Summary of 970502 Meeting W/Util to Discuss Status of Implementation Schedule for Completion of Installation of Thermo-lag at Plants.List of Attendees Encl
ML20148D853
Person / Time
Site: Oyster Creek, Crane
Issue date: 05/28/1997
From: Eaton R
NRC (Affiliation Not Assigned)
To:
NRC (Affiliation Not Assigned)
References
NUDOCS 9706020134
Download: ML20148D853 (26)


Text

.-

,f,6 May 28, 1997 l

l LICENSEE:

GPU Nuclear Corporation FACILITIES: Three Mile Island, Unit I and Oyster Creek t

SUBJECT:

SUMMARY

OF MAY 2, 1997, MEETING REGARDING COMPLETION OF INSTALLATION OF THERMAL LAG FIRE BARRIERS On May 2, 1997, representatives of GPU Nuclear Corporation met with the NRC staff to discuss the status of the implementation schedule for completion of installation of Thermo-lag at both the Three Mile Island, Unit 1 (TMI-1) and Oyster Creek Nuclear Facilities. is a list of attendees.

In summary, GPU representatives stated that the current schedule for completing the installation of all required Thermo-lag fire barriers at Oyster Creek and TMI-l is December 1998 and December 1999, respectively.

The licensee indicated that the completion sciiedule for TMI-l could occur earlier pending approval of two exemption requests from 10 CFR 50, Appendix R currently under review by the NRC staff, in the next three or four months.

The staff indicated that approval of the two exemptions would be based on their merits. provides more detailed information on the issues discussed.

In view of the possibility of selling or retiring the Oyster Creek Facility by the year 2000, the licensee indicated that they are currently reviewing all regulatory commitments with respect to the Oyster Creek facility and will have further communications with the NRC on the results of this review in the next three or four months.

Original signed by Bart Buckley, Senior Project Manager Ronald B. Eaton, *,enior Project Manager Project Directorate I-3 Project Directorate I-3 Division of Reactor Projects -'I/II Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation Office of Nuclear Reactor Regulation Docket Nos. 50-289/50-219 Distribution

Enclosure:

As stated HARD COPl E-MAIL Docket File SCollins/FMiraglia cc w/ encl: See next page PUBLIC RZimmerman MSalley PDI-3 RF SVarga SWest OGC PMilano LTran ACRS BBuckley LMarsh REaton EDunnington mig flif CBM COPY g;rson gpt ji l

WDean V~

PEselgroth, RI DOCUMENT NAME:

G:\\BUCKLEY\\MAY2. SUM To,eceive a copy of this docurnent,indicete in the boa: "g A Ce'py without attachment / enclosure "E" = Copy with attachment / enclosure "N" = No copy 0FFICE PM:PDI-3 lE PM:lPDl43/

l LA:PDII-l l6 (A)D: WI-3 l SPL4 NAME BBuckley REalon EDunnington 87n PMila r "

M est & J DATE 05/u/97 05/4/97 05/10/97 05/2$/97 os/tm 0FFICIAL RECORD COPY 9706020134 970528 PDR ADOCK 05000219 P

pop x

Three Mile Island Nuclear Station, Unit No. I cc:

Michael Ross Robert B. Borsum Director, O&M, TMI B&W Nuclear Technologies GPU Nuclear Corporation Suite 525 P.O. Box 480 1700 Rockville Pike Middletown, PA 17057 Rockville, MD 20852 l

John C. Fornicola William Dornsife, Acting Director l

Director, Planning and Bureau of Radiation Protection Regulatory Affairs Pennsylvania Department of GPU Nuclear Corporation Environmental Resources 100 Interpace Parkway P.O. Box 2063 Parsippany, NJ 07054 Harrisburg, PA 17120 Jack S. Wetmore Dr. Judith Johnsrud Manager, TMI Regulatory Affairs National Energy Committee GPU Nuclear Corporation Sierra Club P.O. Box 480 433 Orlando Avenue Middletown, PA 17057 State College, PA 16803 Ernest L. Blake, Jr., Esquire Mr. James W. Langenbach Shaw, Pittman, Potts & Trowbridge Vice President and Director, TMI-l 2300 N Street, NW.

