ML20147D360

From kanterella
Jump to navigation Jump to search
Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Insp Rept 50-382/87-21
ML20147D360
Person / Time
Site: Waterford 
Issue date: 01/14/1988
From: Callan L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Dewease J
LOUISIANA POWER & LIGHT CO.
References
NUDOCS 8801200148
Download: ML20147D360 (2)


See also: IR 05000382/1987021

Text

. _ _ - _ _ _ _ _ _ _ _ _

.'

E l4 m

,

In Reply Refer To:

Docket:

50-382/87-21

Louisiana Power & Light Company

ATTN:

J. G. Dewease, Senior Vice President

Nuclear Operations

317 Baronne Street

New Orleans, Louisiana

70160

Gentlemen:

Thank you for your letter, dated December 30, 1987, in response to our letter,

dated November 30, 1987. We have no further questions at this time and will

review your corrective action during a future inspection.

Sincerely,

Original Signed By

L L Callan

L. J. Callan, Director

Division of Reactor Projects

,

cc:

Louisiana Power & Light Company

ATTN:

G. E. Wuller, Onsite

Licensing Coordinator

P.O. Box B

Killona, Louisiana

70066

Louisiana Power & Light Company

l

ATTH:

N. S. Carns, Plant Manager

P.O. Box B

'

Killona, Louisiana

70066

Middle South Services

l

ATTN: Mr. R. T. Lally

P.O. Box 61000

'

New Orleans, Louisiana

70161

Louisiana Power & Light Company

i

ATTN:

K. W. Cook, Nuclear Safety and

'

Regulatory Affairs Manager

317 Baronne Street

P.O. Box 60340

New Orleans, Louisiana

70160

Louisiana Radiation Control Program Director

'

bec:

(seenextpage)

()k

$

0:0

l}hoan

g\\

SPE -

LCallan

DHunn utt:cs

J

1/l)./88

1//A/88

1 41) /88

-

8801200148 880114

3DR

ADOCK0500g2

'

.

I

l

Louisiana Power & Light

-2-

Company

bec to DMB (IE01)

bec distrib by RIV:

RRI

R. D. Martin, RA

Section Chief (DRP/A)

DRP

RPSB-DRSS

MIS System

Project Engineer, DRF/A

RSTS Operator

RIV File

J. Wilson, NRR Project Manager

R. Hall

DRS

TSS

Lisa Shea, RM/ALF

.

l

e n

LO UISI AN A / 317 BARONNE STREET

  • p O. BOX 60340

.

(504) 595 3100

POWER & L1GHT

NEW ORLEANS, LOUISIAN A 70160

$00Nbsb

December 30, 1987

W3P87-2242

A4.05

QA

~

U.S. Nuclear Regulatory Corrission

~

@ 2 0W2 p'

ATTN: Document Control Desk

Washington, D.C. 20555

E3l@

"D

Subject: Waterford 3 SES

Docket No. 50-382

License No. NPF-38

NRC Inspection Report 87-21

Attached is the Louisiana Power & Light Company (LP&L) response to

Violation No. 8721-01 identified in Inspection Report No. 87-21.

If you have any questions on the response, please contact G.E. Wuller,

Operational Licensing, at (504) 464-3499.

l

Very truly yours,

l

r

F.J. Drummond

l

l

Nuclear Services Manager

I

l

FJD:GEW:ssf

l

l

Attachment

ec:

R.D. Martin, NRC Region IV

J.A. Calvo, NRC-NRR

J.H. Wilson, NRC-NRR

l

NRC Resident Inspectors Office

l

W.M. Stevenson

l

E.L. Blake

l

l

-

1

l

4 #')so

hg0

>

oY

Y2

l f>'0

N

amu sount opponrustry suptoven"

'

1

.

. . ' . ' , .

Attechnent to

W3P87-2242

Page 1 of 2

,

'

LP&L Response to Violation No. 8721-01

VIOLATION NO. 8721-01

Failure to Evaluate Out-of-Calibration Test Equipment in Timely Manner

10 CFR 50, Appendix B, Criterion XVI, Corrective Action, states, in part,

"Measures shall be established to assure that conditions adverse to quality,

such as failures, malfunctions, deficiencies, deviations, defective

material and equipment, and nonconformances are promptly identified and

corrected."

