ML20141D204
| ML20141D204 | |
| Person / Time | |
|---|---|
| Site: | Millstone, Haddam Neck, 05000000 |
| Issue date: | 03/26/1986 |
| From: | Frank Akstulewicz, James Shea Office of Nuclear Reactor Regulation |
| To: | Opeka J CONNECTICUT YANKEE ATOMIC POWER CO., NORTHEAST NUCLEAR ENERGY CO. |
| Shared Package | |
| ML20141D206 | List: |
| References | |
| IEB-80-11, NUDOCS 8604070443 | |
| Download: ML20141D204 (3) | |
Text
_
y a
March 26,1986 e
Docket No. 50<213/245 DISTRIBUTION p""n 6 3 JPartlow Local PDR FAkstulewicz l
Mr. John F. 0peka, Senior Vice President NRC PDR CGrimes i
Nuclear Engineering and Operations NSIC PAnderson Connecticut Yankee Atomic Power Company ISAP Reading ACRS (10)
Northeast Nuclear Energy Company JShea Post Office Box 270 FMiraglia Hartford, Connecticut 06141 OELD EJordan
Dear Mr. Opeka:
BGrimes
SUBJECT:
SAFETY EVALUATION REPORT FOR MASONRY WALL DESIGN, IE BULLETIN 80-11 Re:
Haddam Neck Plant Millstone Unit 1 By letters dated November 4, 1980, March 3, 1981 and June 26, 1981, Connecticut Yankee Atomic Power Company (CYAPCo) and Northeast Nuclear Energy Company (NNECO) provided information concerning the status of masonry walls at the Haddam Neck Plant and Millstone Unit 1.
By letters dated December 3, 1982, December 31, 1985, February 18 and March 7, 1986, CYAPCo and NNEC0 provided additional responses to staff requests for information.
Based on our review of the CYAPCo and NNEC0 submittals, the staff concludes-that there is reasonable assurance that the safety-related masonry walls at-the Haddam Neck Plant and Millstone Unit I would withstand the specified design load conditions without impairment of either wall integrity or performance of the required safety function. Copies of our Safety Evaluations are enclosed.
This completes our review of masonry wall design at the Haddam Neck Plant and Millstone Unit 1.
Original signed by: F. Akstulewicz Original signed by: James Shea Francis Akstulewicz James J. Shea Integrated Safety Assessment Integrated Safety Assessment Project Directorate Project Directorate Division of PWR Licensing - B Division of PWR Licensing - B
Enclosure:
Safety Evaluation for Haddam Neck Plant Safety Evaluation for Millstone Unit I cc: See Next Page ISAPD:DPL-Bh ISAPD B
I
- PL-B ISAPD
- DPL-B FAkstulewicz:lt JShea n
CGrimes 03/A/86 03/Jj/
03/$f/86 03/$86 8604070443 860326 ADOCK O 3
gDR
4
,o
[
o, UNITED STATES
{
g-NUCLEAR REGULATORY COMMISSION li E
WASHINGTON. D. C. 20555
/
MAR 2 61986 Docket No. 50-213/245 Mr. John F. Opeka, Senior Vice President Nuclear Engineering and Operations Connecticut Yankee Atomic Power Company Northeast Nuclear Energy Company Post Office Box 270 Hartford, Connecticut 06141
Dear Mr. Opeka:
SUBJECT:
SAFETY EVALUATION REPORT FOR MASONRY WALL DESIGN, IE BULLETIN 80-11 Re:
Haddam Neck Plant Millstone Unit 1 By letters dated November 4, 1980, March 3, 1981 and June 26, 1981, Connecticut Yankee Atomic Power Company (CYAPCo) and Northeast Nuclear Energy Company (NNECO) provided information concerning the status of masonry walls at the Haddam Neck Plant and Millstone Unit 1.
By letters dated December 3, 1982, December 31, 1985, February 18 and March 7, 1986, CYAPCo and NNECO provided additional responses to staff requests for information.
Based on our review of the CYAPCo and NNECO submittals, the staff concludes that there is reasonable assurance that the safety-related masonry walls at the Haddam Neck Plant and Millstone Unit I would withstand the specified design load conditions without impairment of either wall integrity or performance of the required safety function. Copies of our Safety Evaluations are enclosed.
This completes our review of masonry wall design at the Haddam Neck Plant and Millstone Unit 1.
@uto uv Francis Akstulew!cz lames J Shea Integrated Safety Assessment Integrated Safety Assessment Project Directorate Project Directorate Division of PWR Licensing - B Division of PWR Licensing - B
Enclosure:
Safety Evaluation for Haddam Neck Plant Safety Evaluation for Millstone Unit I cc: See Next Page
Mr. John F. Opeka Haddam Neck Plant &
Connecticut Yankee Atomic Power Company Millstone Nuclear Power Station, Northeast Nuclear Energy Company Unit No. 1 cc:
Gerald Garfield, Esquire Kevin McCarthy, Director Day, Berry & Howard Radiation Control Unit Counselors at Law Departme'st of Environmental City Place Protection Hartford, Connecticut 06103-3499 State Uffice Building Hartford, Connecticut 06106 Edward J. Mroczka Vice President, Nuclear Operations Board of Selectmen Northeast Utilities Service Company Town Hall Post Office Box 270 Haddam, Connecticut 06103 Hartford, Connecticut 06141-0270 Superintendent State of Connecticut Haddam Neck Plant Office of Policy and Management RFD #1 ATTN: Under Secretary Energy Post Office Box 127E Division East Hampton, Connecticut 06424 80 Washington Street Hartford, Connecticut 06106 Resident Inspector Haddam Neck Plant Richard M. Kacich, Supervisor c/o U.S. NRC Operating Nuclear Plant Licensing East Haddam Post Office Northeast Utilities Service Company East Haddam, Connecticut 06423 Post Office Box 270 Hartford, Connecticut 06141-0270 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 Northeast Nuclear Energy Company ATTN: Superintendent Hillstone Nuclear Power Station P. O. Box 128 ~