GPU Nuclear Corporation Washington, DC 20037 P.O. Box 480 Middletown, PA 17057 Chairman Board of County Commissioners of Dauphin County Dauphin County Courthouse Harrisburg, PA 17120 Chairman Board of Supervisors of Londonderry Township R.D. #1, Geyers Church Road Middletown, PA 17057 Michele G. Evans Senior Resident Inspector (TMI-1)

U.S. Nuclear Regulatory Commission l

P.O. Box 311 1

Middletown, PA 17057 Regional Administrator, Region I l

U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406

/

I l

GPU Nuclear Corporation Oyster Creek Nuclear Generating Station l

CC:

Ernest L. Blake, Jr., Esquire Shaw, Pittman, Potts & Trowbridge 2300 N Street, NW Washington, DC 20037 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406-1415

{

BWR Licensing Manager GPU Nuclear Corporation 1 Upper Pond Road Parsippany, NJ 07054 Mayor Lacey Township 818 West Lacey Road Forked River, NJ 08731 Licensing Manager Oyster Creek Nuclear Generating Station Mail Stop: Site Emergency Bldg.

P.O. Box 388 Forked River, NJ 08731 Resident Inspector c/o U.S. Nuclear Regulatory Comission P.O. Box 445 Forked River, NJ 08731 Kent Tosch, Chief New Jersey Department of Enviror. mental Protection Bureau of Nuclear Engineering CN 415 Trenton, NJ 08625 Mr. Michael B. Roche Vice President and Director GPU Nuclear Corporation Oyster Creek Nuclear Generating Station P. O. Box 388 l

Forked River, NJ 08731 i

I l

GPU MEETING ON THERMO LAG MAY 2,1997 LIST OF ATTENDEES HAmt Office Bart Buckley NRC/NRR/PDI-3 Fred Barbieri GPUN Tom O'Connor (TMI)

GPUN David Distel GPUN Howard Crawford (TMI)

GPUN j

Tim Trettel (OC)

GPUN i

R.W. Keaten GPUN R.J. McGoey GPUN John Fornicola GPUN i

L.B. Marsh NRC/NRR/SPLB L. Tran NRC/NRP./DRPW a

Ed Wenzinger NUS 4

i Steven West NRC/NRR/SPLB Ron Eaton NRC/NRR/PDI-3 Mark Salley NRC/NRR/SPLB Fred Emerson NEI 3

1 l

i i

i 4EERWJigt&Jssts:1 -':. :m...

    • Tsiir E 332 m m m 4
.... -, ~....
mummw,

- xm m.wmmuma. ~...,.

I 4

l THERMO-LAG OPERABILITYRESOLUTION i

SCHEDLILE REVIEW 1

NRC/GPUN MANAGEMENT MEETING MA Y 2,1997 OYSTER CREEK NUCLEAR GENERATING STATION

~

THREE MILE ISLAND NUCLEAR GENERATING STATION-UNIT 1 GPU Nuclear Corp.

1

..w,,,e-..-.

+ - -,

, - +.,,,,..,,.

..-+-,--er-.,.-...

-,,...--,,,,..-,.1,,-,w,,,,,,,,--,e-,.4.,..-,.

_,w

..~.w

~~

..+*v=

- - = -,.,

-,v.-.my w---,

i 1iji1

, i i ii!

l

! j I;

,l

,i;1ii G

P U

N u

e e

e c

le a

PSRRR r

Co r

ce ee r

p o

hv sv v

ieioi e

e dd l

2_

e uwtuw Mh E

l i

?

BeToG

{h a

h nP ff.

s e

u.

i r

SU

_JQ

, P s

mtr f

aN

_. u o

o t

u r

r l

e c p

ag l

S g

ye o

c a

s h

R r

?

e e

e T

i, d

s h

u o

e

((

l l

l{

e u

r m

.?

t

?

i o

o

~

n

~

l a

^

g

^"""

2 i

k i

BACKGROUND

- mmmmm=s=mggg 73gymage-Thermo-lag Fire Barrier Ratings Less than Required; Compensatory e

Measures Are in Place e

Extent ofInstalled Raceway Barriers n

Oyster Creek TMI-1

- 1055 ft. (Approx.)

2600 ft. (Approx.)

- 1 & 3 Hr. Barriers 1 & 3 Hr. Barriers

- 7 Areas 19 Areas

- Conduit & Boxes Conduit, Cable Tray and Boxes e

Radiant Energy Heat Shields Oyster Creek TMI-1

- None 40 ft. (Approx.), Conduit, Boxes GPU Nuclear Corp.

3 w

r-

RESOLUTION STRATEGY RESTORE OPERABILITY OF BARRIERS l

COMMON APPROACH FOR OYSTER CREEK AND TMI-1

_.m_,mmy -

__g;y___

4 1

4 e Fire Barrier Assembly Configuration Evaluations 1

e Review Safe Shutdown Logic forPossible Elimination of Thermo-lag Protected Barriers e Review Impact of Higher Derating Factors on Existing l

Assembly Configurations e Participation In Industry Programs e Prepare Exemptions Where Technically Supportable i

L i

l GPU Nuclear Corp.

