ML20148J082

From kanterella
Jump to navigation Jump to search
Forwards IE Circular 78-18
ML20148J082
Person / Time
Site: Summer 
Issue date: 11/06/1978
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Mary Johnson
SOUTH CAROLINA ELECTRIC & GAS CO.
References
NUDOCS 7811150122
Download: ML20148J082 (1)


Text

.. ___________

TSRA f

-p

  1. p ** RI g8,

s Gut UNITED ST ATES NUCLEAR REGULATORY COMMISSION 07

%.s s, <

y c(

g REGION ti E

101 M ARIETT A STRE E T, N.W.

8 ATL ANT A. GEORGI A 30303 o

/

h.

1979 In Reply Refer To:

RII:JPO 50-395 South Carolina Electric and Gas Company Attn:

Mr. M. C. Johason, Vice President and Group Executive - Special Services and Purchasing P. O. Box 764 Columbia, South Carolina 29218 Gentlemen:

The enclosed Circular 78-18 is forwarded to you for information.

No specific action is requested and no written response is required.

If you desire additional information regarding this clatter, please contact this office.

Sincerely.

/i.

, James P..'O'Reilly

' Director

Enclosures:

1.

IE Circular 78-18 2.

List of IE Circulars Issued in 1978 cc w/ enc 1:

Mr. H. I. Donnelly, Jr.

Quality Assurance P. O. Box 8 Jenkinsv113c, South Carolina 29065 Mr. T. B. Conners, Jr.

Conners, Moore and Corber 1747 Pennsylvania Avenue, N. W.

Washington, D. C.

20006 7 8113 5 9, g_y

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C.

20555 November 6, 1978 IE Circular 78-18 1

UL FIRE TEST

Background

On September 15, 1978, a fire test of a full-scale vertical cable tray array was conducted at the Underwriters Laboratory (UL) near Chicago, Illinois.

It was part of the fire protection research program managed by Sandia Laboratories under NRC contract. The purpose of the test was to demonstrate the effectiveness of area sprinklers and cable tray fire barriers constructed of ceramic fiber blankets in preventing damage to cables as a result of an exposure to a flammable liquid fire.

The test resulted in damage to some electrical cables.

Discussion The configuration of the fire test was selected to simulate a section of a plant area with vertical cable trays containing redundant safety divisions arranged such that the redundant divisions could be simul-taneously exposed to a potential fire resulting from an inadvertent spill of flammable liquid in the area.

The arrangement of the cable trays and the designation of the redundant tray divisions is shown in Figure 1.

Figure 2 shows the lecation of the fire detectors and the three groups of sprinklers.

Each of the five cable trays centained cable insulated with polyvinyl chloride and was enclosed in a separated ceramic fiber blanket fire barrier from floor to ceiling in accordance with the manu-facturer's recommendations.

The sprinkler and detector arrangement was as permitted by NFPA Code.

However, no water was actually used at any time during t his test due to the failure of some sprinkler heads te actuate, as explained below.

Each sprinkler location in the test arrangement contained three nomina 11v identical temperature sensing sprinkler heads with fusible links adjacent to an open sprinkler head which was connected to a manual water supply valve.

The temperat ure sensing heads were wired to signal when their links fused.

Af t er all three t emperat ure sensing heads at a given loca-tion activated, then the water supply for the open head was to be manually admitted.

The sprinklers were of a type which actuate at the slow end of acceptance for reaction time.

The test procedure required that all three temperature sensing heads had to activate before wat er would be turned on.

In this way, it was expected to get some data on variability in the response time of identical sprinklers, pu M - 781Hsooop-

a Novceber 6, 1978 IE Circular 78-18 Test Details The test was started by igniting the two gallons of heptane that was poured into the floor pan.

A fully developed fire occurred almost immediately. The ceiling smoke detector alarmed in about 15 seconds.

In about 50-60 seconds, two of the three temperature sensing sprinklers located between the wall and cable trays 1 and 2 activated.

The fire between cable trays 1, 2, 3, and 4 appeared most intense, apparently because of a chimney effect between the four trays.

The flames between cable trays 3 and 5 did not appear to be so intense. The ceramic fiber blanket absorbed some of the heptane so that after the heptane in the pan burned, most of the flame seemed to come from the bottom outside surface of the ceramic fiber blanket.

No additional temperature sensing sprinkler heads at any location activated; thus, the sprinkler water supply was not turned on for any of the three sprinkler locations.

The apparent slow response of the third temperature sensing sprinkler is being investigated, since this was not intended to be a slow response sprinkler.

At about 3 minutes into the test there was an indication of a short circuit in cable tray 3, which was probably caused by the fire.

After 5-7 minutes the height of the flames appeared to subside; however, residual flames continued for about 40 minutes.

Preliminary Results and A%1yses Preliminary information indicates that the flammable liquid or flames penetrated the protective barriers at the bottom of the vertical trays and caused fire damage to the polyvinyl chloride insulation on cables in four of the five trays.

On subsequent 500-volt megger tests, it was found that another cable in tray 2 had also experienced some damage, as evidenced by a conductor to ground short.

The most probable cause of the fire damage in certain cable trays appears to be related to the absorption or seepage of heptane under the ceramic fiber blanket at the juncture with the floor.

