ML20149H327
| ML20149H327 | |
| Person / Time | |
|---|---|
| Site: | Catawba |
| Issue date: | 07/21/1997 |
| From: | Berkow H NRC (Affiliation Not Assigned) |
| To: | |
| Shared Package | |
| ML20149H329 | List: |
| References | |
| NUDOCS 9707240336 | |
| Download: ML20149H327 (8) | |
Text
_
- 1og p
t UNITED STATES g
).
NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 30606 4 001 l
'A
/
DUKE POWER COMPANY NORTH CAROLINA ELECTRIC MEMBERSHIP CORPORATION SALUDA RIVER ELECTRIC COOPERATIVE. INC.
DOCKET NO. 50-413
, CATAWBA NUCLEAR STATION. UNIT 1 i-AMENDMENT TO FACILITY OPERATING LICENSE-Amendment No.160 License No. NPF-35 j
1.
The Nuclear Regulatory Commission (the Commission) has found that:
L A.
The application for amendment to the Catawba Nuclear. Station.
-Unit 1 (the' facility) Facility Operating License No. NPF-35 filed by the Duke Power Company, acting for itself,' North Carolina Electric Membership Corporation and Saluda River Electric Cooperative, Inc. (licensees), dated May 27, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations J
l as set forth in 10 CFR Chapter I; 1
B.
The facility will operate in conformity with the application, the l
provisions of the Act, and the rules and regulations of the -
j
_ Commission; C.
-There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted-in compliance with the Commission's regulatior.s set-forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common
- defense and security or to the health and safety of the public; and
' E.
The issuance of this amendment-is in accordance with 10 CFR Part 51 of the. Commission's regulations and all applicable requirements have been satisfied.
L i
i-9707240336 970721 PDR ADOCK 05000413 P
PDR l
. v.
- -. - -. -.~.=_. -. - - -.- -.- -..... -.
. -. - - -. -.. ~ -
I l
- 2.
.Accordingly, the license is hereby amended by page changes-to the.
Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Facility Operating License No.
- NPF-35 is hereby' amended to read as follows:
-(2)
Technical Soecifications The Technical Specifications contained in Appendix A, as revised through Amendment No.160, which are attached-hereto, are hereby incorporated into this license.
Duke Power Company shall operate the facility.in accordance with-the Technical Specifications.
3.
This license amendment is-effective as of its date of issuance and shall be implemented within 30 ' days of issuance..
I FOR THE NUCLEAR REGULATORY COMMISSION H b rt N. Berkow, Director P oject Directorate 11-2
(
(
Division of Reactor Projects - 1/II Office of Nuclear Reactor Regulation
]
Attachment:
Technical Specification Changes l
Date of Issuance: July 21, 1997 l
l i-
. =...-- -
I i
ATTACHMENT TO LICENSE AMENDMENT NO.160 FACILITY OPERATING LICENSE NO. NPF-35 DOCKET NO. 50-413 L
Replace the following page of the Appendix "A" Technical Specifications with the enclosed page. The revised page is identified by Amendment number and l
contains vertical lines indicating the areas of change.-
Remove Insert 3/4 7-33 3/4 7-33 l
l c
t l
1 I
l
PLANT SYSTEMS SURVEILLANCE REOUIREMENTS (Continued) 4.7.13.2 The Standby Shutdown System diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
1 At least once per 7 days by verifying that:
a.
1)
The electrolyte level of each battery is at or above the low mark and at or below the high mark;-and.
2)
The overall battery voltage is greater than or equal to 24 volts on float charge.
b.
At least once per 92 days by ' verifying that the individual cell voltage is. greater than or equal to 1.36 volts on float charge, and l
At least once per 18 months by verifying that:
c.
1 li The batteries, cell plates, and battery racks show no visual indication of physical damage or abnormal deterioration, and 2)
The battery-to-battery and terminal connections are clean, tight, and free of corrosion.
4.7.13.3 The Standby Makeup Pump water supply shall be demonstrated OPERABLE by:
a.
Verifying at least once per 7 days that the requirements of l
Specification 3.9.10 are met and the boron _ concentration in the storage pool is greater than or equal to the minimum specified in.
the Core Operating Limits P.eport.
b.
Verifying at least once per 92 days'that the Standby Makeup Pump develops a flow.of greater than or equal to 26 gpm at a pressure greater than or equal to 2488 psig.
