__

March 14, 1988 Docket No. 50-277/278 Mr. Edward G. Bauer, Jr.

Vice President and General Counsel Philadelphia Electric Company 2301 Market Street Philadelphia, Pennsylvania 19101

Dear Mr. Bauer:

SUBJECT:

GENERIC LETTER 83-28, ITEM 2.1.1.

RE:

Peach Bottom Atomic Power Station, Units 2 and 3 You have responded to the staff position of Generic Letter 83-28 Item 2.1.1.,

"Equipr'ent Classification Program" by letters dated November 4,1983, April 23, 1984 and May 29, 1985. The staff's review of these submittals discloses the need for additional information as described in the Enclosure.

/S/

Robert E. Martin, Project Manager Project Directorate I-2 Division of Reactor Projects I/II

Enclosure:

As stated cc: See Next Page DIST2IBUTION Doctet File 3 PDI-2 Readinc[

NRC PDR/LPDR SVarga/BBoger M0'Brien MThadani/DFischer 0GC-WF E. Jordan J. Partlow D. Lasher ACRS(10)

Previously Concurred

  • PD})-2/Py*

PDI-2/D*

R)Mr't'in:tr WButler 03/14/88 03/14/88 8803210348 880314 PDR ADOCK 05000277 P

PDR i

  1. pa atooq'o UNITED STATES 8

k NUCLEAR REGULATORY COMMISSION 3

E WASHINGTON, D. C. 20555

,o Docket No. 50-277/278 Mr. Edward G. Bauer, Jr.

Vice President and General Counsel Philadelphia Electric Company 2301 Market Street Philadelphia, Pennsylvania 19101

Dear Mr. Bauer:

SU8d:T:

GENERIC LETTER 83-28, ITEM 2.1.1.

Re:

Peach Bottom Atomic Power Station, Units 2 and 3 You have responded to the staff position of Generic Letter 83-28. Item 2.1.1.,

"Equipment Clasrification Program" by letters dated November 4,1983, April 23, 1984 and May 29, 1985. The staff's review of these submittals discloses the need for additional information as described in the Enclosure.

hf0/a w

// Robert E. Martin, Project Manager Project Directorate I-2 Division of Reactor Projects I/II Enciosure:

As stated cc: See Next Page

Mr. E. G. Bauer, Jr.

Peach Bottom Atomic Power Station.

Philadelphia Electric Company Units 2 and 3 cc:

Mr. J. S. Kemper, Senior Vice President Mr. R. A. Heiss, Coordinator Philadelphia Electric Company Pennsylvania State Clearinghouse 2301 Market Street Governor's Office of State Planning Philadelphia, Pennsylvania 19101 and Development P. O. Box 1323 froy B. Conner, Jr., Esq.

Harrisburg, Pennsylvania 17120 1747 Pennsylvania Avenue, N.W.

Washington, D.C. 20006 Mr. Thomas M. Gerusky, Director Bureau of Radiation Protection Philadelphia Electric Company Pennsylvania Department of ATTN: Mr. D. M. Smith, Vice President Environmental Resources Peach Botton Atomic Power Station P. O. Box 2063 Route 1, Box 208 Harrisburg, Pennsylvania 17120 Delta, Pennsylvania 17314 Mr. Albert R. Steel, Chairman Mr. W. M. Alden Board of Supervisors Engineer-in-Charge-Licensing Peach Bottom Township Philadelphia Electric Company R. D. #1 2301 Market Street Delta, Pennsylvania 17314 Philadelphia, Pennsylvania 19101 Mr. Gary Mock Morgan J. Morris, III P. O. Box 09181 General Manager - Operating Services Columbus, Ohio 43209 Atlantic Electric P. O. Box 1500 Mr. Jack Urban 1199 Black Horse Pike General Manager, Production Pleasantville, New Jersey 08232 Delmarva Power and Light Company 800 King Street Resident Inspector Wilmington, Delaware 13899 U. S. Nuclear Regulatory Commission Peach Bottom Atomic Power Station Mr. Tom Magette P. O. Box 399 Power Plant Research Program Delta Pennsylvania 17314 Department of Natural Resources B-3 Regional Administrator, Region I Tawes State Office Building U. S. Nuclear Regulatory Commission Annapolis, Maryland 21401 475 Allendale Poad King of Prussia, Pennsylvania 19406 Mr. Roland Fletcher Department of Environment 201 West Preston Street Baltimore, Maryland 21201 b

ENCLOSUQE Peach Bottm Atomic Power Statien l' nits 2, 3 Docket Nos. FO-277/278 Request for. additional Information For Generic letter 83-28 Item 2.1 (Part 1)

==

Introduction:==

We have reviewed the respanses to Generic letter 83-28 Item 2.1 (Part 1) dated November 4,1983, April 23,1984 and May 29, 1985 provided by Philadelphia Electric Company, the licensee for Peach Bottom Atomic Power Station, Units 2, 3, and find them unacceptable as indicated below.

The licensee is requested to provide additional infor. nation for these items as described below.

Evaluation and Specific information Request:

Evaluation:

The licensee's responses state that all systems that contribute to the reactor trip function have been identified as safety-related in the current "Q" list and that all components of safety-related systems are safety-related unless specifically excluded by safety evaluation.

The "0" list is used to identify the applicable codes, standards and procedures to be used for activities relating to the safety-related components.

Each item or service to be procured is reviewed to determine if it is safety-related. The review is performed by a cognizant member of the plant staff or the Engineering and Research Department.

==

Conclusion:==

Item 2.1 (Part 1) requires licensees to confirm that all components whose functioning is reouired to trip the reactor are identified as safety-related on documents, procedures, and information handling systems used in the plant to control safety-related activities. We find that the licensee's response confirms only that the systems which contribute to reactor trio are. identified as safety-related. Components are not confirmed to be so identified en the relevant plant documentation and in information handling systems as requested for this item.

The licensee should confirm that a program of equipment classification has been developed and implemented which does identify components whose functioning is required to trip the reactor as safety-related on documentation and in information handling systems that are used in the plant to control activities which may affect these ccmponents.

~