is complete.

JPM Stop Time:

SRRS: 3D.105 (when utilized for operator initial or continuing training) 2020 ILT NRC JPM j JPM

SUMMARY

Operators Name:

Emp. ID#:

Job

Title:

EO RO SRO FS STA/IA SRO Cert JPM

Title:

RPV Injection Using Condensate System Crosstie JPM Number: 2020 ILT NRC JPM j Revision Number: 11 Task Standard:

Using QCOP 3300-12, locally lineup the Condensate crosstie for emergency injection.

Task Number and

Title:

SRN-3300-P07: (Freq: LIC=B NF=B) Given a reactor plant in a QGA condition, locally crosstie the unit condensate systems to inject into the RPV in accordance with QCOP 3300-12.

K/A Number and Importance: K/A: 295031 EA1.11 Rating: 4.1/4.1 Suggested Testing Environment: Plant Alternate Path:

Yes No SRO Only:

Yes No Time Critical:

Yes No Reference(s): QCOP 3300-12 Rev. 13, Injection into the Reactor Using the Condensate System Crosstie Actual Testing Environment:

Simulator Control Room In-Plant Other Testing Method:

Simulate Perform Estimated Time to Complete: 20 minutes Actual Time Used:

minutes EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes No The examinees performance was evaluated against standards contained within this JPM and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name (Print):

Evaluators Signature:

Date:

2020 ILT NRC JPM j INITIAL CONDITIONS Transient has occurred on Unit 2(1) which requires Alternate Injection Systems to restore RPV water level.

Unit Supervisor has entered QGA 100 and has directed Operator to inject water from Unit 1(2) Condensate system into Unit 2(1) RPV using Condensate system crosstie in accordance with QCOP 3300-12.

The Unit 1(2) Condensate pumps are operating satisfactory.

The Unit 1 and Unit 2 NSOs have been briefed and are standing by to monitor parameters in the Control Room.

There are no Condensate Demin backwashes in progress on either Unit.

You have obtained an S-key from the WEC.

INITIATING CUE Line up Condensate System Crosstie and restore Unit 2(1) RPV water level in accordance with QCOP 3300-12.

SRRS: 3D.100; There are no retention requirements for this section

SRRS: 3D.105 (when utilized for operator initial or continuing training) 11BExelon Nuclear 0BJob Performance Measure 1BLocally Start Diesel Generator with a Failure of Vent Fan 2BJPM Number: 2020 ILT NRC JPM k 3BRevision Number: 24 4BDate: 08/09/2019 5BDeveloped By:

6BInstructor Date 7BValidated By:

8BSME or Instructor Date 9BReviewed By:

10BOperations Representative Date

2020 ILT NRC JPM k SRRS: 3D.100; There are no retention requirements for this section Cabinets/NCS/Training Content/OPERATIONS/Initial License Operator/OPS ILT Quad Cities/JPMs/LP JPMs/LP-003-I-A JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.

Prior to JPM usage, revalidate JPM using steps 9 and 13 below.

1.

Task description and number, JPM description and number are identified.

2.

Knowledge and Abilities (K/A) references are included.

3.

Performance location specified. (in-plant, control room, simulator, or other)

4.

Initial setup conditions are identified.

5.

Initiating cue (and terminating cue if required) are properly identified.

6.

Task standards identified and verified by SME review.

7.

Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

8.

If an alternate path is used, the task standard contains criteria for successful completion.

9.

Verify the procedure(s) referenced by this JPM reflects the current revision:

Procedure QCOP 6600-11 Rev: 33 Procedure QCOA 6600-08 Rev: 11 Procedure QCOA 6600-06 Rev: 12

10. Verify cues both verbal and visual are free of conflict.
11. Verify performance time is accurate
12. If the JPM cannot be performed as written with proper responses, then revise the JPM.
13. When JPM is initially validated, sign and date JPM cover page. Subsequent validations, sign and date below:

SME / Instructor Date SME / Instructor Date SME / Instructor Date

2020 ILT NRC JPM k SRRS: 3D.100; There are no retention requirements for this section Cabinets/NCS/Training Content/OPERATIONS/Initial License Operator/OPS ILT Quad Cities/JPMs/LP JPMs/LP-003-I-A Revision Record (Summary)

Revision 22, JPM revised to match procedure revisions. This JPM was typed new due to loss of previous Microsoft Word versions (reference IR 2658551). Previous versions in EDMS contain a record of previous reasons for revision.

