Amends 128 & 131 to Licenses DPR-44 & DPR-56,respectively, Changing Range Specified for Drywell Temp Indicator & Recorder,Providing Clarifications for Tech Spec Table 3.2.F. & Correcting Error in Table
ML20147B661
Person / Time
Site: Peach Bottom  
Issue date: 02/22/1988
From: Butler W
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20147B664 List:
References
NUDOCS 8803020157
Download: ML20147B661 (14)


Text

..

'o UNITED STATES

~, '

E NUCLEAR REGULATORY COMMISSION j

WASHINGTON, D. C. 20555

%,...../

PHILADEtPHIA ELECTRIC COMPANY PUBLIC SERVICE t.LECTRIC AND GA5 COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-277 PEACH ROTTOM ATOMIC POWER STATION, UNIT NO. 2 AMENDMENT TO FACI',ITY OPERATING LICENSE Amendment No.128 License No. DPR-44 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Philadelphia Electric Company, et al. (the licensee) dated October 24, 1986 as supplemented on Januar.y 22, 1988, complies with the standards and requirements of the Atomi,; Energy Act of 1954, as amended (the Act), and the Cemission's rules and regulations set forth in 10 CFR Chapter I.

B.

The facility will operate in confomity with the application, the l

provisions of the Act, and the rules and regulations of the Comission; t

C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted >rithout endangering the health and scfety of the public, and (ii) t.P.

'"ch activities will be conducted in comoliance with the Comission's regulatwns; 0

The issuance of this amendment will not be inimical to the comon defense and security or t' the health or safety of the public; and E.

The issuance of this unende. ant is in accordance with 10 CFR Part 51 of the Comission's reaulations and all applicable reautrements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachtnent to this license amendinent, and paragraph 2.C(?) of Facility Operatin License No. OPR-44 is hereby amended to read as follows:

8803020157 880222 DR ADOCK 050 27

(2)

Technical Specifications l

The-Technical Specifications contained in Appendices.A and B, as revised through Amendment No.128, are hereby. incorporated in the license. - PEC0 shall operate the facility in accordance with the Technical Specifications.

i

3. - This ' license amendment is effective upon-completion of the modifications-to each device and no later than prior to the beginning of fuel cycle number nine.

FOR THE NUCLEAR REGULATORY COMMISSION

/s/

Walter R. Butler, Director Project Directorate I-2 Division of Reactor Projects I/II

Attachment:

I Changes to the Technical Specifications Date of Issuance: February 22, 1988

[

a RCechmann, 0GC Conc'd on Cover ltr of this am.

on 1/20/88 y,

P(4d$

7N8 OGC PDI-2/D' W WDh

- i EMa tin:mr.

WButler

}

/ /g/88

/ /88 t 69/8 88 t

--~4

- l (2)

Technical Specifications The Technical Specifications contained in Appendices A and 3, as revised threuoh Amendment No. 128, are hereby incorporated in the license. PEL1 shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective upon completion of the modifications to each device and no later than prior to the beginning of fuel cycle number nine.

FOR THE NUCLEAR REGULATORY COMMISSION d

Walter R. Butler, Director Project Directorate I-2 Division of Reactor Projects I/II

Attachment:

Changes to the Technical Specifications Date of Issuance: February 22, 1988 t

ATTACHMENT TO LICENSE AMENDMENT NO.128 FACILITY OPERATING LICENSE NO. DPR-44 DOCKET NO. 50-277 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages. The revised areas are indicated by marginal lines.

Remove Insert 77 77 77a 77a 78a 78a I

i

,,,.n.,

,...,,,,s.,

-c

J

. BAPS Unit 2 P

N e

w w

M M

AA e

e a

M M

MM M

M M

a a

w w

ww w

w w

e e

g A

P e

A A

m e

AA A

=

C N

w w

N N

p NN N

N

.e w

w w

w w

ww w

w m

m O

O e

a a

a a.

m. a.

