l AVERAGE DAILY UtllT POUER LEVEL DOCKET t3D. 050-010
. UtilT Dresden 1 DATE Oct . 4. 1978 COMPLETED BY J .F. Phelan TELEPHONE 815/942-2920 ext 263 MONTH September, 1978 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (rac-tie t ) (Mue-tie t) 121 116 1 17 2 117 18 115 3 121 '19 114 4 120 20 113 5 121 21 113 6 12D 22 112 7 116 23 106 8 117 24 116 9 116 25 116 10 106 26 115 ,
Ii 117 27 115 12 114 23 115 13 114 29 113 14 110 30 109 15 116 31 16 111 7P/o/ r e/ o y
=^ -- ::- : Tr---- --
== -
c AVERAGE DAILY UlllT POWER LEVEL DOCKET tio. 050-237 ,
. Ulll T nroncton TT DATE Oct 4, 1978 COMPLETED BY J.F. Phelan TELEPHONE 815/942-2920 ext 263 nouTH September, 1978 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (11Ue- Ne t ) (MUe-fle t) 1 747 17 607 2 709 18 665 3 682 19 700 4 733 20 724 5 L26 21 734 6 733 22 751 l 7 731 23 712 8 734 24 __
702 9 721 25 753 10 697 26 758 11 724 27 753
)
12 726 23 750 13 8 29 745 14 387 30 690 15 449 31 16 525 1
~
. . _ _ ______Z'" r21_ _ _ ____ ___Z_T_i_ __ _.. ______ _ __ . _ _
2"--
AVERAGE DAILY UtilT POWER LEVEL DOCKET NO. 050-249 UlllT Dresden III DATE Oct 4 1978 COMPLETED BY J.F. Phelan TEL EPHON E815 / 942-2920 ext. 263 MONTH September, 1978 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (ItWe-fle t ) (MUc-Net) 1 748 17 0 2 376 18 0 3 442 19 0 4 538 20 0 5 626 21 0 6 691 22 0 7 753 23 54 8 759 24 388 9 718 25 534 to 731 26 651 ,
i1 736 27 732 l 12 747 28 751 13 749 29 772 14 733 30 769 15 597 31 16 0
~
_" T_[_i~l~i__________rr- : _r z___- _r_ _r ______ _______ __ __ ___________
__________ ___ _ ____________l - - __._7:=d::_r:--- )
OPERATING DATA REPORT DOCKET NO. 050-010 DATE 0ct 10, 1978 COMPLETED BY J.F. Phelan TELEPHONE 815/942-2920 x 263 OPERATING STATUS NOTES
- 1. Unit Name: Dresden I
- 2. Reporting Period: deptember, iv/c 3 Licensed Thermal Power (MWt): 700
- 4. Nameplate Rating (Gross MWe): 209 5 Design Electrical Rating (Net MWe): 200
- 6. Maximum Dependable Capacity (Gross MWe): 205 7 Maximura Dependable Capacity (Net MWe): 197 l 8. If Changes Occur in Capacity Ratings (ltems 3 Through 7) Since Last Report, Give l Reasons:
i NA 9 Power Level to Which Restricted, if Any (Net MWe): 495 MWT
- 10. Reasons For Restrictions, if Any: cnre soray/LOCA Deratine This Month Yr-to-Date Cumulative
- 11. Hours in Reporting Period 720 6551 161831
- 12. Number of Hours Reactor Was Critical 720 5733.78 112442.97 13 Reactor Reserve Shutdown Hours 0 0 0
- 14. Hours Generator On-Line 720 5668.32 110503.72 15 Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 327565.2 2452772.152 55711073.55
- 17. Gross Electrical Energy Generated (MWH) 88,404.42 734,820.98 16,720,598.94
- 18. Net Electrical Energy Generated (MWil) 82,655.9 688,821.4 15,753,389.82 19 Uni t Service Factor 100 86.5 68.3
- 20. Unit Availability Factor 100 86.5 68.3
- 21. Unit Capaci ty Factor (Using MDC Net) 58.3 53.4 49.4
- 22. Unit Capacity Factor (Using DER Net) '
57.4 52.6 48.7 23 Unit Forced Outage Rate O 13.5 11.2
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Decon Outage 781031 1.5 years
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup: NA
, ..=
. ~
m__.____ __.__.. _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ . _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ . -
OPERATING DATA REPORT DOCKET NO. 050-237 DATE Oct 10, 1978 COMPLETED BY J.F. Phelan TELEPHONE 815/942-2920 x263-OPERATING STATUS NOTES
