Forwards Request for Addl Info to Continue Review of Proposed Tech Specs Re Primary Leakage Testing & Request for Exemption from Requirements in App J
ML20148H387
Person / Time
Site: Yankee Rowe
Issue date: 09/11/1975
From: Purple R
Office of Nuclear Reactor Regulation
To: Andognini G
YANKEE ATOMIC ELECTRIC CO.
References
NUDOCS 8011180275
Download: ML20148H387 (2)


Text

.

( -

O- -

e

< ~ mg

} ,)

F .g.

g DISTRIBlTTION g I Docket File Docket No. 50-29 SEP 111975 NRC PDR '7I

'{ Local PDR j d i

ORB #1 Reading ,

i KRGoller 0 TJCarter I ,

h OELD 4. I i Yankee Atomic Electric Company OISE(3) i ATTN: Ftr. G. Carl Andognini, Assistant

  • RAPurple ll to the Vice President ABurger #'

! 20 Turnpike Road S?1Sheppard i Westhoro, Massachusetts 01581 SVarga p

! i DEisenhut Gentlenen: TBAbernathy, TIC h ACRS(16) [

Your letter dated June 4,1975, furnished information in support of your L request for exemption from certain requirements in Appendix J to 10 CFR Part 50, "Prinary Containment Leakage Testing for Water-Cooled Power glj (

Reactors". We have reviewed this informatiott in connection with Sections 16.4.11 and 16.5.4, limiting conditions for operation "Contain- l?. 2 ment Integrity and Surveillance Requirements" and "Containnent Testing", N respectively, which are included in your proposed new format Technical Specifications for Yankee-Rowe. In our review, we are considering the Q[

g exist 1.vig Yankee-Rowe continuous containment Icakago monitoring system as a possible substitution for the frequency requirenents in Appendix J.

In order for us to continue our review of your proposed technten1 spect-- [ *l

! 6 5 fications and your request for exemption from requirements in Appendix J, !e

+c need the edditional information identified in the enclosure to this

Ictter. [;g j

Please r,dvise us within fourteen (14) days from receipt of this letter g when you will provide the needed additional information. @

}

Sincerely, qy m

O M nnldrnmlly

11. A. Puride j

(

?. f -

Robert A. Purple, Chief .f Operating Reactors Branch I'1 h 1

j Division of Reactor Licensing \( yp k,

L l>b (j f Fnclosure: f' N l

Request for Additional Infonnation THIS DOCllME,7 cc)mm POOR QU/.:ir/ p;ng kg cc: See next page y

7..-

fY t

{a RL :pmj#E'~~) ij c . .,u R!:0RB'1/% o. J<.f s

, ,, , , , , ABurger:d c RA urnic. _

n., e 9/10/75 9//(/75 }

  1. v. s. novranwant emmuao op p seu sev4.sae s ee 6

. MCt i Lev. M 3) AT O( (;4 ;

v. & ~ -~ ~-~~ w ~~ .w ~ ~.e.~~m e

- . ~ . .

I

~

h .

l t

5 1 l

5 I

i REQtlEST FOR ADDITIONAL INFORMATION [

5 YANKEE-R0h'E 1

'  ?

DOCKET NO. 50-29 =

2 Y3 1

L'

1. Specify the minimum containment leakage (lower limit) which can s be sensed and recorded by the monitoring system when the plant is 4 being operated at the lowest allowable containment pressure. -

Describe the method used to extrapolate leakage measured at the %j normal containment pressure to the peak calculated accident pres- i sure (Pa) normally used for local Icak rate tests. I 3

2. Propose limiting conditions for operation which require operability i of the continuous containment leakage monitoring system, including
  • the maximum time the plant may remain operational with the moni- m toring system inoperable before plant shutdown is required.
3. Propose a surveillance requirement for performing a containment integrated Icak rato test (Type A) subsequent to equipment hatch removal and replacement.

m w

c ara:s +

l e . u. . - <

  • O t's * ._

D - .* ! C.!!', (1~.e'. 9 5 3 ) AIC L 0:40 W u. s. novs PwMrst Paintino cretate ter4.sse ire

._ , . . i