ML20148A586

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 880104-0213.Violation Noted:On 880112,areas W/Dose Rates of Up to 400 M/H,Which Constitute High Radiation Areas Not Posted as Required
ML20148A586
Person / Time
Site: Susquehanna  
Issue date: 03/14/1988
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML17156A440 List:
References
50-387-88-04, 50-387-88-4, 50-388-88-04, 50-388-88-4, NUDOCS 8803210023
Download: ML20148A586 (1)


Text

-_

APPENDIX A NOTICE OF VIOLATION Pennsylvania Power and Light Company Docket Nos. 387; 50-388 i

Susquehanna Units No. 1 and 2 License Nos. NPF-14; NPF-22 1

As a result of an inspection conducted on January-12,1988, and in accordance with the NRC Enforcement Policy (10 CFR 2, Appendix C), the following violation was identified:

Technical Specifications Section 6.12.1 states that "... each high radia-tion area -in which the intensity of-radiation is greater than 100 mrem /hr i

but less than 1000 mrem /hr shall be barricaded and conspicuously posted as a high radiatirn area...".

J Contrary to tb 2 above, on January 12,- areas with dose rates of up to 400 mr/hr, which ~.onstitute High Radiation Areas, were not postr.d as required.

Specifically, those areas immediately adjacent to the main turbine front standards for both Units 1 and 2 were not posted.

This is a Severity Level IV Violation (Supplement IV).

Pursuant to the provisions of 10 CFR 2.201, Pennsylvania Power and Light is hereby required to submit to this office within 30 days of the date of the letter transmitting this Notice, a written statement or explanation-in reply, i

including:

(1) the reason for the violation if admitted; (2) the corrective steps which have been taken and the results achieved; (3) the corrective steps which will be taken to avoid further violations; and (4) the date when full compliance will be achieved. Where good cause is shown, consideration will be I

give. to extend this response time.

l i

l I

i 0FFICIAL RECORD COPY CIR SUS 88-04/03 - 0003.0.0 03/14/88 8803210023 880314 PDR ADOCK 05000387 O

DCD

]