Final Deficiency Rept CP-83-11 Re Component Cooling Water Class 5 Piping.Initially Reported on 830621.Pipe Stresses & Support Loads & Nozzle Loads Determined within Design Limits & Seismically Acceptable
ML20149G220
Person / Time
Site: Comanche Peak  
Issue date: 02/12/1988
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-83-11, TXX-88211, NUDOCS 8802180176
Download: ML20149G220 (2)


Text

%

MFE log i TXX-88211 fi1e # 10110

._.=

r 903.7 Ref. # 10CFR50.55(e) i nlELECTRIC

% mm G. coemu nuwaaue n,w,.

February 12, 1988 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCllE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 COMPONENT COOLING WATER CLASS 5 PIPING SDAR:

CP-83-11 (SUPPLEMENTALREPORT)

Gentlemen:

On June 21, 1983, by our re) ort logged TXX-3690, we notified you of a reportable item regard'ing t1e Component Cooling Water System Class 5 Piping under the provisions of 10CFR50.55(e).

The item was subsequently identified in our last report logged TXX-6435, dated May 13, 1987, as an item for which the originally scheduled completion date for the implementation of corrective actions had elapsed but the implementation of those actions is still in progress.

This report is submitted to status the implementation of those corrective actions.

As described in our report logged tax-3690, a level'bi-stable has been added to the existing level transmitter on both Train A and Train B of the Surge Tanks.

This bi-stable will sense when the tank is empty and provide automatic isolation of both safeguard loops and the non-safeguard loop, and annunciate in the control room.

We have completed a reanalysis of the associated piping to verify seismic adequacy. We have determined that pipe stresses, pipe support loads, and nozzle loads are within design limits, therefore the piping is seismically acceptable as currently installed.

Y ft 8802100176 800232 DR ADOCK 050 5

O KC Meth Obvr Sirret LB 81 Dall.u. Tenas 13.'01 i

l

h::

I>

M fo TXX-88211 February 12, 1988 Page 2 Our corrective action for this issue is complete.

Supporting documentation is avai?able at the CPSES site for your Inspector's review, Very truly yours, W. G. Counsil l

CBC/mlh l

c-Mr. R. D. Martin, Region VI Resident inspectors CPSES (3) i l

l I