A a

w e

e e

q w

w w

w w

w w

ww w

w h

h b

8 e

8 6 em 8

ee ee e

  • w O

O es e

$e b g h @

m O

=*

e 06 se eQ O

e eV eV N -

.O

.e Q

D D

d e

O e

a e

O O

ca e

a O OC a

Q Og Om a e O@

s

gg MN e>

C=

0 N

e T +

Ne

  • O N

- e N

N eO eO

.M C

=

M eO e

e a

og OM M=

C i

e C

O O

O g

M

=

ce k

6 L

L b

e G k O h

k 6 0 h

L 6

h e 4 0 k e o C ea e

e e*

e e

6 ee en en se Ve D D

De D

D D

De De De us 6 w 6

6 4 w k

6 6

6 w 6 w 6 w S=

O*

O O

C*

O O

O 0=

0+

e*

GDD uD u

u YD u

u u

aD MD M9

>CC eC e

e eC e

e e

eC eC eC Mme S=

R E

S=

E E

a Em E=

E=

ZO m>

4 P

Zw Ia U S S

Su e

==

m e

NN

=

a Z

e 4

4 em m

O O

g CC C

. =

=

0

  • ee &

S S

Se w

=

4

=

=

44

=

u C

@g e

e

@ eO ww w

sh 2

e Ma M

@M@

4 ea 4 e e

k e e e C e

a e e de N

NC e*

MN s

3 Ne Nm GN@

00 Ca Os 00 No NN s

6 e a s&

a C e # e e@

  • a 00 m

o em e

m e nom en m 6 m

en nM me w

e MM MC M&

MMM em

@C dm Sw C

ww w e w

www ww w

we ww wN ww a

m NN Ne ND NNN gN et se TN ee em D

e e e 6 e e e e e e e e e a 6 e e ae e e M

E=

EQ Em St=

as as 80 km Em Em JJ sw ww

&w

&=

>P

>> wJ 6

w M-

"e.

t W

4 a

e o

e a

e e

4 e

3 3

m O

a

=

=

=

C e

b k e e

e e

e h

9 eO 3

D D

b 3

$C e

e e

e e

e e

=

s ae a

d a

s L

s su a e

es a

3 3

3 3-6 4

L e b

L e

e e

ok e

U W 8 L

ee sa e

e e

sa se g

e e

e C m e== e o

ee eC e Ce Cs ee 80 ee k

6 k O kQ e

ok et t

36 3C 3C &

4 C &e >

-3

-e e

e e

o se aC e

L e Lb b e L

=

= h

=$

=

es ow k

30 0

0 0

=

=

    • =

8h e

G wk we we e

e ee se e be km Wb WD We u 3

BD sc 3

O Ce se e*

e3 e he b3 h

T QD eC eB em e 6

k 3 he 6

4 30 aw sw aw a O

Qw Ow Q

Mk Ma

  • e O==

i ZDC i

ece I

h fw i

e3e j

QbC

-O*C I

C se N

N h

N N

N N

N N

N

  • 6 C&

20=W Ge N

M T

k e

e O.

~

Amendmen t No.,W,)<,,&f, M. 128 e_

~

3 Q.

TABLE 3.2;F (Cont'd) - SuavttttANct_)NSTRUMfMTATION 3

rt 2

Mtalmum No.

P of Operable Type Instrument Indicatton Itom ChanneIe Pereseter Inetrument and Range aegien.

m b3 11 2

Suppresoeen Chamber LR-8(9)123A. B Wecorder 1-29 ft.

(10) (l1)

D Meter Levet leide range) 12 3

Centret med Peettten N/A 23 Vest IndeCating

)

Llehte

)

(1) (2) (3) (4)

)

13 1

Neutron Monttoring M/A Smu. IRM. LPRM.

)

0- 1001L

)

14 3

Safety-aseter Velve PO7M-2(3)-2-7tA-l.

Acevette or (5)

Poe9tton Indicatton TE-7(3)-2-113A-L Thermocouple 15 2

Dry =ett High AR-8(9)t03A. e necorder (7)

Range Redtatton 1-tE(+8) R/hr Monttore

,o i

cn 2>

to t

Metn Stoc., Hi.h..noe

..-7 21 (cre.n..n) neco,de, a

Radletten Montter 3.4E(-2) to 1.4E( 4)vCt/cc (7) c 17 1

neector Suttelne neof RR-7827 (Red Pen U/2) necorder 3

s Vent Hosh mange mentation on-7327 (stue pen u/3) 4.dt(-2) to t.at(.aluct/cc (7) et

-~

j tsentter m

e 18 2

Drywent Hydrogen 2(3185215. 2(J)C3215 Analyser and necorder (t) (2) (3)

Concentratten Anotyrer H2R-4(5)9658 C 0-201L volume and Monster

  • Notes for Tebt" 3.2.P sppear on peces 70 and 78e.

e e

a 1

l i

PBAPS Unit 2 NOTES FOR TABLE 3.2.F (Cont'd) 9)

If no channels are operable, continued operation is permissible during the succeeding 7 days, provided both Drywell Pressure instruments (0-70 psig) are operable; otherwise, restore the inoperable channel (s) to operable status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

10)

With the number of operable channels less than the minimum number of instrumentation channels shown in Table 3.2.F, continued operation is permissible during the succeeding 30 days, provided both narrow range instruments monitoring the same variable are operable; otherwise, restore the inoperable channel to operable status within 7 days or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

11)