- 1. Unit Name: Dresden II
- 2. Report ing Period: September, 1978 3 Licensed Thermal Power (MWt): 2527
- 4. Nameplate Rating (Gross Mbe): 828 5 Design Electrical Rating (Net MUe): 794
- 6. Maximum Dependable Capacity (Gross MWe): 812 7 Maximum Dependable Capacity (Net MWe): 772
- 8. If Changes Occur in Capacity Ratirgs (items 3 Through 7) Since Last Report, Give Reasons:
NA 9 Power Level to Uhich Restricted, if Any (Net MWe): NONE
- 10. Reasons For Restrictions, if Any: NA This Month Yr-to-Date Cumulativo
, 11. Hoars in Reporting Period 720 6551 73487 l 12. Number of Hours Reactor Was Critical 7na 7 A9?s 17 55236.17 13 Reactor Reserve Shutdown Hours 0 0 0
- 14. Hours Generator On-Linc 697.95 6059.4 51928.03 15 Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 1.584.131 13.703.046 100.512.248 17 Gross Electrical Energy Generated (MUH) 505.189 4.407.644 32.189.311
- 18. Net Electrical Energy Generated (MWil) 476,879 4,176,729.027 30,420.761.573 19 Unit Service Factor 96.9 92.5 70.7
- 20. Unit Availability Factor 96.9 92.5 70.7
- 21. Unit Capacity Factor (Using MDC Net) 85.8 82.6 53.6
- 22. Unit Capacity Factor (Using DER Net) '
83.4 80.3 52.1 23 Unit Forced Outage Rate ___. 1.0 7.s 1 s .1
- 24. Shutdowns Scheiuled Over Next 6 Months (Type, Date, and Duration of Each):
NONE 25 If Shut Down At End Of Report Period, Estimated Date of Startup:
- w &
. , . 1 OPERATING DATA REPORT DOCKET NO. 050-249 DATE Oct 10, 1978 COMPLETED BY J.F. Phelan TELEPHONE 815/942-2920 x 263; OPERATillG STATUS NOTES
- 1. Unit Name: Dresden III
- 2. Reporting Period: September, 1978 3 Licensed Thermal Power (MWt): 2527
- 4. Nameplate Rating (Gross MWe): ~ 828 5 Design Electrical Rating (Net tiWe): 794
- 6. Maximum Dependable Capacity (Gross MWe): 812 ,
- 7. Maximum De.pendable Capacity (flet t4We): 773
- 8. If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:
l 9 Power Level to Which Restricted, if Any (Net MWe): NONE
- 10. Reasons For Restrictions, i f Any: NA 9
This Month Yr-to-Date Cumulative l
- 11. Hours in Reporting Period 720 6551 63072
- j. 12. Number oi Hours Reactor Was Critical 615 4792.82 47985.28 13 Reactor Reserve Shutdown Hours 0 0 0 ~
- 14. Hours Generator On-Line 518.95 4564.98 'T5672.82 15 Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 1.094.457 8787633 85831418
- 17. Gross Electrical Energy Generated'(MWH) 353.486 2804120 28.500.578sli
- 18. Net Electrical Energy Generated (ftWil) 333.100 2639256.973 27,025,079.613 19 Unit Service Factor 72.1 69.7 72.4
- 20. Unit Availability Factor 72.1 69.7 72.4
- 21. Unit Capacity Factor (Using MDC Net) 59.8 52.1 55.4
- 22. Unit Capacity Factor (Using DER Net) ~
58.3 __
50.7 33.96 23 Unit Forced Outage Rate 27.9 10.6 13.9
- 24. ' Shutdowns Scheduled Over Next 6 Months (Type, Date, and Durat ion of Each):
Snubber Inspection 790122.23 4P de
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup: "A
DOCKET tio.050-010 Ut!IT t!AfiE Dresden I UtilT StiUTD0'.Jils Atl0 POWER REDUCT10fl5 DATE Oct 10, 1978 C0fiPLETED BY J .F. Phelan September , 1978 TE LEP110llE 815/942-2970 REPORT ft0!1TH
"_O t
M o -
87 "co
- t. =
EU
-c Licensee c.e o a En ce Cause & Correct.ive fio . Date S s
$5 u=
c 2US u a Event 73
>. u El eo Action to sv cc e _c c Report # w o Prevent Recurrence o rm3 u
?