4.7.13.4 The Standby Shutdown System 250/125-Volt Battery Bank and its-associated charger shall be demonstrated OPERABLE:
a.=
At least once per 31 days by verifying:
1)
That the electrolyte level of each battery is above the plates, and l
. CATAWBA - UNIT 1 3/4 7-33 Amendment No.160
a nun k
UNITED STATES g
j NUCLEAR REGULATORY COMM SSION p
WASHINGTON, D.C. 30806 4 001 j
i i
~
DQKE POWER COMPANY l
NORTH CAROLINA MUNICIPAL POWER AGENCY NO. 1 i
PIEDMONT MUNICIPAL POWER AGENCY DOCKET NO. 50-414 4
CATAWBA NUCLEAR STATION. UNIT 2 F
AMENDMENT TO FACILITY OPERATING LICENSE I:
j f'
Amendment No.152 l-License No. NPF-52 1.
The Nuclear Regulatory Commission (the Commission) has found that:
j:
A.
The application for amendment to the Catawba Nuclear Station, Unit 2 (the facility) Facility Operating License No. NPF-52 filed by the Duke Power Company, acting for itself, North Carolina Municipal.
[
Power Agency No. I and Piedmont Municipal Power Agency-(licensees),
F dated May 27, 1997, complies with the standards and requirements of i
the Atomic Energy Act of 1954, as amended (the Act), and the i
Comission's rules and regulations as set forth in 10 CFR. Chapter I; B.
The facility will operate in conformity with the application, the i
provision; of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (i) that the activities authorized by l
this amendment can be conducted without endangering the health-and safety of the public, and (ii) that such activities will be-i-
conducted in compliance with.the Commission's regulations set forth in 10 CFR Chapter I; 4
D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and.
E.
The issuance of this amendment is in accordance with 10 CFR Part 51-of the Commission's regulations and all applicable requirements have been satisfied.
1 l
1 I
i
< 2.
Accordingly, the license is hereby amanded by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Facility Operating License No. NPF-52 j '
is hereby amended to read as follows:
(2)' Technical Soecifications l
The Technical Specifications contained in Appendix A, as revised through Amendment No.152, which are attached hereto, are hereby incorporated into this license. Duke Power Company shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days of issuance.
l FOR THE NUCLEAR REGULATORY COMMISSION Her ert N. Berkow, Director Project Directorate II-2 l
Division of Reactor Projec.ts - I/II Office of Nuclear Reactor Regulation
Attachment:
Technical Specifications Changes l
Date of Issuance:
July 21, 1997 t
l t
I L
l
[-
ATTACHMENT TO LICENSE AMENDMENT NO.152 ffCILITY OPERATING LICENSE NO. NPF-52 l
DOCKET NO. 50-414 Replace'the following page of the Appendix "A" Technical Specifications with the enclosed page. The, revised page is identified by Amendment number and contains vertical lines indicating the areas of change.
.1 Etsgyg Insert i.
3/4 7-34 3/4 7-34 l-l l
l l
l l
l I
i j
1 i
l i
PLANT' SYSTEMS SURVEILLANCE REOUIREMENTS (Continued) 4.7.13.2 The Standby Shutdown System diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
a.
At least once per.7 days by verifying that:
'1)
Tiie electrolyte level of each battery is at or above the low mark and at or below the high' mark; and 2)
The overall' battery _ voltage is greater than or equal to'24 volts on float charge.
b.
At least once per 92 days by verifying that the individual cell voltage is greater than or equal'to 1.36 volts on float charge, and c.
At_least once per'18 months by verifying that:
1)
The batteries, cell plates, and battery racks show no visual indication of physical damage or abnormal deterioration, and 2)
The battery-to-battery and terminal connections are clean, tight, and free of corrosion.
4.7.13.3 The Standby Makeup Pump water supply shall be demonstrated OPERABLE by.
a.
Verifying at least once per 7 days that the requirements of l
Specification 3.9.10 are met and the boron concentration in the storage pool is greater than or equal to the minimum specified in the Core Operating Limits Report.
b.
Verifying at least once per 92 days that the Standby Makeup Pump develops a flow of greater than or equal to 26 gpm at a pressure greater than or equal to 2486 r,sig.
4.7.13.4 The Standby Shutdown System 250/125-Volt Battery Bank and its associated charger shall be demonstrated OPERABLEi a.
At least once per 31 days by verifying:
1)
That the electrolyte level of each battery is above the plates, and i
CATAWBA - UNIT 2 3/4 7-34 Amendment No.152 i