If no channels are operable, continued operation is permissible during the succeeding seven days, provided both narrow range instruments n.onitoring the same variable are operable; otherwise, restore the inoperable channel (s) to operable status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

12)

The instrument range may be greater than the range listed in Table 3.2.F provided that (1) the range includes the upper and lowe r range limits specified in Table 3.2.F, and (2) the range does not exceed three times the range specified in Table 3.2.F.

i icendment No. M 128

-78a-j

v " "'W j

4 y

jo, UNITED STATES g

NUCLEAR REGULATORY COMMISSION y

j WASHINGTON, D. C. 20555 f

%g *... s/

PHILADELPHIA ELECTRIC COMPANY PUBLI! SERVICE ELECTRIC AND GAS COMPANY DELMARVA DOWER AND LIGHT COMPANY ATLANTIC CITY ELECTPIC COMPANY DOCKET NO. 50-278 PEAcw norT0" ATCMIC POWER STATION, UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendrent No. 131 License No. DPR-56 1.

The Nuclear Regulatory Canmission (the Commission) has found that:

A.

The apolication for amendment by Philadelphia Electric Company, et al. (the licensee) dated October 24, 1986 as supplemer.ced on January 22, 1988, complies with the standards and r;oufrements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and reculations set forth in 10 CFR Chapter I.

B.

The facility will operate in conformity with the application, the provisions cf the Act, and the rules and regulations of the Commission; C.

There is reascrable assurance (1) that the activities ruthorized by this acerdrent can be conducted without endangering the health and safety of th.i^'4e. trC (ii) that such activities will be conducted in compliarce with the Commission's regulations; D.

The issuance n' this amendment will ret be inimical to the common defense and security or to the health or safety of the public; and F,

The issuance of tnis c"Ardme-+ !c in acccrcar.ce with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordirgly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. DPR-56 is hereby amended to read as follows:

4

. (2)

Technical Specifications

- The Technical Specifications contained in Appendices A and B, as revised through Amendment No.131, are hereby incorporated in the license.

PEC0 shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective upon completion of the modifications to each device and no later than prior to the beginning of fuel cycle number eight.

FOR THE NUCLEAR REGULATORY COMMISSION

/s/

Walter R. Butler, Director Project Directorate I-2 Division of Reactor Projects I/II

Attachment:

Changes to the Technical Specifications Date of Issuance:

February 22, 1988 RBachmann, 0GC conc'd on cover ltr of this am.

on 1/20/88 I-OGC PDI-2/D L

(N f

- tin:mr WButler 88

/ //3/88

/ /88 g/g/88

\\>

. (2)

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.131, are hereby incorporated in the license. PECO shall operate the facility in accordance with the Technical Specifications.

3.

This licenst amendment is effective upon completien of the modifications to each device and no later than prior to the beginning of fuel cycle number etaht.

FOR THE NUCLEAR DEGULATORY COMMISSION

.,b _ Y..,

Walter R. Butler, Director Project Directorate I-2 Division of Reactor Projects I/II

Attachment:

Changes to the Technical Soecifications Date of Issuance: February 22, 19B8

ATTACHMENT TO LICENSE AMENDMENT NO.131 FACILITY OPERATING LICENSE NO. OPR-56 DOCKET NO. 50-278 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages. The revised areas are indicated by marginal lines.

Remove Insert 77 77 77a 77a 78a 78a 1

e

e e

PBAPS UNIT 3 m

N m

G w

w m

a mm a

a m

M M

MM M

M M

m a

w w

ww w

w w

e m

m a

a a

mm a

a C

N w

w N

N NN N

N O

w w

w ww w

w e

a m

w m

O O

m a

a a

am a

a u

a a

e 4

w w

w w

w w

w ww w

w h

h h

b e

e ee 89 0

ee ee aw O

O e6 ok ww e

e 0+

b G k O m

o O

- e O

Go se 6

8 w

e C

aO e

eQ eV h

ea 0

0 a

e D

D

= en e

Q e

O O em a O CD b

G On OM

  • \\

OW s

e a ON e

99 MN e m.

We e

e ca 0

N g a he M

eO e N

  • 4 N

N eO

  1. O
  • M M

eO 4

i Og OM Ma C

C e

a O

O O

e v

M

=

to L

L b

b b

  • O b e b

b b e b

b b

b S b O b 8 wC ee e

e te e

e e

se se Sw ee De D D

De D

D D

De De De UE k u 6

b b u 6

6 6

b u 6 u k u em O*

e 0

0*

O O

O O*

e-9*

ADD uD u

u U1 u

u 6

UD UD UD hCC eC e

e eC e

e e

eC eC eC Mme Em E

E Em E

E E

Em Em Em EO e>

4e Zw E

u.