l l
l 1
1 2 F: Forced Reason: G-Operational Error 4-other (Explain) 5: Scheduled A-Equipment Fa i l u re (Expla in ) H-Other (Explain)
B-Itaintenance of Test 4 Exhibit G-Instructions for C-Refuelin9 3 Method: Preparation of Data D-Regulatory Restriction 1 -itan ua l Entry Sheets for Licensee E-Operator Training & License Examination 2-tianual Scram Event Reoort (LER) F i l e (tJUREG F-Administrative 3-Automatic Scram 0161) 5 Exhibit 1 - Same Source
DOCKET NO. 050-237 Utili SiluTD0 TINS AND POWER REDUCTIOi!S UNIT fiAttE Dresden II DATE Oct 10, 1978 C0tiPLETED BY 3 p_ puntnn REPORT l-10NTil September, 1978 TELEPHONE 815/947-707n av* 263 1
C^ N oO
~
e . E E ,8' Licensee @c c"o Cause & Corrective No. Date S Eo $ SUS Event 53 S3 Action to 5 S U[g Report S N" j Prevent Recurrence e
11 780913 F 22.05 A 3 X-area Hi Temp - Coolers Tripped l
. t l
1 2 F: Fo rced Reason: G-Operational Error 4-other (Explain) 5: Scheduled A-Equipment Failure (Explain) H-Other (Explain)
B-11aintenance of Test 4 Exhibit G-Instructions for C-Refueling 3 Method: Preparation of Data D-Regulatory Restriction 1 -itan ua l Entry Sheets for Licensee E-Operator Training & License Examination 2-tian ua l Scram Event Report (LER) File (NURE' F-Administrative 3-Automatic Scram 0161) 5 Exhibit 1 - Same Source
DOCKET NO. 050-249 UtilT SHUTDOW!15 A?10 POWER REDUCT10l15 UNIT NAME Dresden III DATE Oct 10. 1978 COMPLETED BY J.F. Phelan REPORT M0tlTH September, 1978 "u s.J
%. Q e
E7
.- u "co c-0 EU L.icensee ca e e En ce Cause & Correct.ive No. Date S
%o E SUE Event %3 8.3 Action to o
55 E U5c rm a Report # N" u
$ Prevent Recurrence o
8 780915 F 201.05 A 1 "A" Recire Pump Seal Replacement
. l i
l 1 2 F: Forced Peason: G-Operational Error 1-other (Explain) 4
. 5: Scheduled A-Equipment Fa i lu re (Exp la i n ) H-Other (Explain)
B--Itai ntenance of Tes t li Exhibit G-Instructions for C- Refuel i ng 3 Method: Preparation of Data
! D-Regulatory Restriction 1 -t1a n ua l Entry Sheets for Licensee E-Operator Training & License Examination 2-f tanua l Scram Event Report (LER) File (NORE' F- Admi n i s t ra t i ve 3-Automatic Scram 0161)
I 5 Exhibit 1.- Same Source
DRESDEN UNIT 1 SAFETY RELATED MAINTENANCE September, 1978 a
NATURE OF LER OR OUTAGE MALFUNCTION-l ~ EQUIPMENT - MAINTENANCE NUMBER '
CAUSE RESULT CORRECT I VETACTI ON '
l
. Fuel Bldg. Preventive WR#5341 NA NA Replaced Grapple Latch-Grapple Switch
'Incore 110C Preventive WR#6881 NA NA Ran Plateau & Checked-Electronics Check OK-Incore 104B Preventive WR#6880 NA NA Ran Plateau & Checked
-1 Electronics Check OK' Channel 11 Preventive WR#7242 NA NA Replaced Electronic Period Meter Tube V23 "A" SSG Recirc. Corrective WR#4995 Bad Gasket & Studs Leakage ' Replaced Flange Gasket &
