Informs That Util 760127 Proposal to Replace Automatic Transfer Switches W/Manually Operated,Double Throw Switches, & to Install Interlocks Between Breakers Acceptable.Schedule for Switch Replacement Also Acceptable
ML20148F548
Person / Time
Site: Yankee Rowe
Issue date: 03/08/1976
From: Goller K
Office of Nuclear Reactor Regulation
To: Groce R
YANKEE ATOMIC ELECTRIC CO.
References
NUDOCS 8011050695
Download: ML20148F548 (3)


Text

.

i

~

C Ma'rch 8, 1976 Docket fjo. 50-29 Yankee Atomic Electric Company A*ITN : Mr. Robert M. Groce Licensing Engineer 20 Turnpike Road '

Westboro, Massachusetts 015S1  ;

t=

Gentlemen: y As a result of our review of your Core XII refueling submittal and W your related Emergency Core Cooling System (ECCS) performance evalua-tion, we concluded that Yankee-Rowe can be operated safely with Core

(

XII and in conpliance with 10 CFR Part 50, 550.46. This conclusion r was based in part on our finding (described in our Safety Evaluation k dated December 4,1975) that with the disabling of the automatic f bus transfers by racking out and locking of the alternate supply F?

breakers to the two automatic transfer switches, the onsite emergency I power system meets the single failure criterion. We required as a -

pemanent fix the eventual removal of the autonatic bus transfer feature in the 480 V clectrical power distribution systen and we requested in our letter dated Decenber 4, 1975, your proposal for accomplishing this.

Responding to our December 4, 1975 request, you nroposed in your

.Tanuary 27, 1976 submittal to replace the autonatic transfer switches with nanually operated, double throw safety suitches. You also proposed to install Kirk Key interlocks between n e nornal and alternate sup;,1y circuit breakers for each nanual suitch. From our revicu cf the infor ation and drawing which you provided in your .icnuary 27.

1976 subnittal, we conclude that since your proposed nethod of renoval of the automatic bus transfer feature will not affect the Yankee-nowe onsite ener'ency power syster 's confornance . tith Regulatory Guide 1.6, " Independence Betiecen Redundant Standby (Onsite) Power Sources and Detween their Distribution Systens", it is acceptabic.

.Y

/

l W-THIS DOCUMENT CONTAINS POOR QUAUTY PAGES l _

o i:

l l

13 O&O Qg .

~

Yankee Atomic Electric Company Fiarch 8, 1976 As a result of discussions between our staffs on March 1, 1976, wo understand that based on the anticipated delivery of the Kirk Key interlochs during April 1976, you plan to complete the removal of the automatic bus transfer feature by mid-May 1976. We find your schedule tb he acceptabic. We request that you advise us of any changes in this schedule.

Sincerely,

/s/  :.

I' Karl R. Coller, Assistant Director T' for Operating Reactors  ;

Division of Operating Reactors  !:

F.

DISTRIBUTICN --'

p- '[:[

Docket c:

NRC PDR {9 Local PDR r:

OKB-1 Reading KRGoller TJCarter RAPurple ABurger S?heppard Attorney, OELD OI6E (3)

JRBuchanan TBAbernathy DEisenhut ACRS (16)

- .? --l.c.

p, t_!

orric

  • DOR:0RB-1/rj .D0$0Rir:) DOR:AD/ ors

. df.k.

  • ABurger: p .. Rt ke. . . KRGt;11 er.
o. n
  • 3/ 5 /76 .3/[/76. ._3/I/7b ..

]<.e-e' .18 (i .er. P 3 3 ) A' Lf 02 4'>

" D U, s. out r e a v rm? re innin o op rice s t o74.sae t es

, g .

Yenkes, Atomic ElectriE' Company.- -

. - March ' 8,- 1976 - - "

11

~ ~

~

cc: Hr. Donald G. Allen, President -

' Yankee. Atomic Electric l Company

-20 Turnpike Road W Westboro, Massachusetts' 01581

.Greenfield.Public Library-402 Main'St'rcet .

Greenfield, Massachusetts 01581 p ,

y t::

5

  • 9

- n.

bhhb

,:-=

e s r. ..'+l

=.

-F eme e i.:

- [

  • - i-l"

., y:3 6

9 a

, . 'f -

e ,

e 9

4 6

e

- *  ?: "!

4 .['. -

.{..

4 e

4 e. m. . - - , . < ma,, - ,, -

---,a, -- v-y-s ..e w . , . , , , , y , , ,.