Revision 23, 9/11/2018, JPM revised to reflect current procedure revision and add new template.

Revision 24, Modified cues and delineated critical performance elements in the STANDARD section.

2020 ILT NRC JPM k SRRS: 3D.100; There are no retention requirements for this section INITIAL CONDITIONS A loss of off-site power has occurred on Unit 1.

The Unit 1(1/2) EDG failed to start.

A fire in the plant has damaged fire detection cabling associated with the Unit 1(1/2) EDG Room as indicated by control room alarms.

A manual start from the Control Room was attempted but was not successful due to a faulty control switch.

QCOA 6600-16, Unit 1 Diesel Generator Fails to Start (QCOA 6600-02, Diesel Generator 1/2 Fails to Start) has been entered and another NSO is taking actions directed by that procedure.

Unit 1(1/2) EDG Day Tank level is 90% and the storage tank level is 95%.

INITIATING CUE The Unit Supervisor directs you to locally start the Unit 1(1/2) EDG in accordance with QCOP 6600-11, Diesel Generator Local Operation, to energize Bus 14-1 (13-1). Report to the Unit Supervisor when Diesel Generator is ready to be loaded.

Provide examinee with: Copy of QCOP 6600-11.

Fill in the JPM Start Time when the examinee acknowledges the Initiating Cue.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes critical steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section. The comment section should be used to document: the reason that a step is marked as unsatisfactory, marginal performance relating to management expectations, or problems the examinee had while performing the JPM.

Comments relating to procedural or equipment issues should be entered and tracked using the sites appropriate tracking system.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the examinee to direct the local Operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the examinee acknowledges the initiating cue.

2020 ILT NRC JPM k SRRS: 3D.105 (when utilized for operator initial or continuing training)

JPM Start Time:

STEP ELEMENT STANDARD SAT UNSAT Comment Number CUE:

If asked, report as NSO, Annunciator 901-8 G-8, DIESEL GEN 1 RELAY TRIP (901-8 G-5, DIESEL GEN 1/2 RELAY TRIP) is NOT alarming.

F.2.

Verify MAINTENANCE SW (toggle switch) is in REMOTE AUTO START position.

At the Engine Mounted Control Panel, checks the Maintenance Switch is in the REMOTE AUTO START position.

CUE:

Point to the REMOTE AUTO START position and state, This switch is in this position.

F.3.

Determine status of applicable DG output breaker(s).

Contacts Control Room or dispatches an EO to:

DG 1: Bus 14-1 cub 10.

DG 1/2: Bus 13-1 cub 1 and Bus 23-1 cub 10.

CUE:

As NSO or dispatched EO state, DG output breaker is open.

EVALUATOR NOTE: Step F.4. is N/A. Step F.5. examinee may elect to point at the governor panel rather than climb up on the DG.

F.5.

Verify Governor Speed Droop set at 0.

At the Governor control panel (on the DG), verifies that the upper left knob points at zero.

CUE:

After the examinee identifies the control knob, point to zero and state, The knob points here.

  • F.6.

Isolate DG controls.

At panel 2251-10 for U1 EDG (panel 2212-45 for U1/2 EDG),

isolates DG controls by placing TRANSFER SWITCH to LOCAL.

CUE:

Point to switch and state, This switch is in this position. (point to the position the examinee has indicated)

Unit 1:

Point to the 2251-10 C-1, DIESEL GENERATOR IN LOCAL CONT annunciator and state, You hear a horn and this tile is flashing.

Unit 1/2:

Point to the 2212-45 C-1, DC CONT PWR EM SCE/DG IN LOCAL CONTROL annunciator and state, You hear a horn and this tile is flashing.

EVALUATOR NOTE: The examinee will silence the alarm and may review the alarm procedure before proceeding.