4

\\

1

RESOLLITION STRATEGY RESTORE OPERABILITY OF BARRIERS l

COMMON APPROACH FOR OYSTER CREEK AND TMI

_--__,,g,_.

__;,nngg. _

j e Estimate Cost of Upgrades / Replacements e Modify Required Barriers to Restore Operability l

Oyster Creek-12/98 l

- Unit Outage for Some Modifications I

TMI-1-12/99

-Includes Augmenting Control Building Fire Detection System

- Radiant Energy Heat Shield Modifications Scheduled for 10/97-Outage Required GPU Nuclear Corp.

5 O

l RESOLUTION STRATEGY ACCOMPLISHMENTS nex=m v =.=--

_ _ ;_ ;;g sers = r -

t l

e Completed Fire Barrier Assembly Configuration Evaluations l

Walkdown and Photograph i

i Develop Electronic Data Base to Compare Walkdown Results to Accepted Testing i

i Verify Barrier Construction Compare Installed to Tested Configurations (NEl Application i

Guide). Oyster Creek > 400 Evaluations TMI-1 > 950 Evaluations Establish Fire Barner Ratings for Bounded Assemblies n

Establish Cable Qualification Ratings for 1-HourBarriers l

4 i

GPU Nuclear Corp.

6 i

i

RESOLUTION STRATEGY i

ACCOMPLISHMENTS spm m m,y, i

e Completed Review of Safe Shutdown Logic Cost of Detailed Evaluation Outweighs Reduction in Requimd l

Protection and Savings in Modifications. No Change in Existing Evaluation.

e Completed Derating Review

> Bound Existing Configurations Against Configurations with Accepted Testing Compare TVA and TUEC Derating Test Results with Available, Derating Margins. Results Acceptable I

i GPU Nuclear Corp.

7

- ------.2...

i RESOLLITION STRATEGY l

ACCOMPLISHMENTS ihNNXhfvb+NUZhN -5b hk >N)N!! b-[ - '

5-[

'. j' '.'

,'.5 3

i j

e Participation In Industry Programs l

Provided Input for Configurations in NEI Test Program Tested Material Samples forInput to NEI Thenno-lag Chemical Composition Program n Active Member of NEI Fire Protection Working Group Shared Mecatiss Testing with Florida Power Corp.

)

Member of EPRI Tailored Collaboration Group to Establish Methods forEvaluating Fire Wrap-Effort Cancelled i

l GPU Nuclear Corp.

8

RESOLUTION STRATEGY

\\

ACCOMPLISHMENTS I

,- n - a n n a w y y

_ _ _ ; ; y 7,x, _ _

l l

e Completed Preparing Exemption Requests c

l Modify Fire Hazards Analysis to include Thermo-lag as a Combustible l

Perform Fim Hazards Analysis Using NRC Guidance Provided in n

i RAI's of September,1994 To Support Exemption Requests Oyster Creek Exemption Requests Submitted 12/95. Exemptions Withdrawn 10/96 After Examining Cost of 100% Upgrade.

l TMI-1 Exemption Requests Submitted 8/96 and 12/96 AfterExamining l

Cost of100 % Upgrade.

l

- 8/96 Exemption Request Downgrades 3 Hr. Barrisrs in 9 Fire l

Areas / Zones to at Least 1 Hr. and Commits to Augment Fire l

Detection in These Areas

- 12/96 Exemption Requests Acceptance of Barriers in 10 Fire Areas / Zones With Ability to Insure Cable Functionality forat Least i

- 57 Minutes.

l l

~

j GPU Nuclear Corp.

9 1

i

l RESOLUTION STRATEGY i

ACCOMPLISHMENTS M3MES3EEDTE "2

' 3357sMdMWWR p

e Completed Estimating Cost of Upgrades / Replacements l

Obtain Estimates for Cost to Upgrade / Replace Committed vs 100%

1 Estimates Obtained forDannatt, Versawrap and Mecatiss Oyster Creek Differential Cost Not Large Enough to Continue With Exemption Requests.

n At Oyster Creek, Commit to Upgrade (10/96) l l

- Approx.1055 LinearFt. of 1 Hr. Conduit,1 Hr. Boxes l-

- Approx. 20 LinearFt. of 3 Hr. Conduit i

i

~

l GPU Nuclear Corp.