Once the heptane entered the interior regions of the cable tray, then ignitien apparently occurred via the small opening at the floor or through a vaper/ air path within the joints.

There is some indication that some cable damage was caused by absorption of hept ane on the inside of the barrier (vicking ef f ect) and its ignition which heated a cable tray ladder rung, causing damage to a cable in contact with the rung. The ingress of the heptane into the ceramic fiber needs to be further evaluated since this appears to be the most significant failure mode.

I November 6, 1978 IE Circular 78-18 Tentative Conclusions The test results are still being analyzed, and it would be premature to establish firm conclusions at this time; however, the results now available l

indicate that the following areas of the fire protection program need j

close consideration:

1 1.

To protect against spills of flammable liquids, barriers or curbs may be needed to prevent entry of the flammable liquid behind fire barriers. A wick effect may also need to be considered in the design of fire barriers.

2.

Some small fires may not actuate sprinkler heads.

To reduce this possibility in sprinkler systems to be installed, fast response sprinkler heads should be considered (less than approximately 3 minutes in the UL Standard 199 " Automatic Sprinklers for Fire Protection Service").

3.

The location of the fire detection devices and the sprinkler heads relative to the fire and components being protected is of great importance. The path of the air movement in the area influences the actuation of such devices and should be considered in the system layout.

The final results of this test will be issued when the analysis of the test is complete.

This circular is being issued for information only.

No specific action is requested and no written response is required.

If you desire addi-tional information regarding this matter, centact the Director of the appropriate NRC Regional Office.

At t ac hment s :

1.

Figure 1 2.

Figure 2

l l

IE Circular No. 78-18 l

November 6, 1978 LISTING OF IE CIRCULARS ISSUED IN 1978 Circular Subject Date Issued To No.

of Issue 78-01 Loss of Well Logging 4/5/78 All Holders of Source Well Logging Source Licenses 78-02 Proper Lubricating 011 4/20/78 All Holders of for Terry Turbines Reactor OLs or cps 78-03 Packaging Greater Than 5/12/78 All Holders of Type A Quantities of Reactor OLs, cps, Low Specific Activity Puel Cycle, Radioactive Material Priority I Material for Transport and Waste Disposal Licenses 78-04 Installation Error That 5/15/78 All Holders af Could Prevent Closing of Reactor OLs or Fire Doors cps 78-05 Inadvertent Saf ety inj ection 5/23/78 All Holders of During Cooldown Reactor OLs or cps 78-06 Potential Common Mode 5/23/78 All Holders of Flooding of ECCS Equipment Reactor OLs or Rooms at BWR Facilities cps 78-07 Damaged Components of a 5/31/78 All Holders of Bergen-Paterson Series Reactor OLs er 25000 Hydraulic Test cps Stand 78-08 Environmental Qualification 5/31/78 All Holders of of Safety Related Equipment Reacter OLs er at Nuclear Power Plants cps 78-09 Arcing of General Electric 6/5/78 All Holders of Company Size 2 Contactors cps Enclosure Page 1 of 2

IE Circular No. 78-18 November 6, 1978 LISTING OF IE CIRCULARS ISSUED IN 1978 Circular Subject Date of Issued to No.

Issue 78-10 Control of Sealed 6/14/78 All Medical Sources Used in Licensees in Radiation Therapy Categories G and G1 78-13 Recirculation M-G 6/15/78 All Holders of Set Overspeed Stops BkT OLs or cps 78-12 HPCI Turbine Control 6/30/78 All Holders of Valve Lift Rod Bending BWR OLs or cps for plants with HPCI Terry Turbine 78-13 Inoperability of Multiple 7/10/78 All Holders of Service Water Pumps Reactor OLs and cps except for plants located in: AL, AF.,

CA, FL, GA, LA, SC 78-14 HPCI Turbine Reversing 7/12/78 All Holders of Bb7 Chamber Hold Down Bolting OLs or cps for plants with a HPCI Terry Turbine excepting Duane Arnold and Monticelle 78-15 Checkvalves Fail to 7/20/78 All Holders of Close In Vertical Reactor OLs or cps Position 78-36 Limitorque Valve 7/26/78 All Holders of Actuators Reactor OLs cr cps 78-17 Inadequate Guard Training /

10/13/78 All Holders of Qualification and Falsified and applicants Training Records for Reactor OLs.

Enclosure Page 2 of 2

Figure 1 1

approximate boundary

~~~

of pan for liquid spill fire

/

77 / / / / / / / / / '/ f 1 / / / f / / / / / -(

/

/

o

/'

M 3"k-

/

-- r M, - TIg

/

{o.v i l

I_ 055 1 JL g

I,' O k,,

/

i e

I

-3 y_Div i l

l C %__l

/

8 l

/

l L

7 ll O sv 1 J!

f I

Y s W It" i

e

,___1

--s Yertical Tray Corner Test

h e

4 es

(

_~%~

O c__

h k

  • --N L*, -

s s,L L, 0

4 t

1 e

  • e t

w a

[

e en 4l a

'Hr J

k 9

c' 5

4 m

L 2

f h

G 4

N y

m E

's g.3 C8 8

5.

LO 4

g 4,

go--

4

. J L.

l o.A g

54 ~

A T[^i d

34 bg

'N1 3

x=

l-t i b

o