Pump Studs ,
Core Spray-In- Preventive WR#8699 NA NA Replaced & Connected Jection Header Unions Channel 7 Perio<1 Preventive WR#7475 NA NA Replaced with Spare Meter Chassis & Testad L
- 4
DRESDEN UN1T 2 SAFETY RELATED MAltlTENANCE September, 1978 MALFUNCT10tl NATURE OF LER OR OUTAGE CORRECTIVF-ACTION EQUIPMENT MAINTEriANCE liUMBER '
CAUSE RESULT Replaced Accumulator Preventive WR#6730 NA NA Accumulator 50-11 22B CCSW Pump Preventive WR#6808 NA NA Opened Both Valves.&
Removed Lime Deposists
-Room Cooler From Seats & Discs oCCSW Pump Corrective WR#5869 Damaged Coil Leakage Repared Leak & Tested Room Cooler 01601-21 Corrective WR#6282 Bad Solenoid Air Leakage Replaced Solenoid Valve Valve LPRM Input Preventive WR#3512 NA NA Replaced'23 Bad Relays Relays B Stack Gas Preventive WR#6900 NA NA Disassembled Valve Analyzer & Cleaned Diesel Genera- Preventive WR#6867 LER 78-50-OlL-0 NA NA Installed Air Start Motor tor Containment Preventive WR#6982 NA. NA Repacked Pump Cooling Serv.
Water Pump ,
2"B" 12CI Heat Preventive WR#6828 Outage 2-11 NA NA Replaced Strain Cauge Exchanger DP & Amp in Transmitter Controller O
DRESDEN UNIT 2 SAFETY RELATED MAltlTENANCE September, 1978 MALFutiCT10tl NATURE OF LER OR OUTAGE CORRECTIVF- ACTION EQUIPMENT HAINTENANCE IlUMBER '
CAUSE RESULT Vent to Reacto: Preventive WR#7178 LER-78-51-03L-0 NA NA Tightened Fittings on .
. Exchanger Valve Valve Operator 1601-24 LPRM 16-330 Preventive WR#6437 NA NA Checked LPRM Calibration
& Ran Plateau. Check-Indicated Normal Operatiot LPRM A4-40-33 Preventive WR# 6412 NA NA Replaced Fuse & Ad-justed Power Supply 250V Battery Preventive WR#1681 NA NA Installed New Breaker Charger LPCI Heat Preventive WR#7243 NA NA Cleaned & Checked Torque Exchanger Cool- Switch ing Water Dis-charge Valve RPS Relays Preventive WR#7376 NA NA Installed & Removed 590-ll2A,B,C, Jumpers Per Test
&D
- O
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _______..m__ _ - _ ___________m____ -.
' " ' ' - ' - ' ~ - - ' - " '
DRESDEN UNIT 3 SAFETY RELATED MANTENANCE September, 1978 LER OR OUTAGE MALFUNCTION NATURE OF EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION NA NA Adjusted Switch in O "B" CCSW Pump Preventive WR#6866
' Gear Hnit C/S-' Momentary Contact Transfen GrounEl '
Delay Bad Union Leakage Repaired Union
- "A" Recire. Corrective WR#6856 Pump #1 Seal.
Cavity In- 1 .
strument Line , /
Bad Union Leakage Welded Union
- HPC1 Drain Pot Corrective WR#6759 (2301-3)
NA NA Cleaned & Lubricated
- CCSW Pump Room Preventive WR#6615 . LER-78-32-03L-0 Contacts .
