NOTICE OF VIOLATION Commonwealth Ediba Company Docket No. 50-374 As a result of the inspection conducted on October 1 through November 12, 2

1985, and in accordance with the General Policy and Procedure for NRC Enforcement Action (10 CFR Part 2, Appendix C), the following violations were identified:

10CFR50,AppendixB,CriterionIII,asimplementedbyCommonwealthEdison Quality Requirements 3.0, requires that safety-related parts and equipment be reviewed for suitability of application.

Contrary to the above the licensee failed to perform a suitability of application review for replacement parts which were not like for like replacements during the maintenance activities listed below:

1.

The licensee fabricated a spring button and installed same in the Unit 2 Scram Discharge Vent Valve 2C11-380 on August 17, 1985 after the original spring button was found to be broken.

2.

On or about August 20, 1985 the licensee replaced the originally supplied screws on the handle of the Unit 2 2B Diesel Generator cooling water pump breaker, MCC'243-1, with longer screws.

This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this Notice a written statement or i

explanatica in reply, including for each violation: (1) corrective action taken and the results achieved; (2) corrective action to be taken to avoid

-further violation; and (3) the date when full compliance will be achieved.

Consideration may be given to extending your response time for good cause shown.