10

- - - - =

vg

a l

RESOLUTION STRATEGY ACCOMPLISHMENTS <estimatcscont.>

um

=mwmaremmemw c===mam-I TMI-1 Differential Cost ($2M) Warranted Proceeding With Exemption Requests At TMI-1, Commit to Upgrade

- Approx.1000 LinearFt.1 Hr. Conduit and Cable Tray,1 Hr.

l Boxes l

- Upgrade Unbounded 3 Hr. Penetration Interfaces to 1 Hr

- Augment Control Building Fire Detection System.

- Note: Exemptions Support Using 1600 Ft. of Existing Thermo-lag i

Without Exemptions Must Upgrade l

- Approx.' 2000 LinearFt.1 Hr. Conduit, Cable Tray, Boxes

- Approx. 600 LinearFt. 3 Hr. Conduit, Cable Tray, Boxes Estimate Cost to Modify Radiant Energy Heat Shields in TMI-1 ReactorBuilding. Modification consists of Covering Existing Shields with Stainless Steel to Eliminate Thermo-lag as a combustible i

GPU Nuclear Corp.

11

,--,,,,,-,e

_-,,,,,.,__,.-,,____,,,,,_,,.._,,,_,___.v.,.-,,..

.,__m___r

.,y., _,..,., _,

,-,,,,_.,,_.,.,y,,

RESOLLITION STRATEGY

~

PLANS s,.lygg,hgyh;.ygy;g.y

.;ggggg, x

.v.v s:,

e Modify Required Barriers to Restore Operability Basis for Committec' Schedules

- Completion of Fire Barrier Assembly Configuration Evaluations and Submittal of Exemption Requests 12/95 (Oyster Creek),

12/96 (TMI-1)

- One Year for Exemption Review Process; 12/96 (Oyster Creek),

12/97 (TMI-1)

- Two Years forModifications Assuming Completion Requires Unit Outage. Both Oyster Creek (12/98) and TMI-1 (12/99),

Completion Schedules Coincide with Outage Years.

1 l

n Bids Released for Proposals 3/97. Bid Proposals Due 5/97.

Contract Awarri Scheduled 7/97.

TMI-1 Radiant Energy Heat Shields to be Modified by 10/97 (Unit n

Outage Required). Engineering Complete. Materials on Order.

GPU Nuclear Corp.

12

i RESOLUTION STRATEGY i

KEYISSUES mEmana w N m

  • ^*:an e r m m m m=w =r -

k

\\

e Additional Weight and Derating of Upgraded / Replaced Barriers -

1 Potential forincrease in Work Scope ie. Modify Raceway Supports.

e Additional Testing for Unique Configurations May be Required Unit Outage Required at Oyster Creek forApproximately 10% of e

Upgrade Effort.

l e

Exemption Request Status at TMI-1 Requires Resolution in Order to l

Finalize Work Scope.

i 1

i GPU Nuclear Corp.

13 c_

-,y

_,.,,_..,.,_._..y

_ _,.,,,-,,,,,,,,,,. -y

,,y..,,,

wy.__,..,

F 1

i I

l THERMO-LAG COMPLETION i

OYSTER CREEK /TMI-1 mmrances">'"

, _...;rpag"q:"irrm m -

J l

l 1

{

BARRIER EVALJEXEMPTION E OYSTER CREEK O TMI-1 REHS(TMIONLY) I I

\\

i 1

i BARRIER UPGRADES i

i i

)

DETECTION (TMI ONLY) -j i

,t

% COMPLETE O

20 40 60 80 100 l

GPU Nuclear Corp.

14 j

~

l 1

l THERMO-LAG RESOLUTION i

OYSTER CREEK ama_ - -womm== % _ _ _,

__ja m===wmmm

.~=

I i

Dollars Expended / Projected i

e Oyster Creek Expenditures 72g

\\

to date are appmx. $30GK 4

l e

Based Upon Current 1

Committments, a totalof D COMPLETE l

$1.2 Mis projected i

i i

E TO-BE i

COMPLETED 28%

a

)

I

~

i GPU Nuclear Corp.

15 i

i-...-..

\\

i l

i l

THERMO-LAG RESOLUTION OYSTER CREEK

- -ummm wmmesmmpm.77, g3 p m m m p m - m e n smemusumummusums l

e OYSTER CREEK THERMO-LAG MODIFICATION SCHEDULE l

ACTIVITY SCHEDULED DATE l

- Award Contract 7/1W97

'l l

- Release Engineering Package 12/31/97 l

- AllMaterials on Site 1/31/98 i

- Complete Planning / Issue Job Packages 1/31/98

)

- Complete Installer Training 3/1W98

- Mobilize and Construct Scaffolding 6/1/98.

1

- Cominence w/Non-Outage Work Areas 7/1/98 l

- Start of Unit Refueling Outage 9/12/98-l

- Target Completion Date (End of Outage) 10/30/98 l

- Project Completion 12/31/98 1

GPU Nuclear Corp.