Coolers NA NA Replaced Asco Valve
- Diesel Preventive WR#6499 Generator. Fuel ,
Oil Transfer Pump NA NA Replaced LPRM Meters
.d:
~.
DRESDEN UNIT 3 SAFETY RELATED MANTEMANCE September, 1978 l
N!\TURE OF LER OR OUTAGE MALFUNCTION' EQUIPMENT MAINTENANCE NUMBER -'
CAUSE RESULT CORRECTIVE itTION g
Diesel Genera- Preventive WR#6058 NA NA Replaced Inboard & Out-tor Cooling board Bearing Assembliec
! Water Pump i* Diesel Genera- Preventive WRf6050 NA NA Installed New Pump tor Cooling ,
Water Pump G LPRM Input Preventive WR#3513 NA NA Tested Relays & Replaced Relays Bad Relays Main Steam Line Preventive WR#6731 LER-78-33-03L-0 i NA NA Replaced Pointer & -
High Flow Calibrated Switch Switch ,
HPCI Oil PJlter Preventive WR#6939 NA NA Cleaned Filters Assumulator_ Preventive WR#6973 NA .NA' Replaced Packing Nipple 06-15 & Cap "A" Recire Preventive WR#7159 Outage 3-8 NA NA Installed Seal & Tested Pump Hydraulic Preventive WR#7400 Outage 3-8 NA NA Filled Snubbers with Snubbe,rs Oil Drywell Snubber ; Preventive WR#7426 Outage 3-8 .NA NA $ Installed Rebuilt Snubber & Tested Safety Valves Preventive WR#7150 Outage 3-8 ,
, NA NA Removed Lifting # Bail Nuts .
G
-__.,n=----____--__-
DRESDEN UNIT 3 l SAFETY RELATED MANTENANLr_ <eptember, 1978 L .*u_., s rg.,
't ._
NATURE OF LER OR OUTAGE MALFUNCTION d ;
EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION iw V "B" Recirc Corrective WR#7392 Outage 3-8 Loose Packing Water Leakage Tightened Packing & g Pump Discharge Operated Valve ,
Valve C; Drywell Equip. Preventive WR#7153 Outage 3-8 NA NA . Opened Hatch
( Hatch' '
l -~ a LPRM 56-33C Preventive WR#6954 NA NA Replaced LPRM Input Card
~h Reactor Safety Preventive WR#7427 Outage 3-8 '
NA NA '. Replaced Diaphram Valve #203-4F *
/
Drywell Hatch Preventive WR#7154 Outage 3-8 NA NA Closed hatch 9 l Control Rod Preventive WR#7524 Outage 3-8 NA NA Adjusted Stem Drive A-7 (02- . .
- 27) Scram In-
- Let Valve N.
b IRM Channel 13 Preventive WR#5822 Outage 3-8 NA NA Repaired Broken Signal D Wire ,
- IM Outage 3-8 IRM Channel 16 Preventive WR#7050 NA NA Cleaned Connectors & l Remade Input Calbe gv Connector ,,
IRM Channel 16 Preventive WR#7531 Outage 3-8 NA NA Replaced Module With Spare IRM Monitor & 3 Calibrated %
- -_ _ _ , _ _ _ _ __b_ _..
DRESDEN UNIT 3 -
SAFETY RELATED MANTENANCE Septenber, 1978 flATURE OF LER OR OUTAGE MALFUNCT10fl flAINTENANCE NUMBER RESULT' CORRECTIVE /ITION
,; EQUIPMENT '
CAUSE SR11 #21 Penetra- Preventive WR#5990 Outage 3-8 NA- NA Moved Cable & Recalibratec
- tion & Drywell
. Cable 3"A" Recire. Preventive WR#7260 Outage 3-8 NA NA Removed, Tested & Rein-l' ump Seal Purge stalled Check Valve -s Flow Check Valve k 02 Analyzer Preventive WR#7374 Outage 3-8 NA NA Cleaned & Adjusted Flow-rater & Tested IRM Channel 12 Preventive WR#7389 Outage 3-8 NA NA Cleaned Connector
' Vacuum Relief Preventive WR#7614 NA NA Adjusted Limit Switch Valve 3-1601-
-320 LPCI Heat Preventive WR#7576 Outage 3-8 NA NA Checked & Cleaned Con-Exchanger Out- tacts on Breaker let Valve 3A S
4 1
. ___ m _,. . . _ _ _ - . . . - . _ . _ .._ . _ _ _ _. . _ . . . __ _
DRESDEN UNIT 2/3 .i 4
SAFETY RELATED MAINTENANCE September, 1978 ;
MALFUNCTION NATURE OF LER OR OUTAGE
' CORRECTIVE- ACTION EQUIPMENT MAINTEttANCE tiUMBER CAUSE RESULT
-Diesel' Genera- Preventive WR!6871 NA NA Tightened Covers tor Inspection Cover Porthole Gaskets Reactor Recire Preventive WR#2837 NA NA Inspected Seal .