2020 ILT NRC JPM k SRRS: 3D.105 (when utilized for operator initial or continuing training)

STEP ELEMENT STANDARD SAT UNSAT Comment Number F.7.

Notify plant personnel of impending DG start.

Contacts the control room or uses the overhead page via the telephone system to make a plant announcement of impending DG start.

CUE:

As appropriate, acknowledge the direction and inform examinee that he hears an overhead page that the Unit 1(1/2) EDG is to be started.

EVALUATOR NOTE: Double hearing protection is required. This may be simulated by the examinee.

  • F.8.

Start DG.

Depresses DG START pushbutton, located on Engine Mounted Control Panel.

CUE:

As the EO at Bus 14-1 (bus 13-1) report, Diesel Generator output breaker has closed.

ALTERNATE PATH STARTS HERE.

F.9 Verify DG Room Vent Fan automatically starts.

Monitors for an increased air flow and/or verifies red run light lit for DG Room Vent Fan.

CUE:

As appropriate, point to the red light and state This light is NOT lit or state, Air flow through the room has NOT changed.

CUE:

If examinee chooses to align the alternate power source to the vent fan by placing the VENT FAN SELECTOR SWITCH to ALT (Limitations and Actions step E.2.), then give the following cues as the examinee points to the indications:

(Alternate power yellow light), This light is lit.

(Vent fan red light), This light is not lit.

(Vent fan green light), This light is lit.

(Air flow through the room), Air flow through the room has not changed.

EVALUATOR NOTE: Per the initial conditions, examinee will identify that the Vent Fan is locked out due to cable damage. The Vent Fan Fire Protection Bypass Switch may be moved to Bypass per Limitations and Actions step E.3. OR the examinee may use QCOA 6600-08 for Unit 1 EDG (QCOA 6600-06 for 1/2 EDG). The steps below are numbered from QCOA 6600-08 and are located at panel 2251-37 for Unit 1 EDG and panel 2212-50 for 1/2 EDG.

2020 ILT NRC JPM k SRRS: 3D.105 (when utilized for operator initial or continuing training)

STEP ELEMENT STANDARD SAT UNSAT Comment Number D.2.b.(1)

Open Diesel Generator Room Vent fan key locked box.

Uses an object to break the glass covering the panel OR retrieves the key from the WEC.

Unlocks and opens Diesel Generator Room Vent Fan key locked box.

CUE:

As appropriate state, The glass has been broken OR An EO has brought you the key from the WEC. Then state, Diesel Generator Room Vent fan key locked box is open.

  • D.2.b.(2) Place D.G. 1 VENT FAN FIRE PROTECTION BYPASS SWITCH in BYPASS.

Moves U1 DG Vent Fan Fire Protection Bypass switch to BYPASS.

CUE:

Point to the (BYPASS position) of the switch and state, This switch is in this position and the RED light is lit.

As appropriate, inform examinee he feels additional air flow through the room.

D.2.b.(3)

Close and lock Diesel Generator Room Vent Fan key locked box.

Closes and locks Diesel Generator Room Vent Fan key locked box.

CUE:

As appropriate state, Diesel Generator Room Vent Fan key locked box is now closed and locked.

D.4 Verify proper operation of associated dampers.

Looks at the damper position and verifies the vent louvers are open.

CUE:

As appropriate state, Vent louvers are open.

EVALUATOR NOTE: The following steps are in QCOP 6600-11.

F.10 Verify DGCWP automatically starts.

Verifies DGCWP red run light lit on the 2251-37 panel for Unit 1 EDG (2212-50 panel for 1/2 EDG).

OR Verifies increase pressure on DG HX SW gauges.

OR Observes flow meter outside DG room > 900 gpm, FI 1-3941-26 for Unit 1EDG (FI 1/2-3941-27 for 1/2 EDG)

2020 ILT NRC JPM k SRRS: 3D.105 (when utilized for operator initial or continuing training)

STEP ELEMENT STANDARD SAT UNSAT Comment Number CUE:

As appropriate, respond with the following:

Point to the red run light and state This light is lit.

Indicate 50 psig on the DG HX pressure gage and state, The indicator points here.