LP&L Procedure UNT-5-009, "Administrative Procedure Dispositioning of M&TE

Nonconformances," dated October 12, 1986, paragraph 5.5. states, "The M&TE

nonconformance evaluation Condition Identification and Work Authorization

(CIWA) must be completed by the department within 30 days from the date of

identification recorded on the originator section of the M&TE

nonconformance evaluation. The 30-day limit may be exceeded in cases where

retest or recalibration of equipment is necessary to evaluate the

nonconformance." Paragraph 5.15 states, "The Operations Quality Assurance

department shall review the completed evaluation for acceptability and

close out the M&TE nonconformance evaluation."

Contrary to the above, three out of five evaluated nonconformance CIWA's

seiteted by the NRC inspector, were found to have exceeded the 30-day

lim. cation imposed by paragraph 5.5, LP&L Procedure UNT-5-009, as

identified above,

Specific CIWA documents are as follows:

CIWA Documents

Originator Date

Completed,

CIWA 031565

March 9, 1987

September 17, 1987

CIWA 031566

March 9, 1987

May 29, 1987

CIWA 031600

March 30, 1987

May 29, 1987

This is a Severity Level IV violation.

RESPONSE

(1) Reason For The Violation

UNT-05-009 "Dispositioning of M&TE Nonconformances" Section 5.5 states

,

"The M&TE nonconformance evaluation Condition Identification Work

l

Authorization (CIWA) must be completed by the department within 30

days from the date of identification recorded on the originator

section of the M&TE nonconformance evaluation." For the three CIWAs

'

identified in the violation #8721-01, two of the three met this

l

requirement. The specific dates for department evaluation completion

l

are as follows:

l

l

ORIG. SECTION OF

DEPARTMENT

CIWA

THE EVALUATION

EVALUATION COMPLETED

CIWA CLOSED

031565

March 4, 1987

March 9, 1987

Sept. 17, 1987

031566

March 4, 1987

May 7, 1987

May 29, 1987

031600

March 25, 1987

April 22, 1987

May 29, 1987

P

-.

, _ . _

. _ . _

- ,-

.

.

.

'

..

' ' ' ' , '

Attach 2Gnt to

.

W3P87-2242

Page 2 of 2

.

CIWA 031566 did not meet the 30 day limitation as specified in

UNT-5-009.

This CIWA was sent to Nuclear Operations Engineering on

March 9, 1987. The reason for this violation was an inadequate

tracking method ueed to ensure a timely record search completion.

(2) Corrective Actions That Have Been Taken

The Station Information Management System (SIMS) is now employed in

the tracking of M&TE nonconformances.

Each user department is now

responsibic for planning the Work Authorization (WA) within that

department.

A generic work authrrization has been entered into SIMS to provide

consistency in planning by the various depcrtments now responsible for

planning and conducting the evaluations.

SIMS reports are now issued on a weekly basis to all departments thr,t

have record search CI/WAs. This report provides a listing ot' near

term M&TE record c earchea and the responsible groups required to

plan / evaluate them.

The Plant Manager issued letter W3I87-0151 on December 2, 1987, to th.

tasponsible managers explaining the SIMS report, the urgency of timely

evaluation completion, and the sam,le generic work autho71:ation used

for planning. The overdue Records 3earch Evaluations listed in the

Plant Manager's letter have been completed.

(3) Corrective Actions To Be Taken

A proposed revision to UNT-5-009 gives the evaluator the ability to

request an extension in time for performance of the evaluation.

The

reason for the extension will oe documented on the WA along with the

Maintenance Superintendent's approval s'.gnature.

The revision to

UNT-5-009 is scheduled for approval by January 31, 1988.

(4) Date When Full Compliance Will Be Achieved

~

Waterford 3 is in full compliance at this time.

.

L

. _ _ _ _ _ _

___