. Pump Seal
' Spare Safety. Preventive WR#6737 NA NA Rebuilt Safety Valve Valve SN#BK 6525-Diesel Genera- Preventive WR#5441 NA NA Installed New Bearings i
tor Cooling & Gasket Water Pump-Stack Gas Preventive WR#7126 NA NA Replaced Vacuum Pump
, Sample Pump "B"' 4 Diesel Genera- Corrective WR#7588 Bad Seals Diesel Generator Disassemblied valve &
tor Failed to Start Replaced.2 seals 125V Battery Preventive WR#1680 NA NA Installed New Breaker Charger Diesel Genera- Preventive WR#7587 NA NA Tested Timer - Tested OK I tor, Control Rod Preventive WR#5223 NA NA Overhauled Control Rod Drives Drives-i i _ .
)
DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE' September, 1978 NATURE OF LER OR OUTAGE MALFUNCTIO!!
flUMBER '
RESULT CORRECTIVE ACTION EQUIPMENT MAINTENANCE CAUSE Spare Safety Preventive WR#11225 NA NA Rebuilt Safety Valve
-Valve SN#6296
' Chimney Stack- Preventive WR#6762 NA NA Rebuilt Pump Gas Vacuum Pump "B" Stack Gas ' Preventive WR#6827 NA NA Replaced Pump Motor Sample Pump Main Stack Preventive WR#6953 NA NA Replaced Discharge <
Gas Sample Needle Valve With Gate System Valve
- Diesel Preventive WR#6723 NA NA Readjusted' Alarm Generator l
'
- Diesel Genera- Preventive WR#5491 NA NA Removed Extra Wire tor Main hearing Low 011 Pressure Alarm Diesel Genera- Preventive WR#6256 NA NA Performed 6 Month In-tot spection 6
g.
,w, . .m .
SUMMARY
OF OPERATING EXPERIENCE UNIT ONE SEPTEMBER, 1978 9 The unit entered the reporting period on line at a power level of approximately 123 MWe and remained there for the full reporting period.
9-30 On September 30 Unit'1 completed 132 days of continuous operation.
l l
SUMMARY
OF OPERATING EXPERIENCE UNIT TWO t
SEPTEMBER, 1978 9-1 .The unit entered the month of September on line.
. 9-13 The unit scrammed at 0034 due to X-area high temperature.
A burnt lug in the breaker for the X-area room cooler fans caused the breaker to trip resulting in the high temperature
- condition. The unit was placed back on line at 2237 hours0.0259 days <br />0.621 hours <br />0.0037 weeks <br />8.511785e-4 months <br /> the same. day.
9-30 The unit finished the reporting period on line.
SUMMARY
OF OPERATING EXPERIENCE UNIT THREE SEPTEMBER, 1978 9-1 The unit entered the month of September on line.
9-15 At 0722 the unit was shutdown to replace the "3A" recircula-tion of inaccessible snubbers was made. .During an attempted turbine startup, a blown fuse in the EIIC system caused the turbine to overspeed which in turn caused the generator hydrogen seal to leak. The seal was reseated and the EHC problemses corrected.
9-23 The unit was returned to service at 1625 and remained there through the end of the reporting period.