APPENDIX A NOTICE OF VIOLATION GPU Nuclear Corporation Docket No. 50-289 Three Mile Island, Unit No. 1 License No. DRP-50 As a result of an inspection conducted on October 2-31, 1987, and, in accordance with the NRC Enforcement Policy (10 CFR 2, Appendix C), the following violation was identified:

Technical Specification 6.8.1 states, "Written procedures important to safety shall be implemented... covering the applicable procedures recommended in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978...."

Appendix A of Regulatory Guide 1.33, Revision 2, lists procedures for bypass of safety functions and jumper control" and also for "surveillance tests and calibrations." Step 6.14 of Preventive Maintenance Procedure IC-15, Revision 5, dated February 20, 1986, associated with the calibration check of nuclear river water pump differential pressure (D/P) switches requires the use of a jumper and lifted lead verification per AP 1013, Enclosure 5 for important-to-safety equipment.

Contrary to the above, on October 14, 1987, leads for important to safety D/P switch NR-DPS-138 were lif ted and reconnected without completion of the requirements of AP 1013, Enclosure 5.

Additionally, the appropriate step of procedure IC-15, Step 6.14, was marked "N/A" when in effect it should have been performed as required by 10-15.

This is a Severity Level V violation (Supplement I).

Licensee corrective actions taken or planned are adequate as documented in the attached inspection report.

Accordingly, no response to the violation is required.

B801120271 871228 PDR ADOCK 05000289 0FFICIAL RECORD COPY IR TMll 87 0012.0.0 0

DCD 12/22/87