Indicate 950 gpm on the Flow Indicator and state, The indicator points here.

CUE:

The following indications are on the 2251-10 panel for Unit 1 EDG and 2212-45 panel for 1/2 EDG.

F.11 Verify DG Frequency is at 60 Hz.

At Panel 2251-10 (2212-45),

verifies DG Frequency is 60 Hz.

CUE:

Point to 60Hz on the Frequency meter and state, Indicator points here.

F.12 Verify DG Voltage is at 4160 Volts.

At Panel 2251-10 (2212-45),

verifies DG Voltage is 4160 Volts.

CUE:

If asked about Generator speed point to 900 RPM on the local tachometer and state, The meter reads here and the Digital indication reads 900 RPM.

The 1/2 EDG has analog indication only.

CUE:

Point to 4160 Volts on the Voltage meter and state, Indicator points here.

Notify Control Room (Unit Supervisor) Diesel Generator is ready to be loaded.

Contacts the Control Room and reports Diesel Generator status.

CUE:

As the Unit Supervisor, acknowledge DG status and state, Another Operator has been dispatched to monitor DG voltage, frequency, and load.

EVALUATOR: Examinee should inform you that the task is complete.

JPM Stop Time:

2020 ILT NRC JPM k SRRS: 3D.105 (when utilized for operator initial or continuing training)

JPM

SUMMARY

Operators Name:

Emp. ID#: ____________

Job

Title:

EO RO SRO FS STA/IA SRO Cert JPM

Title:

Locally Start Diesel Generator with a Failure of Vent Fan JPM Number: 2020 ILT NRC JPM k Revision Number: 24 Task Standard:

Using QCOP 6600-11 start the U1(1/2) EDG and when the vent fan failure is identified use step E.3 or QCOA 6600-08(06) to start the EDG room vent fan.

Task Number and

Title:

SRN-6600-P04: (Freq: LIC=B N=B) Given a condition where the 1/2 (U1) Emergency DG has failed to auto start, Bus 18 (19) is de-energized, and fire detection cable damage has locked out the 1/2 (U1) DG vent fan, locally start the 1/2 (U1) Emergency DG and energize Bus 13-1 (14-1) in accordance with QCOP 6600-11, QCOA 6600-06 (QCOA 6600-08) and QOP 6500-

10.

K/A Number and Importance:

K/A: 264000 A3.03 Rating: 3.4/3.4 Suggested Testing Environment: Plant Alternate Path:

Yes No SRO Only:

Yes No Time Critical:

Yes No Reference(s): QCOP 6600-11, Rev. 32, Diesel Generator Local Operation QCOA 6600-06, Rev. 12, 1/2 Diesel Generator Room Vent Fan Failure QCOA 6600-08, Rev. 11, Unit 1(2) Diesel Generator Room Vent Fan Failure Actual Testing Environment:

Simulator Control Room In-Plant Other Testing Method:

Simulate Perform Estimated Time to Complete: 20 minutes Actual Time Used:

minutes EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes No The examinees performance was evaluated against standards contained within this JPM and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name (Print):

Evaluators Signature:

Date:

2020 ILT NRC JPM k SRRS: 3D.100; There are no retention requirements for this section INITIAL CONDITIONS A loss of off-site power has occurred on Unit 1.

The Unit 1(1/2) EDG failed to start.

A fire in the plant has damaged fire detection cabling associated with the Unit 1(1/2) EDG Room as indicated by control room alarms.

A manual start from the Control Room was attempted but was not successful due to a faulty control switch.

QCOA 6600-16, Unit 1 Diesel Generator Fails to Start (QCOA 6600-02, Diesel Generator 1/2 Fails to Start) has been entered and another NSO is taking actions directed by that procedure.

Unit 1(1/2) EDG Day Tank level is 90% and the storage tank level is 95%.

INITIATING CUE The Unit Supervisor directs you to locally start the Unit 1(1/2) EDG in accordance with QCOP 6600-11, Diesel Generator Local Operation, to energize Bus 14-1 (13-1). Report to the Unit Supervisor when Diesel Generator is ready to be loaded.