ML20148F659

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept CP-87-26 Re Diesel Generator Fuel Oil Transfer Pump Suction Lift.Initially Reported on 871223. Low & High Fuel Oil Storages Will Be Implemented to Allow 7 Days of Fuel Oil at 100% Power Level
ML20148F659
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 01/20/1988
From: Counsil W, Woodlan D
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-26, TXX-88106, NUDOCS 8801260305
Download: ML20148F659 (2)


Text

,

i 1

=

M b

EE Log # TXX-88106

.=

File # 10110

=

=

909.5

  1. # '* " 0**

I'}

TilELECTRIC January 20, 1988 w mi.m c. coumii una,, va, r,num, U. 3. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION DOCKET NOS. 50-445 AND 50-446 DG FUEL OIL TRANSFER PUMP SUCTION LIFT SDAR: CP-87-26 (FINAL REPORT)

Gentlemen:

On December 23, 1987, we notified you by our letter logged TXX-7125 of a deficiency involving diesel generator fuel oil transfer pump suction lift which we deemed reportable under the provisions of 10CFR50.55(e).

Th'= is a final report submitted to provide the corrective actions for this issue.

The pump net positive suction head (NPSH) criteria and the seven day fuel oil storage criteria are established in Design Basis Document DBD-ME-215, "Emergency Diesel Generator Fuel Oil Transfer System." Low and high fuel oil storage tank. level alarm setpoints have been revised and associated field changes will be implemented consistent with calculation 16345-ME(B)-306 to allow for a full seven days of fuel oil while operating at 100!s power level.

Fuel oil reserved for diesel testing has also been reduced to a maximum of 3450 gallons. Appro)riate FSAR change requests will be made to reflect this reserve capacity ratler than the current FSAR values which indicate a 15's of tank capacity testing reserve, in addition, the specific gravity of the fuel oil will be inspected within strict tolerances specified by the plant Technical Specifications when received on-site for storage.

Technical Specification values for specific gravity and minimum allowable storage tank volume will be modified as necessary, 9

8801260305 880120 PDR ADOCK 05000445 p

s oco

\\

a n,,w.

s.,,,,

u n a u r,, a.m

~'

~

TXX-88106 January 20, 1988 Page 2 of 2 This is our final report on this issue.

Supporting documentation will be available for your inspectors to review at the CPSES Project Site after April 20, 1988.

Very truly yours, (2). Co. Q W. G. Counsil By:

D. R. Woodlan Supervisor, Docket Licensing MCP/grr c-Mr. R. D. Martin, Region IV Resident Inspectors, CPSES (3)

.