ML20141D659

From kanterella
Jump to navigation Jump to search
Forwards Insp Rept 50-263/97-03 on 970220-0411.No Violations Noted.Insp Revealed That Some Problems Occurred During Maint Activities Which Resulted in Loss of Voltage to Essential Electrical Bus & Starting of Emergency Diesel Generators
ML20141D659
Person / Time
Site: Monticello 
Issue date: 05/09/1997
From: Caldwell J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Wadley M
NORTHERN STATES POWER CO.
Shared Package
ML20141D664 List:
References
50-263-97-03, 50-263-97-3, EA-97-032, EA-97-32, NUDOCS 9705200167
Download: ML20141D659 (3)


See also: IR 05000263/1997003

Text

{{#Wiki_filter:--. - .-. - -_-- .. .. . ._ - - . _ -. . . . . . - - - Mh i !- T&O/ ^ l < 7 i ' r May 9,1997 EA 97-032 Mr. M. Wadley, Vice President Nuclear Generation j Northern States Power Company i 414 Nicollet Mall Minneapolis, MN 55401 SUBJECT: NRC INSPECTION REPORT NO. 50-263/97003(DRP) Dear Mr. Wadley: On April 11,1997, the NRC completed an inspection at your Monticello reactor facility. The enclosed report presents the results of that inspection. During the seven week period covered by this inspection period, your conduct of activities at the Monticello facility was acceptable. Recent Generation Quality Service audit findings demonstrated a good questioning attitude and follow through with identified concerns. ' However, we noted that some problems occurred during maintenance activities. One such , activity resulted in a loss of voltage to an essential electrical bus and starting of emergency diesel generators. Electricians failed to remove a temporarily-installed meter from logic circuitry. In additioni the inspectors identified that the operators were unaware .the #13 emergency service water pump had been operating for two days. This oversight existed through four shift turnovers between three operating crews. This raises concern i over the effectiveness and thoroughness of operator walkarounds and shift turnovers. Our review of the circumstances leading to this event is not complete and will be discussed in a future inspection report. We will contact you in the near future to schedule a management meeting to discuss these and other recent operation and surveillance issues. A predecisional enforcement conference was conducted on March 5,1997, to discuss the ' apparent violation identified in inspection Report No. 50-263/96009 regarding an i inadequate safety evaluation related to ECCS pump configuration (EA 97-032). You will be informed of our decision regarding enforcement action via separate correspondence. !

200039 ll[l[gglll[l[g " 9705200167 970509 PDR ADOCK 05000263 O PDR

i ' . M. Wadley -2- . In accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter and its enclosures will be placed in the NRC Public Document Room. Sincerely,

i Is) 3. e. Gro6s & ' James L. Caldwell, Director - Division of Reactor Projects Docket No. 50 263 License No. DPR-22 Enclosure: Inspection Report No. 50-263/97003(DRP) cc w/ encl: Plant Manager, Monticello s John W. Ferman, Ph.D., Nuclear Engineer, MPCA l State Liaison Officer, State of Minnesota i Distribution: Docket File w/ encl DRP w/ encl PUBLIC IE-01 w/enci Rill PRR w/enci OC/LFDCB w/ encl Project Manager, NRR w/enci SRI Monticello, w/ encl Prairie Island w/ encl A. B. Beach, w/enci Rill Enf. Coordinator, v,/ encl Deputy RA, w/enci CAA1 w/enci (E-mail) TSS w/enci DRS (2) w/enct SEE PREVIOUS CONCURRENCE 1 DOCUMENT NAME: R :\\l N S PR PT S\\PO W E R S\\M O NT\\M O N 97003. D R P To receive e copy of th6e docununt. indicate in the tox *C' = Copy without attachment / enclosure *E" = Copy with attachment / enclosure "N* = No copy OFFICE Rlli } j' Rill Q fill Rllig p s NAME ESchw(bW:ho JJacobsori. }7 HClayton JC W DATE 05/\\ /9Vf 05f\\/97V Q 05/ /97 05/p /97 OFFICIAL RECORD COPY , i ! !

.-. . - . _ _ _ . ._ - . . . _ - - . -- - _ -. - _ .- 9 j I May 9, 1997 1 . 4 Mr. M. Wadley, Vice President Nuclear Generation -

i Northem States Power Company 1 i 414 Nicollet Mall Minneapolis, MN 55401 ' , , i. < I SUBJECT: NRC INSPECTION REPORT NO. 50-263/97003(DRP) ] 1 ! Dear Mr. Wadley: On April 11,1997, the NRC completed an inspection at your Monticello reactor facility. l The enclosed report presents the results of that inspection. i 4 ! During the 7-week period covered by this inspection period, your conduct of activities at ' the Monticello facility was acceptable. Recent Generation Quality Service audit findings 4 i demonstrated a good questioning attitude and follow through with identified concerns. l However, we noted that some problems occurred during maintenance activities in which a ! contributor was a lack of detailed work instructions. One such activity resulted in a loss } of voltage to an essential electrical bus. Electricians failed to remove a temporarily- ) installed meter from logic circuitry. In addition, the inspectors identified that the operators were unaware the #13 emergency service water pump had been operating for 2 days. j This oversight existed through four shift turnovers between three operating crews. This i raises concern over the effectiveness and thoroughness of operator walk arounds and shift turnovers. Our review of the circumstances leading to this event is not complete and will l 2 ' 4 ' be discussed in a future inspection report. We will contact you in the near future to i schedule a management meeting regarding your conduct of operations. ! s

in accordance with 10 CFR 2.790 of the NRC's " Rules of Practice," a copy of this letter and its enclosures will be placed in the NRC Public Document Room. , Sincerely, ' /s/ J. A. Grobe for James L. Caldwell, Director Division of Reactor Projects Docket No. 50-263 License No. DPR-22 l l Enclosure: Inspection Report No. 50-263/97003(DRP) DOCUhENT NAhE: R:UNSPRPTSPOWERIAMONhMON97003.DfP To receive e copy of this doeurnent, indecote in the box 'C' r Copy ethout ettechlenal "E" = Copy wth attachtenci

  • N' = No copy

of90CE Rill M M d ( w b frC- mAME soh m i.e u .6e.n C- [[//p"[ DATE El 19 7 5/ /97 5/ 19 7 - ~~m - }}