.u

==

=

e e

e e NN g

Z S

e 4

49 w

O O

T CC C

O

  • es e e

e 84 W

=

4 e

94 u

C

@9 e

i

@ sO ww w

  • h 2

e Ma M

@M@

4 da ee 4

E e e o C a

e e a de N

NC MN J

3 Ne Nm WNd 00 Om Os CO No NN s

6 e e s&

e C e e e ec

  • C se ma CO m

o mm m

me men mm m e a

em mM mm W

e MM MC M&

MMM eM Sh

@C

@M Sw SO C

ww we

=

www ww w

w e ww wN ww E

m NN Ne ND NNN TN SD se TN es SS O

8 e e b e 9 8 e t e e 8 e e b I I e 8 E=

EC EE EEm SE EE EC Em Em Eo sJ sw dw

&w tw JJ h.

N.

M b

b w

e e

s e

e a

a e

e 4

e B

3 P

O m

=

C e

b b e e

e e

a b

e 80 b

3 g

gC e

e e

e e

e e

e s

3 e d

J J

h b

b bu e

e eb 1

m 3

3 3

3-6 4

4 Le b

b e

e e

eb e

u u3 b

ee em e

e e

em et Q

0 e

  • C we em e

e en et E

Ce tb w

ee 90 ee b

b L O bQ e

Ok e6 f

3b 3C 3C &

4C &a >

e 3 w e e

e S

9 Sw eC e

b 8 Lb b e b

  • b
  • E es ow k

Se e O

O

=

eb e

a wb we we e

e ee es e b e be uk ut ue u a

sg sa 3

g he ee se e3 e he h3 h

a eC et et e

b 6 3 6 e b

e 3e Sw Ew Ew E

O C=

Qw Q

$J

.e o**

\\

3DCeee t.

b S

abC

  • owc C

se N

N N

N N

N N

N N

N

-~ Cz seau 1

ee

=

N M

e n

a e

O m

Amendment No. AtT, {T, M, RT,131.

I

e k

T c0 bu 3

(.n C

a 3

_7ABLE 3.2;F (Cont *d) - SuavtgLt,AN(f JNSTRUMfMTATION c4 r+

2 (J

O hinimum No.

of Operable Type Inetrument Inuttetton item Channels Parameter Instrument and Range Actton*

H b)

H tt 2

Suppressten Chamber LR-e(9)t23A, 8 Recorder 1-21 ft.

(10) (tt) water Leven (etd. range) 12 Centret med Peettton N/A 2e vest Indicateng

)

Lighte

)

(1) (2) (3) (4)

I 13 1

Neutron Monttoring N/A SAM, JRW, Lpmu.

)

0-1005

)

14 1

Safety-Rettef Velve POAM-2(31-2-7tA-1.

Acoustic or (5) 2 Poettton Indicatton TE-2(3)-2-113A-L Thermocouple 15 2

OrywatI High RR-6(9)1034, 8 Recorder (7)

Range Redtatton 3-tE(+0) R/hr Monttore 16 main Stock Hteh Range RR-7127 (Green Pen)

Recorder Radiation mentter 1.4E(-2) to 1.4E(+4)uCt/cc (7) 17 1

Reacter Sutiding Roof RR-7127 (Red Pen U/2)

Recorder I

Vent High Range Redletten 9R-7127 (Blue Pen U/3) 1.4E(-2) to 1,4t(ed)uCE/Cc

(?)

meniio, e>

e le 2

Orywell Hydrosen 2(3385215 2(3)C5215 Anetyser end Receeder (4) (2) (3)

Concentrettoo Analyrer H2R-4(5)9658, C 0 - 201L wotume and m ntter o

eNotes for vobie 3.2.P e,prer en paese 7e =ad vea.

)

Unit 3 PBAPS NOTES FOR TABLE 3.2.P (Cont'd) 9)

If no channels are operable, continued operation is permissible during the succeeding 7 days, provided both Drywell Pressure instruments (0-70 psig) are operable; otherwise, restore the inoperable channel (s) to operable status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

10)

With the number of operable channels less than the minimum number of instrumentation channels shown in Table 3.2.F, continued operation is permissible during the succeeding 30 days, provided both narrow range instruments monitoring the same variable are operable; otherwise, restore the inoperable channel to operable status within 7 days or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

11)

If no channels are operable, continued operation is permissible during the succeeding seven days, provided both narrow range instruments monitoring the same variable are operable; otherwise, restore the inoperable channel (s) to operable status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

12)

The instrument range may be greater than the range listed in Table 3.2.F provided that (1) the rar.ge includes the upper and lower range limits specified in Table 3.2.F, and (2) the range dces not exceed three times the range specified in Table 3.2.F.

i Mendment No. M 131