UNITED STATES NUCLEAR REGULATORY COMMISSION If WASHINGTON, D.C. 20555-0001 July 22,1997 b'
Mr. H. B. Barron l
Vice President, McGuire Site l
Duke Power Company 12700 Hagers Ferry Road Huntersville, North Carolina 28078
SUBJECT:
COMPLETION OF LICENSING ACTION FOR GENERIC LETTER 96-01,
" TESTING 0F SAFETY-RELATED LOGIC CIRCUITS," DATED JANUARY 10, 1996 MCGUIRE, UNIT 1 (TAC N0. M94695)
Dear Mr. Barron:
On January 10, 1996, the U.S. Nuclear Regulatory Commission (NRC) issued Generic letter (GL) 96-01, " Testing of Safety-Related Logic Circuits," to all holders of operating licenses or construction permits. The NRC issued GL 96-01 for three principal reasons:
l 1.
Notify addressees about problems with testing of safety-related logic circuits; 2.
Request that all addressees implement the actions described within the generic letter; and l
3.
Require that all addressees submit to the NRC a written response regarding implementation of the requested actions.
In GL 96-01, the NRC staff specifically requested that licensees take the following actions:
i 1.
Compare electrical schematics and logic diagrams for the reactor protection system,' emergency diesel generator load shedding and sequencing, and actuation logic for the engineered safety feature 4
systems against plant surveillance test procedures to ensure that all portions of the logic circuitry, including the parallel logic, interlocks, bypasses, and inhibit circuits, are adequately covered in l
the surveillance procedures to fulfill the. technical specification requirements.
This review should also include relay contacts, control switches, and other relevant electrical components within these systems, utilized in the logic circuits performing a safety function; and 2.
Modify the surveillance procedures as necessary for complete testing to comply with the technical specifications. Additionally, the licensee may request an amendment to the techr.ical specifications if relief from certain testing requirements can be justified.
bYOl l
D 9707240236 970722 gh h
DR ADOCK 0500 9
_ =.
i.
s i
L H. B. Barron..
2-July 22,1997 Furthermore, the NRC staff required that addressees prepare and submit the following:
1.
A written response indicating whether.or not the licensee would implement the actions requested above or propose an alternative action;-
l 2.
A schedule for completing the requested actions or proposed alternative; and 3.
A response confirming completion of the requested actions.
In response to GL 96-01, you provided letters dated April 17, 1996, and June'12, 1997, for McGuire, Unit 1.
These submittals provided both the information requested and the responses required by GL 96-01; therefore, TAC No. M94695 is closed.
If you have any questions-regarding this matter, please contact me at 301-415-1484.
Sincerely, ORIGINAL SIGNED BY-l Victor Nerses, Senior Project Manager Project Directorate II-2 Division of Reactor Projects - I/II-Office of Nuclear Reactor Regulation Docket No. 50-369 cc:
See next page DISTRIBUTION:
Docket File HGarg
~ UBLIC ACRS P
PDII-2 RF OGC BBoger HBerkow
.VNerses LBerry JJohnson,RII
- SShaeffer (A),RII DOCUMENT NAME:
G:\\MCGUIRE\\9601.LTR To receive a copy of thle document, indicate in the box: "C" = Copy without enclosures
- E' = Copy with enclosures *N* = No copy N
OFFICE PDII.,2/_PM l#
PDII-2/LO d
HICB:NRR l
PDIld/Q l NAME y_.N(R9E6' L. BERRY V dl, H.GARG
- 6@
H.E)ERW DATE 1/p/ /97 1 / 9 /97 \\
7 /2W97 1 / n /97 0FFICIAL RECORD COPY
=,
\\
l H. B. Barron t Furthermore, the NRC staff required that addressees prepare and submit the following:.
1.
A written response indicating whether or not the licensee would L
implement the actions requested above or propose an alternative action; 2.
A schedule for completing the requested actions or proposed l
alternative; and l
3.
A response confirming completion of the requested actions.
l i
In respor.se to GL 96-01, you provided letters dated April'17, 1996, and June 12, 1997, for McGuire, Unit 1.
These submittals provided both the l
information requested and the responses required by GL 96-01; therefore, TAC l
No. M94695 is closed.
i If you have any questions regarding this matter, please contact me at j
301-415-1484.
Sincerely, i
Victor Nerses, Senior Project Manager i
Project Directorate 11-2 l
Division of Reactor Projects - I/II L
Office of Nuclear Reactor Regulation i
Docket Nos. 50-369 l
l cc:
See next page L-1 5
l i.
i
f,
g.
I l
l MgGuire Nuclear Station Units 1 and 2 cc:
Mr. Paul R. Newton Ms. Karen E. Long Legal Department (PB0SE)
Assistant Attorney General Duke Power Company North Carolina Department of j
422 South Church Street Justice Charlotte, North Carolina 28242-0001 P. O. Box 629 I
County Manager of Mecklenburg County 720 East Fourth Street Mr. G. A. Copp Charlotte, North Carolina 28202 Licensing - EC050 Duke Power Company
-Michael T. Cash 526 South Church Street Regulatory Compliance Manager Charlotte, North Carolina 28242 Duke Power Company McGuire Nuclear Site Regional Administrator, Region II i
l 12700 Hagers Ferry Road U.S. Nuclear Regulatory Commission l
Huntersville,~ North Carolina 28078 Atlanta Federal Center 61 Forsyth Street, S.W., Suite 23T85 J. Michael McGarry, III, Esquire Atlanta, Georgia 30303 Winston and Strawn l
1400 L' Street, NW.
Elaine Wathen, Lead REP Planner Washington, DC 20005 Division of Emergency Management 116 West Jones Street
-Senior Resident Inspector Raleigh, North Carolina 27603-1335 c/o U. S. Nuclear Regulatory i
Commission.
Mr. Richard Fry, Director l
12700 Hagers Ferry Road Division of Radiation Protection Huntersville, North Carolina 28078 i
North _ Carolina Department of Environment, Health and Natural Mr. Peter R. Harden, IV Resources Account Sales Manager P. O. Box 27687 i
i Westinghouse Electric Corporation Raleigh, North Carolina 27611-7687 i-Power Systems Field Sales l.
P. O. Box-7288 l
Charlotte, North Carolina 28241 Dr.' John M. Barry l
Mecklenberg County LDepartment of Environmental Protection 700 N. Tryon Street Charlotte, North Carolina 28202 Mr. T. Richard Puryear Owners Group.(NCEMC)-
Duke Power Company 4800 Concord Road
. York, South Carolina 29745
-,