Notice of Violation from Insp on 970414-18 & 0428-0502. Violations Noted:Periodic Update of USAR Performed on 971012 Did Not Assure Rept Contained Latest Matl Developed & Did Not Provide Correct Info Re Capacity of Fuel Oil Day Tank
ML20141E234
Person / Time
Site: Fort Calhoun Omaha Public Power District icon.png
Issue date: 06/27/1997
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20141E228 List:
References
50-285-97-06, 50-285-97-6, NUDOCS 9707010009
Download: ML20141E234 (2)


Text

.- - . . _ .- . . . .

I ENCLOSURE 1 J

NOTICE OF VIOLATION Omaha Public Power District Docket No.. 50-285 Fort Calhoun Station License No.. DPR-40 4

Curing an NRC inspection conducted on April 14-18 and April 28 through May 2,1997, two violations of NRC requirements were identified. In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG-1600, the violations are listed below:

A. 10 CFR Part 50, Appendix B, Criterion ill, requires that measures shall be established to assure that applicable regulatory requirements and the design basis for those structures, systems, and components to which this appendix appli% are correctly translated into specifications, drawings, procedures, and instructions. The design control measures shall also provide for verifying or checking the adequacy of design, such as, by the performance of design reviews, by the use of alternate or simplified calculational methods, rst by the performance of a suitable testing ,

program. Design control measures shall be applied to items, such as, accident and I l hydraulic analyses.

! Contrary to the above, the measures established by the licensee were not adequate, ,

as evidenced by the following examples:

1. From initial licensing through May 1,1997, the design basis requirements were not correctly incorporated into surveillance test procedure acceptance criteria for the motor-driven auxiliary feedwater pump, the high pressure i safety injection pumps, the containment spray pumps, the low pressure safety injection pumps, and the raw water pumps. Specifically, the 4

acceptance criteria that provided the minimum flow for these pumps was e slightly less than would have been required to mitigate their design basis l accidents.

I

2. On April 5,1997, design control measures were not adequately applied to j the hydraulic analysis calculation for the component cooling water surge tank to assure that following a temperature transient there would be sufficient net positive suction head for the component cooling water pumps.
3. From initial licensing through May 1,1997, a design basis requirement was not correctly incorporated into the technical specifications in that a technical specification limiting condition for operation did not assure that the minimum )

water level in the emergency feedwater storage tank was sufficient to

. mitigate accident scenarios. Specifically, Technical Specification 2.5(2) required 55,000 gallons of water to be availahe in the tank; however, calculations indicated that 55,969 gallons were required to mitigate design basis accidents.

This is a Severity Level IV violation (Supplement l} (50-285/9706-01).

9707010009 970627 PDR ADOCK 05000285 G PDR

l 2-B. 10 CFR 50.71e, requires that the Updated Safety Analysis Report be updated periodically to assure that the information included in this report contains the latest

material developed. ,

! l

( Contrary to the above, the periodic update uf the thdated Safety Analysis Report performed on October 12,1995, did not assure that the report contained the latest j material developed, in that it did not provide the correct information regaiding the l capacity of the diesel-driven auxiliary feedwater pump fuel oil day tank. The l Updated Safety Analysis Report specified that the fuel oil day tank contained l sufficient fuel oil for 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of continuous operation. However, the tank was i routinely maintained at a less-than-tull levsl such that 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of continuous operation would not be obtained ftom the avaitable fuel oilin the tank.

I This is a Severity LevelIV violation (Suppimoent 1)(50-285/9706-03).  !

Pursuant to the provisions of 10 CFR 2.' e01., Omaha Public Power District is hereby required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C. 20505 with a copy to the i

Regional Administrator. Region IV,611 Ryan Plaza Drive, Suite 400, Arlington, Texas j 76011, and a copy to the NRC Resident inspector at the facility that is the subject of this  !

Notice, within 30 days of the oate of the letter transmitting this Notice of Violation (Notice). This reply should be clearly marked as a " Reply to a Notice of Violation" and should include for each violation: (1) the reason for the violation, or, if contested, the I basis for disputing the violation, (2) the corrective steps that ' nave been taken and the results achieved, (3) the corrective stepe that will be taken tu avoid further violations, and  ;

(4) the date when full compliance will be achieved. Your response may reference or )

include previous docketed correspondence, if the correspondence adequately addresses the j required response, if an adequate reply is not received within the time specified in this  :

Notice, an order or a Demand for Information may be issued as to why the licensu should ]

not be modified, suspended, or revoked, or why such other action as may be proper should ]

not be taken. Where good cause is shown, consideration will be given to extending the  ;

response time.  !

'1 Because your response will be placed in the NRC Public Document Room (PDR,, to the l extent possible, it should not include any personal privacy, proprietary, or safeguards 1 information so that it can be placed in the PDR without redaction. However, if you find it l necessary to include such information, you should clearly indicate the speci'ic information ]

that you desire not to be placed in the PDR, and provide the legal basis to support your ]

request for withholding the information frorn the public. j l

l I Dated at Arlington, Texas I this 27th day of June 1997 i