16

-1 v--m,8~~w,,

i THERMO-LAG RESOLLITION l

OYSTER CREEK

~

e Areas Requiring a,; Outage for Access l

n Fire Area Location Reason

\\

RB-FZ-1E Rx Bldg 23' Elev.

Sensitive Components i

RB-FZ-1E Rx Bldg 38' Elev.

ALARA RB-FZ-1F2 Rx Bldg -19' Elev.

ALARA I

4 i

l i

GPU Nuclear Corp.

17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - - - _ _ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ' ^ - - - - - - - - - - - - - - - - - - - - " ~ ~ - - ' - ' - - - ~ ' ' ' - - - - ' - - ' - ' '

I i

I, l

THERMO-LAG RESOLUTION TMI-1 i

)

-xim v...*.:w.';..ev' :w:r:ere:.::: xpWI::MW.y v..:::-

'"'"!:QiQyyyjy[pfggg t

I e

TMI-1 Expenditures to date are i

approx. $500K Dollars Expended /Proj.ected t

l e

Based Upon Current l

Committments, a total of $1.7 M 65 %

l is projected (Exemption acourteTe l

RequestsApproved) i i

1 1

l E TO BE i'

COMPLETED 35%

i i

l i

l j

GPU Nuclear Corp.

18 4

i.

._-_._,..-_.-_.,_..-_,,_,,_-.._2_,,.,__...._..-,......_.,_..

i THERMO-LAG RESOLUTION TMI-1 4

-m A4.s*.i-:.s,w:23a.J:e:3::.wp v+:nw Ni:--EJ n::k;

-'+mpgp Myg g 1

4 e

TMI-1 THERMO-LAG MODIFICATION SCHEDULE ACTIVITY SCHEDULED DATE Reactor Building Radiant Energy Heat Shields n

- Release Engineedng Package Complete Complete Planning / Issue Job Package Complete Complete Installation in 12R Outage 10/10/97 4

1 GPU Nuclear Corp.

19 e

y

,3-

.-.y,

, i -,,

-, -i,,,..,...-.,-<

w v

l i

THERMO-LAG RESOLUTION 4

TMI-1 i

nnxew,.: w ARwgyg

7
2.. _ g.

g g.:w:me92p m l

e TMI-1 THERMO-LAG MODIFICATION SCHEDULE (Cont.)

i CURRENT COMMITTMENT PENDING EXEMPTION REQUESTS ACTIVITY WORK DURATION *

- Control Building Incipient Fire Detection

)

e Receive Exemption Approval.

TBD e Release Engineering Package 2 Months i

j e Complete Planning / Issue Job Package 1 Month l

e Complete Installation 1 Month

  • Durations Gould Lengthen Due to Conflict with 12R Outage i

i GPU Nuclear Corp.

20 i

--w-m vg---

--e-2 y,

y p

pp a

+-- -

q 3-3 m

q

,--+yn,-

l l

THERMO-LAG RESOLlD10N i

TMI-1 1

mm+ampamengwr. _..

.;;-~y--~~~~~~-----

.,.,,.,,,,... - maag:;,:. gan

. s,,mnammmm. ;.

i i

l e

TMI-1 THERMO-LAG MODIFICATION SCHEDULE (Cont.)

l CURRENT COMMITTMENT PENDING EXEMPTION REQUESTS ACTIVITY WORK DURATION *

- Thermo-lag Upgrades / Modifications e Award Contract 7/15/97 e Release Engineering Package **

2 Months e Complete Planning / Issue Job Package 1 Month e Complete Installation ***

6 Months l

  • Durations Could Lengthen Due to Conflict with 12R Outage

)

    • Additional Qualification Testing for Unique Configurations

)

Could Delay Engineedng Release l

Resolved 1

1 l

GPU Nuclear Corp.

21 1

i

..-,.-----~~i---

i

}

l THERMO-LAG RESOLLITION l

TMI-1 l

. o e,mwam;rmfagg7.

gyyx7 --

i j

e TMI-1 THERMO-LAG MODIFICATION SCHEDULE (Cont.)

l WITHOUTEXEMPTION REQUESTS l

ACTIVITY WORK DURATION Thermo-lag Upgrades / Modifications e Award Contract 7/15/97 l

l e Release Engineenng Package

  • 12 Months i

e Complete Planning / Issue Job Package 6 Months t

i e Portions Require Outage forInstallation (13R) 9/99

~12/31/99' e Project Completion l

1

  • May Include Qualification Testing for Unique Configurations i

l i

t i

j GPU Nuclear Corp.