l1AR 21'97 14:45 FR ENERTECH 714 5280128 TO 913018165151 P.02/02 qq l
Solutions for Today. Standards for Tomorrow (714) 528 2301 2950 Birch Street, Brea, CA 928216235
/
FAX (714) 528-0128 o
P2l 9 '] l March 21,1997 l
Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Subject-Potential reportable defect in BW/IP Electro-Hydraulic Actuators, Model number 88500, to properly operate on demand at the McGuire Station.
McGuire is performing a root cause investigation, and is communicating with the hydraulic fluid manufacturer for assistance. Enertech has personnel on-site assisting the McGuire personnel, and is in contact with the actuator manufacturer. BW/IP (acmator manufacturer) is in the process of evaluating this event under their Part 21 program.
It is suspected that the hydraulic fluid temperature inside the plunger area of the solenoid valve exceeded the manufacturers recommendations for continuous operation and effected the performance of the actuator.
)
/k 8
p
- Rgards, l
r
(
/%g
- l F
U. Erlac Pre ' dent 9705300004 970321 l
PDR ADOCK 05000369 S
PDR l