. _.

. - ~.. -

k84FOq\\

UNITED STATES g:

j NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 3066t@001

    • e...../

DMQ.VESNE LIGHT COMPANY l

l OHIO EDIS0N COMPANY PENNSYLVANIA POWER COMPANY DOCKET N0. 50-334 BEAVER VALLEY POWER STATION. UNIT N0. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 204 License No. DPR-66 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Duquesne Light Company, et al. (the licensee) dated February 27, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act),

and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health l

and safety 'of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; l

D.

The issuance of this amendment will not be inimical to the commen defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

l l

l 9706020275 970528 PDR ADOCK 05000334 I

p PDR

i f '

i 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-66 is hereby i

amended to read as follows:

(2) Technical Soecifications The Technical Specifications contained in Appendix A, as revised i

through Amendment No. 204, are hereby incorporated in the license.

l The licensee shall operate the facility in accordance with the l

Technical Specifications.

3.

This license amendment is effective as of its date of issuance, to be i

implemented within 60 days, l

FOR THE NUCLEAR REGULATORY COMMISSION 3

Joh F. Stolz, Director l

Pr e Directorate 1-2 1

Div' ion of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical l

Specifications Date of Issuance: May 28, 1997 i

t l

ATTACHMENT TO LICENSE AMENDMENT NO. 9n4 l

FACILITY OPERATING LICENSE NO. DPR-66 DOCKET NO. 50-334 5

Replace the following page of the Appendix A, Technical Specifications, with the attached page. The revised page is identified by amendment number and contains a vertical line indicating the area of change.

Remove Insert 5-2 5-2 l

i i

DPR-66 DESIGN FEATURES l

c.

A nominal center to center distance between fuel assemblies l

placed in the fuel storage racks of 10.82 inch for Region 1, with 9.02 inch for Regions 2 and 3; i

l d.

Fuel assembly storage shall comply with the requirements of l

Specification 3.9.14.

j l

5.3.1.2 The new fuel storage racks are designed and shall be i

maintained with:

a.

Fuel assemblies having a maximum U-235 enrichment of 5.00 l

weight percent with a tolerance of + 0.05 weight percent; l

b.

K gf 5 0.95 if fully flooded with unborated water, which l

includes an allowance for uncertainties as described in UFSAR Section 9.12; c.

Keff $ 0.98 if moderated by aqueous foam, which includes an l

allowance for uncertainties as described in UFSAR Section 1

9.12; d.

A nominal 21 inch center to center distance between fuel assemblies placed in the storage racks.

j 5.3.2 DRAINAGE l

The spent fuel storage pool is designed and shall be maintained to prevent inadvertent draining of the pool below elevation 750' - 10".

5.3.3 CAPACITY The fuel storage pool is designed and shall be maintained.with a storage capacity limited to no more than 1627 fuel assemblies.

l I

BEAVER VALLEY - UNIT 1 5-2 Amendment No. 204 l

1 I